York W1LC420 Installation Instruction Download Page 8

CHECKING THE SYSTEM PRIOR TO
INITIAL START UP

With the system piping and electrical wiring completed, the unit
is ready to have electrical power applied. Before applying
power, however, the following checks should be made:

1. Compressor shipping brackets have been removed and

rubber isolators installed.

2. The Return Liquid Temperature Contron (TC) has been

adjusted to the desired Return Liquid Temperature and
Between Stage Differential.

3. The Freeze Control thermostat (FC) has been set to the

proper setting. (Factory setting is 36

°

F.)

4. Fan blades rotate freely.

5. Compressor crankcase oil level shows 1/3 to 1/2 in sight

glass.

6. Suction, discharge and liquid line king valves, located in the

compressor section, are open. There are two systems in
these units and each system employs one of these valves.

CAUTION: Suction, discharge and liquid line valves are

shipped closed.

7. The power supply voltage is the same as the unit name-

plateu voltage.

8. Proper fuses are in main disconnect power circuits.

APPLYING POWER TO THE UNIT

CAUTION With the preceding steps completed, make sure

the DAY/NIGHT switch is in the NIGHT or UNOC-
CUPIED position or the unit will start immediately
and compressor damage may occur.

1. The main power disconnect switch may now be turned ON.

CAUTION: Check to insure that the compressor crankcase

heater is energized. Allow at least 24 hours
warm-up to allow all liquid refrigerant to be
driven from the compressors. After warm-up,
the crankcase should be warm to the touch.

2. Start the chilled water circulating pump. Assure that the flow

rate is approximately correct by checking the water pres-
sure drop across the cooler with the data shown in Table 5.

3. Check that the liquid freeze prevention thermostat (FC)

does not need to be reset. It may have tripped if the unit
was exposed to low outdoor temperatures during shipment.

4. Turn the DAY/NIGHT switch to the DAY or OCCUPIED

position. If the water flow switch is closed, the unit will start
after the required time delays built into the control circuit,
provided the return liquid temperature is warm and the
temperature control (TC) is calling for cooling.

5. Allow the unit to operate, but be ready to stop the unit should

any unusual noise or other adverse condition develop.

NOTE: Opening the DAY/NIGHT switch will only shut the

unit off after completion of the pumpdown cycle.

Turning OFF the main power supply will stop the
unit immediately.

6. To determine if the unit is operating properly, the refrigerant

subcooling and superheat should be checked.

SEQUENCE OF OPERATION

NOTE:

The contact opening and closing times for 50 HZ
units are 5/6 of those listed for 60 HZ units.

System start-up and staging is controlled by the TC  which is
energized through the day/night switch, optional field installed
pump aux. contact, FC  and WFS. The FC  opens below 36

°

F

leaving water temperature and closes above 42

°

F with manual

reset. The WFS  closes at water flow rates above 55 GPM. The
TC  is a solid state thermostat which maintains the desired
chilled (supply) liquid temperature by sensing and regulating
the return liquid temperature (see the ELECTRICAL CON-
TROLS section). It employs an encapsulated thermistor lo-
cated in a well in the return liquid line.

NOTE: The timing intervals described in the following proce-

dure are nominal. Some variations will naturally occur
due to differences in individual components, ambient
temperature, or line/control voltage.

COMPRESSOR NO. 1 OPERATION

When the first stage of the TC  calls for cooling.:

1. TC-1  closes and energizes relay 16R. 16R-1  will energize

compressor protector module MP, and after a 2 minute time
delay 1MP contacts  will close. Contact 16R-3  closes
energizing contactors 1M, 5M, relays 1R, 20R, and timer
1TR. 16R-2  energizes liquid line solenoid valve 1LLS, and
liquid refrigerant will flow to the expansion valve.

2. Relay 1R contacts close, with 1R-1 and 1R-2 closing in

parallel with contacts 16R-1 and 16R-3 respectively main-
taining operation during the pumpdown cycle.

3. Contactor 1M energizes compressor #1, and contactor 5M

energizes the condenser fans #1, #2 and #3. Contact 20R
opens to de-energize compressor crankcase heater 1CCH
while the compressor runs.

4. After 2 minutes, low pressure bypass timer 1TR-1 opens.

If the compressor suction pressure remains abnormally low
after initial start-up, the compressor circuit will lock out as
described in the HIGH / LOW PRESSURE LOCKOUT
section.

When the second stage of the TC calls for cooling:

1. Contacts TC-3 will close to energize relay 4R, and con-

denser fan No. 2 will start up, providing the temperature of
the outdoor air is above the 45

°

F set point of thermostat

2TH.

2. Contact TC-4 will open to de-energize compressor solenoid

valve 2SOL, and the 20 ton compressor will operate at full
capacity.

