1083292-UIM-A-0114

14

Johnson Controls Unitary Products

When connecting the Communicating Control (wall thermostat) and fur-
nace control to a non-communicating outdoor A/C or heat pump, use
the wiring diagram in Figure 20. The thermostat and furnace will be con-
nected exactly as shown above, but the conventional 24 volt R, C and
Y/Y2 terminals will be used to control the outdoor unit.

CONVENTIONAL LOW VOLTAGE CONTROL WIRING 

CONNECTIONS

Install the field-supplied thermostat by following the instructions that
come with the thermostat. With the thermostat set in the OFF position
and the main electrical source disconnected, connect the thermostat
wiring from the wiring connections on the thermostat to the terminal
board on the ignition module, as shown in Figures 22-27. Electronic
thermostats may require the common wire to be connected. Apply
strain relief to thermostat wires passing through cabinet. If air condition-
ing equipment is installed, use thermostat wiring to connect the Y and C
terminals on the furnace control board to the proper wires on the con-
densing unit (unit outside). 

The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.

AIR CONDITIONER CONNECTIONS

This furnace may be used with single-stage or two-stage air condition-
ing units.

For Single-Stage A/C -

 Connect the low voltage wiring as shown in

Figure 22.

For Two-Stage A/C - 

Use a two-stage thermostat, connect the low volt-

age wiring as shown in Figure 23.

For Two-Stage A/C using a Single-Stage Thermostat - 

connect the

low voltage wiring as shown in Figure 24.

This furnace control board can control a two-stage A/C using only a sin-
gle-stage thermostat. In this case, the furnace control switches between
high cool and low cool based on the calculated cooling load.

 FIGURE 19:  

Modulating Furnace with Communicating AC or HP

 FIGURE 20:  

Modulating Furnace with Communicating Thermostat and 

Non-Communicating AC

Do not place more than one wire under any single communication
terminal screw (there are four communication terminal screws). If
more than one wire must be connected to a terminal screw, attach
only the terminal end of a one wire pigtail no longer than 6“, and
use a wire connector to connect the other end of the pigtail to the
other wires. Failure to do this will result in nuisance communication
error faults. See Figure 21.

A+

R

C

B-

A+

R

GND or C

B-

A+

R

GND

B-

LO

COMP

HI

COMP

O

DHUM

Y1

Y/Y2

W

R

G

C

Touch Screen

Communicating control

Modulating Furnace

Communicating control

Air Conditioner/Heat Pump

Communicating control

A+

R

C

B-

A+

R

B-

LO

COMP

HI

COMP

O

DHUM

Y1

Y/Y2

W

R

G

C

Touch Screen

Communicating control

Modulating Furnace

Communicating control

Non-

Air Conditioner

Communicating

Y

Y2

R

C

GND or C

 FIGURE 21:  

Terminal Screw Wire Connection

Set the heat anticipator in the room thermostat to 0.1 amps. Setting
it lower will cause short cycles. Setting it higher will cause the room
temperature to exceed the set points.

Some electronic thermostats do not have adjustable heat anticipa-
tors. They should be set to six cycles per hour. Follow the thermo-
stat manufacturer's instructions.

A+

C

B-

A+

R

C

B-

B-

NOTE

ENSURE ONLY ONE WIRE UNDER
TERMINAL SCREW.

TO CONNECT MORE THAN ONE WIRE:

1. CONNECT ONLY TERMINAL

END OF 6” WIRE PIGTAIL,

2. USE WIRE CONNECTOR TO

CONNECT OTHER END OF PIGTAIL
TO OTHER WIRES.

WIRE

CONNECTOR

TERMINAL

SCREW

THERMOSTAT

OUTDOOR UNIT

MODULATING FURNACE

COMMUNICATING

CONTROL

INDOOR UNIT

Summary of Contents for TP9C Series

Page 1: ...rmostat Chart Two Stage Air Conditioner with Single Stage Thermostat Variable Speed Modulating Furnace 17 Thermostat Chart Single Stage Heat Pump Variable Speed Modulating Furnace 18 Thermostat Chart...

