Note 1: Complete York ERV model number includes the electrical information. Example DM 060

needing 800 CFM outside of air at 230 volts/3 phase. Model would be a VP011A06H2AAA1.

2: Predator models D/B*078-150, with ERV must use “slab” type economizers and downflow position.

TABLE 4: PERFORMANCE - PIVOTING WHEEL MODELS

“P” Series Pivoting Wheel for Units with Economizers

York

Packaged Unit

Model No.

Unit 
Size 

(Tons)

ERV

CFM

Range

Max.
CFM

Power

Exhaust

Matching 

ERV

Model

Voltage &

Phase

Voltage 

Code

Nominal ARI Data (Total

CFM

Net Effectiveness

Heating

Cooling

DM 036-072

DF 036-072

DH 036-060
BQ 036-060

3 - 6

600-

1000

1900

VP011A06H

208/230v-1ph

9

900

73%

72%

208/240v-3ph

2

460v-3ph

4

575v-3ph

5

DM 090-102

DF 090-102

DH 078-102

BP 090

(See note 2)

7.5 - 8.5

600-

1000

1900

VP011B12H

208/230v-3ph

2

900

73%

72%

460v-3ph

4

575v-3ph

5

1100-

1700

3000

VP020B12H

208/230v-3ph

2

1600

65%

64%

460v-3ph

4

575v-3ph

5

DM 078

DM 120-150

DF 078

DF120

DH 120-150

DJ 150

DR 090-150

BP 078

BP 120-150

(See note 2)

7.5 - 
12.5

600-

1000

1900

VP011A12H

208/230v-3ph

2

900

73%

72%

460v-3ph

4

575v-3ph

5

1100-

1700

3000

VP020A12H

208/230v-3ph

2

1600

65%

64%

460v-3ph

4

575v-3ph

5

1500-

2200

3450

VP028A12M

208/230v-3ph

2

1950

71%

70%

460v-3ph

4

575v-3ph

5

2200-

2800

4200

VP028A12H

208/230v-3ph

2

2600

65%

63%

460v-3ph

4

575v-3ph

5

FIGURE 3 - “P” SERIES PIVOTING WHEEL FOR UNITS W/ECONOMIZERS

Enthalpy Wheel

(with removable pie 
segments)

Exhaust

Air Blower

(energized)

Outside

Air Blower

(energized)

Exhaust

Air Blower

Fresh Air Damper

(opens during economizer 
operation)

Unit & UERV Disconnect 

(provided correct wire size used 

for both units  and 

local code approval

)

Enthalpy Wheel 

Pivoted out of  Intake and 

Discharge Air Stream

Summary of Contents for V* Series

Page 1: ...omizermode when outside sensorcallsfor economizer operation 3 12 5 ton packaged units equipped with economizers U S Patent 5 548 970 Pivoting wheel models used with packaged unit with econo mizer Sequ...

Page 2: ...078 THROUGH 150 18 7 UERV DIMENSIONAL DATA 180 THROUGH 300 18 8 MILLENNIUM UNIT VR074 AND VR122 19 9 STAND ALONE UERV S FOR SIDE BY SIDE DUCT ARRANGEMENTS 21 10 STAND ALONE UERV S FOR OVER AND UNDER...

Page 3: ...P DU L 20 064 080 092 Z05 P UR P XU PXU V 16 075 Z05 P UR P XU PXU V 20 095 Y05 P UR P XU PXU V 20112 130 X05 P DH P XD V 20 075 V05 N AH N VS B G2FD 14 20 048S 060S 061H Z03 P HU P DU P DU V P HU P D...

Page 4: ...ecovery ven tilators This standard deals specifically with the ratings of the Energy Recovery Wheel that is incorporated into the Energy Recovery Ventilator ERV All of the York ERV s have an ARI certi...

Page 5: ...rning to the space This is not contami nated air as some would suggest It is however air that effectively never left the space The operation cost of moving this air is far less than that required for...

Page 6: ...op Start Jog SSJ M3 MOA SSJ and Pressure Sensor PS M4 MOA and PS S1 Stop Start Jog SSJ S2 SSJ and Pressure Sensor PS P1 Pressure Sensor PS NOTE denotes only options available for VR074 VR122 HOW TO SE...

Page 7: ...018 060 D NP 024 048 D NZ 024 060 1 5 5 300 550 VR006A05H 110v 1ph 1 500 65 64 208 230v 1ph 9 208 240v 3ph 2 460v 3ph 4 DM 036 072 DF 036 072 DH 036 060 BQ 036 060 3 6 300 550 VR006A06H 110v 1ph 1 50...

Page 8: ...2200 VR028A15M 208 230v 3ph 2 1950 71 70 460v 3ph 4 575v 3ph 5 2200 2800 VR028A15H 208 230v 3ph 2 2600 65 63 460v 3ph 4 575v 3ph 5 2800 3600 VR036A15H 208 230v 3ph 2 3100 65 63 460v 3ph 4 575v 3ph 5 3...

Page 9: ...78 102 BP 090 See note 2 7 5 8 5 600 1000 1900 VP011B12H 208 230v 3ph 2 900 73 72 460v 3ph 4 575v 3ph 5 1100 1700 3000 VP020B12H 208 230v 3ph 2 1600 65 64 460v 3ph 4 575v 3ph 5 DM 078 DM 120 150 DF 07...

Page 10: ...Cooling 65 Curb A C Unit Curb Height in Shipping Weight lbs Net Weight lbs Note 1 A stepdown transformer is provided to stepdown high voltage primary to 115 volt secondary 10 1 59 9 90 500 6 2 1 02 0...

