TECHNICAL GUIDE
MAXA-MI$ER
®
V* Series
Unitized Energy Recovery
Ventilators
ERV Unit with a Champion® Series Packaged Unit
ERV Unit with Predator® Packaged Unit
ERV Unit with Sunline® Packaged Unit
Energy recovery COMPONENT rated in
accordance with ARI Standard 1060-2000 and
certified to ARI. Actual performance in packaged
equipment may vary.
®
246681-YTG-B-0607
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
ETL Certified per UL 1995 and CSA 22.2
DESCRIPTION
•
Reduces cooling load at design temperatures up to 4 tons per
1000 cfm of outside air.
•
Reduces heating load up to 2.5 Tons Btuh per 1000 CFM of out-
side air.
•
Dry energy transfer. Moisture in supply (intake) air stream is
transferred to exhaust air stream in a vapor state, eliminating
condensate plumbing from the UERV.
•
Attaches directly to the York rooftop units. All mounting equip-
ment is provided.
•
Separate fused power supply.
•
Filters / mist eliminators are provided on the entering air open-
ings.
•
Adjustable support legs are provided.
•
Two modes of operation (Pivoting Wheel Models only)
•
Recovery mode during normal energy recovery operation.
•
True economizer mode when outside sensor calls for
economizer operation (3 - 12.5 ton packaged units
equipped with economizers). U. S. Patent 5,548,970.
•
Pivoting wheel models used with packaged unit with econo-
mizer. Sequence of operation controlled by economizer. (select
models only)
•
Balancing dampers provided on VR, VH and VU Modules.
(Except Millennium or VR74 and VR122)
•
Centrifugal blowers (both intake and exhaust for high static
capability and low sound levels).
•
Heavy gauge galvanized steel cabinets corrosion protected with
powder paint process that match York units.
•
Fully insulated cabinet.
•
ARI certified internal enthalpy wheel is provided.
•
Internal enthalpy wheel made of polymeric material with silica
gel impregnated into the material. The enthalpy wheel has a
five year limited warranty.
•
Internal enthalpy wheels are easily cleanable. Large wheels (25
inch diameter and above) are split into easily removable pie
segments. Smaller wheels can be removed from the ERV.
•
Continuous operation down to 10 ºF (-12 ºC) without defrost at
indoor relative humidity up to 40%. For temperatures below 10
ºF (-12 ºC), Optional Low Ambient Control Kit is required. Kit
includes temperature sensor to control the ERV before frost
build up can occur on recovery wheel.
Note: MAXA-MI
$
ER
®
UERV’s are designed for use with
rooftops using 14” high or greater roof curbs.