Page 2: ...marking Means for providing outdoor air required for combustion Return air temperature maintained between 55 F 13 C and 80 F 27 C The air filter must be replaced upon substantial completion of the co...

Page 3: ...g jurisdiction In the United States and Canada follow all codes and standards for the following using the latest edition available STEP 1 Safety US National Fuel Gas Code NFGC NFPA 54 ANSI Z223 1 and...

Page 4: ...nstalled in every dwelling building or structure used in whole or in part for resi dential purposes including those owned or operated by the Com monwealth and where the side wall exhaust vent terminat...

Page 5: ...ed down for shipment In order to use the flanges remove the screw holding an individual flange rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flan...

Page 6: ...t exchang ers where attached to the vestibule panel Do not use the top return bend of the heat exchangers as lifting points as the tubes may shift out of position or their location brackets baffles SU...

Page 7: ...il casing over or under the furnace opening as shown in Figure 7 after configuring coil flanges as required see Coil Flange sec tion below COIL FLANGE INSTALLATION The coil cabinet includes four remov...

Page 8: ...t such that a minimum dis tance is maintained between the top of the coil and the top of the duct Refer to Table 2 COIL FURNACE ASSEMBLY HD SERIES COILS Horizontal duct coils are referred to as HD ser...

Page 9: ...trical Entry Condensate Drain Optional Return Air Cutout Either side 29 5 For Cladded door add appoximately an additional 75 C SUPPLY END 56 56 20 B 3 23 8 56 Combustion Air Inlet RETURN END B 24 25 2...

Page 10: ...from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace Refer to Figures 13 and 16 All filters and mounting provision must be field supplied All installa...

Page 11: ...es to larger 43 orifices which will bring the input rate back up to approxi mately 76 000 BTU H which is what it should be for that furnace at 6 000 feet SECTION V ELECTRICAL POWER ELECTRICAL POWER CO...

Page 12: ...bushing where the wires pass through the furnace panel After making the wiring connections replace the wiring box cover and screws Refer to Figure 17 3 The furnace s control system requires correct p...

Page 13: ...or heat pump with a fully communicating control This furnace may also be used along with the Communicating Thermo stat Control and a non communicating outdoor air conditioner through the addition of...

Page 14: ...tage wiring as shown in Figure 24 This furnace control board can control a two stage A C using only a sin gle stage thermostat In this case the furnace control switches between high cool and low cool...

Page 15: ...Heat Clipping Jumper W914 for electric heat on thermostat is not necessary C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE STAGE AIR CONDITIONER C 24 Volt Com...

Page 16: ...Volt Hot Y1 Single Stage Compressor MODULATING FURNACE CONTROL G Fan MODULATING FURNACE Y Y2 Second or Full Stage Compressor DHUM Dehumidification Open on Humidity Rise W Modulating Heat Move HUMIDIST...

Page 17: ...ssary C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor MODULATING FURNACE CONTROL G Fan MODULATING FURNACE Y Y2 Second or Full Stage Compressor DHUM Dehumidification Open on Humidity Rise W M...

Page 18: ...CONTROL X L Malfunction Light W Auxiliary Heat SINGLE STAGE HEAT PUMP Y2 Second Stage Compressor Step 9 of Thermostat Installer Configuration Menu must be set to Pump OFF Step 1 of Thermostat Installe...

Page 19: ...Energized in Cool C 24 Volt Common R 24 Volt Hot W1 OUT First Stage Heat W2 OUT Second Stage Heat Y2 OUT Second Stage Compressor Y1 Single Stage Compressor X L Malfunction Light Y2 Second Stage Compre...

Page 20: ...at XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Step 1 of Thermostat Installer Configuration Menu must be set to HP2 Selection of GAS ELEC switch on thermostat not necessary Thermostat Installer S...

Page 21: ...the W signal is removed 2 Defrost Cycle When both a W signal and a Y2 signal are pres ent the modulating firing rate will operate at a constant 80 firing rate and there will be no Run 2 function so th...

Page 22: ...and drain hose located in the loose parts bag The intake drain hose is to be installed by connecting it to the inlet pipe coupling and to the collec tor box as shown in Figures 29 31 and 32 The drain...

