background image

JOHNSON CONTROLS

10

FORM 145.05-SU2 (1207)

COOLING SUPPLY AIR TEMPERATURE CONTROL

This feature allows the unit to control the staging of 

the compressors based on the difference between the 

supply air temperature and the supply air temperature 

set point.

Field Wiring

None required.

Programming

The following items must be programmed through the 

Setpoints

” section of the User Interface:

• 

“AC-S/A Temp En”

 must be set to ON. Default 

is ON.

• 

“AC/Econ-S/A SP”

 set point must be pro-

grammed.  The default value is 55.0˚ F.  This 

is the supply air temperature the unit will try to 

maintain.

C O O L I N G   R E T U R N  A I R   T E M P E R AT U R E 

CONTROL

This feature allows the unit to control the staging of 

the compressors based on the difference between the 

return air temperature and the return air temperature 

set point.

Field Wiring

None required.

Programming

The following items must be programmed through the 

Setpoints

” section of the User Interface:

• 

“AC-R/A Temp En” 

must be set to ON.  Default 

is OFF.

• 

“AC/Econ-R/A SP”

 set point must be pro-

grammed.  The default value is 75.0˚ F.  This 

is the return air temperature the unit will try to 

maintain.

COOLING SUPPLY AIR AND RETURN AIR 

TEMPERATURE CONTROL

This feature allows the unit to control the staging of the 

compressor based on either the temperature difference 

between the supply air temperature and the supply air 

temperature set point and the return air temperature 

and the return air temperature set point.  When both are 

selected the compressors will be cycled based on the 

lesser of the two differences.

Field Wiring

None required.

Programming

The following items must be programmed through the 

Setpoints

” section of the User Interface:

• 

“AC-S/A Temp En”

 must be set to ON.  Default 

is ON.

• 

“AC/Econ-S/A SP” 

set point must be pro-

grammed.  The default value is 55.0˚ F.  This 

is the supply air temperature the unit will try to 

maintain.

• 

“AC-R/A Temp En”

 must be set to ON.  Default 

is OFF.

• 

“AC/Econ-R/A SP”

 set point must be pro-

grammed.  The default value is 75.0˚ F.  This 

is the return air temperature the unit will try to 

maintain.

SUPPLY FAN OPERATION

This feature tells the unit if is has a constant volume or 

variable volume supply fan.

Field Wiring

None required.

Programming

The following item must be programmed through the 

Setpoints

” section of the User Interface:

• 

“Fan-VAV/CV En”

 must be set to VAV.  The 

default is VAV.

FLEXSYS

Summary of Contents for VERSECON YSWD Series

Page 1: ...AIR CONDITIONING UNITS New Release Form 145 05 SU2 1207 VERSECON Indoor Upflow Self Contained Air Conditioner YSWU 10 105 Ton Water Cooled Indoor Downflow Self Contained Air Conditioner YSWD 10 105 T...

Page 2: ...ls This individual will also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in...

Page 3: ...t YORK Applied Systems Service office It is the responsibility of operating service personnel to verify the applicability of these documents to the equipment in question If there is any question in th...

Page 4: ...SUPPLY AIR AND RETURN AIR TEMPERATURE CONTROL 8 SUPPLY FAN OPERATION 9 SUPPLY FAN DUCT STATIC PRESSURE 9 FLEXSYS 10 COOLING SUPPLY AIR TEMPERATURE CONTROL 10 COOLING RETURN AIR TEMPERATURE CONTROL 10...

Page 5: ...d by the User Interface should be diagnosed as referenced in the Installation Operation and Maintenance manual refer to Faults and Alarms in the Service section of the manual QUICK START GUIDE VERSECO...

Page 6: ...t Connect the wire of a shielded twisted pair to the terminal of the Network Port Programming Go to the Daily Sched section of the User Interface Change the Daily Schedule Status to OFF CONDENSER WATE...

Page 7: ...e return air temperature the unit will try to maintain COOLING SUPPLY AIR AND RETURN AIR TEMPERATURE CONTROL This feature allows the unit to control the staging of the compressor based on either the t...

Page 8: ...Temp En must be set to ON The default is OFF AC Econ R A SP set point must be pro grammed The default value is 75 0 F This is the return air temperature the unit will try to maintain COOLING SUPPLY AI...

Page 9: ...C The default value is 1 0 WC of SPSensors The control has the capability to use one or two duct static sensors If a single sensor is used this value would be set to 1 If two sensors are used this val...

Page 10: ...temperature the unit will try to maintain COOLING SUPPLY AIR AND RETURN AIR TEMPERATURE CONTROL This feature allows the unit to control the staging of the compressor based on either the temperature di...

Page 11: ...ed to Avg the control will compare the average of the two sensors to the Fan S A Pres SP and control the speed of the VFD based on these values SUPPLY AIR PROVING SET POINT The Unit Control monitors t...

Page 12: ...of the User Interface AC S A Dew En must be set to ON FLEXSYS DEW POINT TEMPERATURE CONTROL AC S A Dew Min set point must be pro grammed The default value is 48 0 F This is the lowest supply air tempe...

Page 13: ...a return air temperature The default value is OFF Econ Valve Min This parameter establishes the minimum position of the water side econo mizer valve The parameter can be set between 0 and 100 The defa...

Page 14: ...A Econ En This parameter must be set to ON The default value is OFF Econ S A Tmp En This parameter must be set to ON if you want the water side economizer to be controlled by a supply air temperature...

Page 15: ...1 Heat R A Tmp En must be set to ON The default is OFF Heat R A Tmp SP set point must be pro grammed It can be set between 40 0 F and 90 0 F The default value is 72 0 F This is the return air tempera...

Page 16: ...value is 72 0 F This is the return air temperature the unit will try to maintain Tele 800 861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed...

Reviews: