175244-BIM-A-0706
28
Unitary Products Group
NOTE 1: HACR Type per NEC.
TABLE 11: WW ELECTRICAL DATA W/POWERED CONVENIENCE OUTLET - STD DRIVE MOTOR (CONT.)
MODEL
(TON-
NAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES
AMPS
-25
(25)
208
42.3
245
2.4
38.6
10.0
None
~
~
~
153.4
175
E18
13.5
1
37.5
153.4
175
E36
27
2
74.9
154.4
175
E54
40.6
2
112.7
201.6
225
E72
54.1
2
150.2
210.9
225
230
42.3
245
2.4
38.6
10.0
None
~
~
~
153.4
175
E18
18.0
1
43.3
153.4
175
E36
36.0
2
86.6
169.0
175
E54
54.0
2
129.9
190.7
225
E72
72.0
2
173.2
234.0
250
460
17.6
125
0.9
19.3
5.0
None
~
~
~
67.9
80
E18
18.0
1
21.7
67.9
80
E36
36.0
2
43.3
84.5
90
E54
54.0
2
65.0
95.3
110
E72
72.0
2
86.6
117.0
125
575
14.5
100
0.6
16.2
4.0
None
~
~
~
55.7
70
E18
18.0
1
17.3
55.7
70
E36
36.0
2
34.6
68.6
70
E54
54.0
2
52.0
77.2
90
E72
72.0
2
69.3
94.5
100
VOLTAGE LIMITATIONS
1
ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
MIN.
MAX.
208
208
1.00
208/230-3-60
187
253
240
230
0.92
460-3-60
414
506
480
460
0.92
575-3-60
518
630
600
575
0.92
1.
Utilization Range “A” in accordance with ARI Standard 110.