Page 23: ...ff so that no sagging loops will collect and hold condensate which will cause the furnace to not operate Shorten pressure switch hose Re route and shorten pressure switch hose Shorten rain gutter hose...

Page 24: ...tch hose to this position NOTE May require the longer hose that is provided with wider cabinets Move condensate drain hose to this position May exit either side of the cabinet Move rain gutter hose to...

Page 25: ...ose to this position NOTE May require the longer hose that is provided with wider cabinets Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this position Mov...

Page 26: ...tting provided Move condensate drain hose to this position Move rain gutter hose to this position Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this posit...

Page 27: ...to American National Standards Institute ANSI and American Society for Test ing and Materials ASTM standards D1785 Schedule 40 PVC D2665 PVC DWV F891 PVC DWV Cellular Core D2261 ABS DWV or F628 Schedu...

Page 28: ...5 80 000 4 125 100 000 2 20 100 000 2 NA 100 000 3 80 100 000 3 60 100 000 4 145 100 000 4 125 120 000 3 80 120 000 3 60 120 000 4 145 120 000 4 125 Elevation 4001 5000 Elevation 8001 9000 Model Input...

Page 29: ...VENTING FIGURE 33 Dimensions TABLE 8 Elbow Dimensions Elbow A Dimension Illustrated in Figure 33 2 Standard 2 5 16 3 Standard 3 1 16 2 Sweep 3 1 4 3 Sweep 4 1 16 TABLE 9 Equivalent Length of Fittings...

Page 30: ...equirements of the gas supplier 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 30 5 cm or in accordance with local...

Page 31: ...Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 36 and 37 can be insta...

Page 32: ...ipes are not termi nated in the same atmospheric zone Refer to Figure 44 for attic and crawl space termination Only the combustion air intake may terminate in the attic The vent must terminate outside...

Page 33: ...as an exhaust fan kitchen ventilation system clothes dryer or fireplace may cre ate conditions requiring special attention to avoid unsatisfactory operation of gas appliances A venting problem or a l...

Page 34: ...Refer to Table 7 for intake pipe sizing allowable length and elbow usage Follow all notes procedures and required materials in the COMBUSTION AIR VENT PIPE SIZING section in these instructions when i...

Page 35: ...no thermostat calls no call for heating cooling or continuous fan push and hold the TEST but ton on the board for one second The LED on the board will glow red 2 Release the TEST button The LED on the...

Page 36: ...ifice hole is essential for proper flame characteristics DO NOT bottom out gas valve regulator adjusting screw This can result in unregulated manifold pressure and result in excess over fire and heat...

Page 37: ...R jumper on the furnace control board The jumper is factory set to deliver an air temperature rise near the midpoint of the nameplate temperature rise range If more air is desired lower temper ature r...

Page 38: ...e southern part of the country On a call for cooling the blower will ramp up to 50 of full capacity and will stay there for two minutes then will ramp up to 82 of full capacity and will stay there for...

Page 39: ...90 840 H B 1100 715 1090 710 MH B 1065 690 1015 660 H A 1000 650 1000 650 MH A 960 625 960 625 H C 760 495 760 495 ML B 900 585 900 585 MH C 660 430 660 430 L B 690 450 680 445 ML A 600 400 600 400 L...

Page 40: ...e is equipped with a high temperature limit control mounted to the left side of the furnace vestibule panel This limit switch will open and shut off gas to the burners if it detects excessive air temp...

Page 41: ...ating airflow an open fuse on the control board Five Red Flashes Rollout switch or condensate pressure switch open Check the rollout switch es on the burner assembly It is a man ual reset switch To re...

Page 42: ...GHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d PAN CONDENSATE BRACKET DOOR HARNESS WIRING FERRULE 3 Req d GROMMET 3 Req d MOTOR MOUNT TUBING SILICON HOSE RAIN GUTTER HOSE CONDENSATE PLUG SEAL 7...

Page 43: ...und neutral Gas valve shorted ON Check blower motor wiring ID plug missing OR not connected properly None Slow Green Rapid Green Slow Amber Rapid Amber 2 Amber 3 Amber 4 Amber 5 Amber 6 Amber Steady R...