OPERATION

570.05-N4Y

8

Unitary Products Group

Summary of Contents for W1LC420

Page 1: ...referenced in this instruc tion may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York Pa 17405 INSPECTION As soon as a unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A separate request for inspection by the carrier s agent should be made in...

Page 2: ... 10 Condenser Fan Motor Control 10 Electric Controls 11 MAINTENANCE General 12 Cleaning Condenser Surface 12 Lubricating Fan Motors 12 Compressor Replacement 12 Secure Owner s Approval 12 TABLES No Description Page 1 Application Data 3 2 Physical Data 4 3 Electrical Data 6 4 Electrical Data International Models 6 5 Water Side Pressure Drop 6 FIGURES No Description Page 1 Unit Handling 3 2 Support ...

Page 3: ... location should be selected for minimum sun exposure and to insure an adequate supply of fresh air for the condenser Avoid locations beneath windows or between struc tures where normal operating sounds may be objectionable The condenser fans are propeller type and are not suitable nor intended for use with duct work in the condenser air stream On either rooftop or ground level installations rubbe...

Page 4: ...move the compressor hold down nuts and shipping spac ers Install rubber grommets shipped in bag tied to compressor Replace the hold down nuts and tighten until they start to bind the rubber grom mets Continue to tightened additional half turn See Figure 3 DISCHARGE LINE HOLD DOWN BRACKET CAUTION Do NOT remove the discharge line support brack ets located within the compressor compartment It reduces...

Page 5: ...ut located on the bottom of the electrical box Remove the plastic plug from the knockout and discard See Table 3 or 4 for electrical data The disconnect switch may be bolted to the side of the unit but not to any of the removable panels this would interfere with access to the unit Make sure that no refrigerant lines or coils will be punctured when mounting the disconnect switch and note that it mu...

Page 6: ...LC420 A50 380 415 3 50 2 38 0 each 1651 each 380 415 1 50 3 4 4 2 2 3 2 5 105 110 2 320 380 368 415 A40 380 3 60 2 52 1 each 208 each 460 1 60 3 4 4 2 2 3 2 5 135 150 0 377 W1LC530 A50 380 415 3 50 1 1 38 0 62 7 1651 2252 380 415 1 50 3 4 5 2 2 3 2 5 135 150 0 369 380 412 415 A40 380 3 60 1 1 52 1 77 8 208 307 460 1 60 3 4 5 2 2 3 2 5 170 200 00 357 1100 Amps on part winding start 4Based on three ...

Page 7: ...GHT Lbs Oper Dry W1LC420 10 x 7 4 13 72 1 2 12 7 8 26 800 700 W1LC530 10 x 7 4 13 72 1 2 12 7 8 26 800 700 Nominal pipe size victaulic type COOLER DIMENSIONS WEIGHTS FRONT 36 BACK 24 LEFT SIDE 24 RIGHT SIDE 24 TOP 120 One side only NOTE The area within the clearances shown above and area under the unit must be kept clear of all obstructions that would impede free air flow to the unit In installati...

Page 8: ... off after completion of the pumpdown cycle Turning OFF the main power supply will stop the unit immediately 6 To determine if the unit is operating properly the refrigerant subcooling and superheat should be checked SEQUENCE OF OPERATION NOTE The contact opening and closing times for 50 HZ units are 5 6 of those listed for 60 HZ units System start up and staging is controlled by the TC which is e...

Page 9: ...ressor crankcase heater 2CCH while the compressor runs 4 After 2 minutes low pressure bypass timer 5TR 1 opens If the compressor suction pressure remains abnormally low after initial start up the compressor circuit will lock out as described in the HIGH LOW PRESSURE LOCKOUT section When the fourth stage of the TC 81 calls for cooling 1 Contacts TC 7 will close to energize relay 11R and 12R 2 When ...

Page 10: ...e drops below 180 psig high pressure con trol 2HP will close to energize relay 3R When contact 3R 1 opens and contact 3R 2 closes condenser fan 3 will be powered through choke coil 1CH and its speed will drop to 450 RPM Timer 3TR will remain open for 10 seconds after unit start up so the condenser fan 3 will always start at high speed NO 2 20 TON SYSTEM Under 65 F the 4 condenser fan will shut off...

Page 11: ... 100 capacity All temperatures considered are for a TC 6A control and thermistor working at design conditions Allowable toler ances could change the actuation temperatures by 1 25 F With the RETURN water temperature to the cooler rising due to increasing cooling load for the application the 1 compres sor will start at part load when the RETURN water temperature reaches 47 75 F The LEAVING water te...

Page 12: ... means Take care so as not to damage or bend the condenser fins LUBRICATING FAN MOTORS The condenser fan motors are equipped with factory lubricated and sealed ball bearings requiring no maintenance COMPRESSOR REPLACEMENT Obtain replacement compressors or parts from your local Copeland Wholesaler See Instruction Form 55 72 RD2 2 for replacement compressor reference data SECURE OWNER S APPROVAL WHE...

Reviews: