SECTION 4 - CYCLING SHUTDOWNS
MESSAGE
DESCRIPTION
Harmonic Filter - 110 % Input
Current Overload
FLTR OVERLOAD FLT
The three phases of RMS filter current are measured by the output DCCTs’. This
information is sent to the harmonic filter logic board. If any one phase of filter cur
-
rent exceeds a threshold for 40 seconds a shutdown will occur. Refer to the chart
below for the shutdown threshold value.
DRIVE HP RATING
THRESHOLD SHUTDOWN VALUE
270, 292, 351
128 Amps
424
138 Amps
385, 419, 503
176 Amps
608 (575 VAC)
190 Amps
608 (400 VAC), 658, 704, 790
278 Amps
868, 882, 914, 917, 948, 1055
385 Amps
Harmonic Filter - DC Bus
Voltage Imbalance
FLTR BUS V IMBALANCE FLT
The DC link is filtered by many large capacitors. These capacitors are connected
in series to achieve a higher DC link voltage then can be supported by a signal
capacitor. It is important that the voltage is shared equally between the two sets of
series capacitors. Each set of capacitors must share approximately 1/2 of the total
DC link voltage. The harmonic filter logic board then measures the voltage of the 2
sets of the bus capacitors. If at anytime while the harmonic filter is running that the
difference in the voltage between the 2 sets of capacitors is greater than 50 VDC
(for 380 through 460 VAC input voltage) 65 VDC (for 575 VAC input voltage), then
a shutdown will occur.
Harmonic Filter - DC Current
Transformer 1 (or 2)
FILTER DCCT 1 (OR 2)
ERROR
During initialization, with no current flowing through the Direct Current Current
Transducers (DCCTs), the DCCT’s output voltages are measured and compared
with a preset limit in the harmonic filter logic board. If the measured values exceed
the preset limits, the DCCTs are presumed to be bad and this shutdown will be
generated.
Harmonic Filter - High DC
Bus Voltage
FLTR BUS OVER-VOLTAGE FLT
The harmonic filter logic board continuously monitors the harmonic filter DC link
voltage if the level of the DC link voltage exceeds a range of 822 to 900 VDC (for
380 through 460 VAC input voltage) or 999 to 1099 VDC (for 575 VAC input volt-
age) this shutdown is initiated. Keep in mind that the harmonic filter has its own
DC Link as part of the harmonic filter power unit. The harmonic filter DC Link is not
connected in any way with the drive’s DC Link.
Harmonic Filter - High Phase
A (or B, C) Current
FLTR PHASE A (B, C)
OVERCURRENT
The output current of the harmonic filter is read by the Direct Current-Current
Transducer (DCCT). This current information is sent to the harmonic filter logic
board where it is compared against a threshold. If the output current of the har-
monic filter power unit is greater than the threshold, then the harmonic filter will turn
off for 5-6 line cycles. After that time the filter operation will resume. If the harmonic
filter operation is stopped 3 times within a period of 60 line cycles, then the filter
and VSD power units are shut down and this message is generated.
DRIVE HP RATING
THRESHOLD SHUTDOWN VALUE
270, 292, 351, 424
378 Amps Peak
385, 419, 503, 608 (575 VAC)
523 Amps Peak
608 (400 VAC), 658, 704, 790
781 Amps Peak
868, 882, 914, 917, 948, 1055
1225 Amps Peak
TABLE 4 -
CYCLING SHUTDOWN MESSAGE (CONT'D)
Summary of Contents for VSD 292
Page 30: ...JOHNSON CONTROLS 30 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 34: ...JOHNSON CONTROLS 34 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS 42 FORM 160 00 O4 ISSUE DATE 07 31 2019...