SECTION 4 - CYCLING SHUTDOWNS
FORM 160.00-O4
ISSUE DATE: 07/31/2019
4
MESSAGE
DESCRIPTION
Harmonic Filter
Communications
IEEE-519 FILTER FAULT
This shutdown states that the hardware on the harmonic filter logic board is indicat
-
ing a fault, but the software on the harmonic filter logic board does not state why.
The harmonic filter logic board signals a fault condition to the OSCD logic board
but does not respond to a software request for fault information.
Harmonic Filter - Logic Board
Power Supply
FLTR POWER SUPPLY FLT
This shutdown indicates that one of the low voltage power supplies on the harmon-
ic filter logic board have dropped below their permissible operating voltage range.
The harmonic filter logic board receives its power from the OSCD logic board. The
power supplies for the OSCD logic board are in turn derived from the secondary of
the 120 to 24 VAC transformer.
Harmonic Filter - Low DC Bus
Voltage
FLTR LOW BUS VOLTAGE FLT
The harmonic filter dynamically generates its own filter DC link voltage by the inter
-
action of the harmonic filter inductor and switching its transistors. This DC level is
actually higher than the level obtained by simply rectifying the input line voltage.
The DC link voltage is always higher on
the harmonic filter power unit then on the
OSCD VSD power unit.
Thus the harmonic filter actually performs a voltage “boost” function. This is neces
-
sary in order to permit current to flow into the AC line from the harmonic filter when
the AC line is at its peak level. This particular shutdown and its accompanying
message are generated when the harmonic filter’s DC link voltage drops to a level
less than 80 VDC (for 380 through 460 VAC input voltage), 110 VDC (for 424 HP)
and 140 VDC (for 575 VAC input voltage 608 HP) below the harmonic filter DC link
voltage setpoint.
Harmonic Filter - Phase
Locked Loop
FLTR PHASE LOCK LOOP FLT
This shutdown indicates that a circuit called a “phase locked loop” on the harmonic
filter logic board has lost synchronization with the incoming power line for a period
of time.
Harmonic Filter - Precharge -
Low DC Bus Voltage
FLTR PCHARGE LOW BUS V FLT
Two minimum voltage thresholds must be met in order to complete the precharge
cycle. The first occurs 1/10th of a second after pre-charge is initiated and the other
occurs 5 seconds after precharge is initiated. See table below for specific values.
NOMINAL INPUT
VOLTAGE VALUE
1ST MINIMUM
VOLTAGE VALUE
2ND MINIMUM
VOLTAGE VALUE
380-460 VAC
41 VDC
425 VDC
575 VAC
60 VDC
630 VDC
Harmonic Filter - Run Signal
FLTR RUN RELAY FLT
When a digital run command is received at the harmonic filter logic board from the
OSCD logic board, a 1/10 second timer is started. A redundant run command must
also occur on the communication link from the OSCD logic board before the timer
expires or the OSCD will be shut down.
TABLE 4 -
CYCLING SHUTDOWN MESSAGE (CONT'D)
Summary of Contents for VSD 292
Page 30: ...JOHNSON CONTROLS 30 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 34: ...JOHNSON CONTROLS 34 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS 42 FORM 160 00 O4 ISSUE DATE 07 31 2019...