Page 11: ...w Cooling 81 73 72 67 70 100 Airflow Heating 76 68 68 61 65 75 Airflow Heating 81 73 72 67 71 100 Airflow Cooling 76 68 68 61 64 75 Airflow Cooling 81 73 72 67 70 Curb A C Unit Curb Hgt in Shipping We...

Page 12: ...2 4 Full Load Amps Pivoting 9 4 4 3 6 Service Factor 1 15 1 15 Wheel Electrical Data Motor hp 1 phase 0 17 0 17 Potential Volts 200 208 230 200 208 230 Motor Speed rpm 1725 1725 Full Load Amps 1 1 1 1...

Page 13: ...0 50 Potential Volts 200 208 230 200 208 230 Motor Speed rpm 1725 1725 Full Load Amps 2 7 2 7 Total Electrical MCA Stationary 22 4 10 9 8 4 16 1 18 6 6 6 OCPD Stationary 30 15 9 20 12 9 Wheel Data Whe...

Page 14: ...0 5 Potential Volts 200 208 230 200 208 230 Motor Speed rpm 1150 1150 Full Load Amps 1 2 1 2 Total Electrical MCA Stationary 34 5 17 12 22 11 8 7 OCPD Stationary 40 25 15 30 15 12 Wheel Data Wheel Dep...

Page 15: ...otential Volts 200 208 230 200 208 230 Motor Speed rpm 1075 1075 Full Load Amps 1 2 2 7 Total Electrical MCA Stationary 36 8 17 5 13 6 34 5 17 12 7 OCPD Stationary 50 25 20 40 25 15 Wheel Data Wheel D...

Page 16: ...7 52 22 6 19 OCPD 50 20 15 70 30 25 Wheel Data Wheel Depth x Diameter in 3 x 58 3 x 74 Construction Media Type Segmented Pies Polymeric Segmented Pies Polymeric Enthalpy Wheel Airflow Data Nominal Air...

Page 17: ...B HA HH HP 018 060 Optional Eqpt Support Exhaust Blower Outdoor Air Intake Blower Enthalpy Wheel A B C D VR006B05H VR006A05H B HA HH HP 018 060 FIGURE 5 UERV DIMENSIONAL DATA 036 THROUGH 072 14 High C...

Page 18: ...851 44 75 1137 60 38 1533 600 1000 1100 1700 37 25 946 37 5 953 FIGURE 7 UERV DIMENSIONAL DATA 180 THROUGH 300 Model Number Unit Size A B C D CFM 1500 2200 180 300 180 180 300 180 180 300 180 180 300...

Page 19: ...the ERV Exhaust Blowers See blower performance charts for airflow at various external static pressures FIGURE 8 MILLENNIUM UNIT VR074 AND VR122 74 75 24 59 61 23 82 13 20 92 Model Number CFM Descript...

Page 20: ...CFM 6000 910 1060 1200 1300 1400 6500 955 1095 1225 1360 1430 7000 1000 1130 1260 1380 1475 7500 1040 1170 1290 1400 1500 8000 1080 1200 1315 1425 1530 RPM Range Low 910 1320 Standard Unit High 1325...

Page 21: ...Roof curbs are available for the UERV s 5 CFM at 0 0 external static pressure Series Model Number VS006 1RC0480 VS011 VS020 VS028 VS036 VS046 VS062 300 550 23 25 x 32 5 34 69 24 75 24 63 8 00 20 00 2...

Page 22: ...12 00 27 00 Features and Notes 4 Roof curbs are available for the UERV s 600 1000 UERV with Horizontal Ductwork UERV Roof Curbs Dimensional Data UERV Data 2 60 5 00 2 56 11 00 18 32 39 50 8 00 3 59 18...

Page 23: ...side for access Dimensions 4 Static test ports are provided for verification of CFM 5 Filter rack accepts 1 or 2 filters and comes with flex connector to air handler Features 3 Access panels located o...

Page 24: ...urn Series for 600 1 000 CFM UERV for Ducted Applications The U11 ducted series is designed intake and exhaust air is ducted to the UERV Applications with long duct runs may require booster fans Duct...

Page 25: ...XU P XU V 20 112 130 Upflow Only P DH P XD V 16 075 VH 006 X05H Horz Only P DH P XD V 20 075 Horz Only P DH P XD V 20 112 VH 006 W05H Horz Only N AH N VS D G2FD 14 20 048S 060S 061H VH 006 V05H VU 006...

Page 26: ...rifugal blower It shall have ball bearings and adjustable belt drive Motor mount base shall permit ease of motor changeover and belt tension adjust ment On pivoting wheel models exhaust blowers shall...

Page 27: ...space thermostat sends a signal to the RTU for cool ing heating or fan only operation 2 The ERV is activated with the supply blower of the RTU The intake blower the exhaust blower and the wheel rotat...

Page 28: ...ed operation or 1 and 2 if in low speed operation are outputting 110 volts to B26 exhaust blower motor though J P151 plug assembly 3 Verify B26 wheel motor C25 capacitor is good Replace the capacitor...

Page 29: ...blower motor 4 On direct drive models verify B26 wheel motor C25 capacitor is good Replace if necessary 5 If all of the above are operational the exhaust motor is bad Replace it with new motor UERV h...

Page 30: ...at the contacts are closed 3 Verify power to B26 exhaust blower motor though J P151 plug assembly 4 On direct drive models verify B26 wheel motor C25 capacitor is good Replace if necessary 5 If all of...

Page 31: ...A130 circuit board terminals TB 37 numbers 1 and 3 Terminal 1 is the hot and 3 is the common side of the power source from activation power source a c unit energy management control etc Typically 1 wo...

Page 32: ...change without notice Printed in U S A 246681 YTG B 0607 Copyright by Unitary Products Group 2007 All rights reserved Supersedes 246681 036 21360 004 A 0105 Unitary 5005 Norman Products York OK Group...

Reviews: