background image

ENGLISH

OPERATION TIPS

The following events may occur during normal operation.

 

P

 

 

 

 

 Compressor 

protection

 

•  The compressor cannot restart for 3 minutes after it stops.

 

 

Anti cold air (Cooling and heating models only)

 

•  The unit is designed not to blow cold air on  EAT mode, when the indoor heat exchanger is in one of the following  

 

three situations and the set temperature has not been reached.

 

 

A)   When heating has  ust starting.

 

 

)    efrosting.

 

 

C)   Low temperature heating.

 

•  The indoor or outdoor fan stop running when defrosting (Cooling and heating models only).

 

 

efrosting (Cooling and heating models only)

 

•  Frost may be generated on the outdoor unit during heat cycle when outdoor temperature is low and humidity is  

 

high resulting in lower heating ef ciency of the air conditioner.

 

• 

uring this condition air conditioner will stop heating operation and start defrosting automatically.

 • The time to defrost may vary from 4 to 10 minutes according to the outdoor temperature and the amount of frost

  

 

buildup on the outdoor unit.

 A 

 

 

 

 

 

 

 

 

•  A white mist may generate due to a large temperature di erence between air inlet and air outlet on COOL mode  

 

in an indoor environment that has a high relative humidity.

 

•  A white mist may generate due to moisture generated from defrosting process when the air conditioner restarts in  

 

EAT mode operation after defrosting.

 

L

 

 

 

 

 

.

 

• 

ou may hear a low hissing sound when the compressor is running or has  ust stopped running.

 

 

This sound is the sound of the refrigerant  owing or coming to a stop.

 •  ou can also hear a low  s ueak  sound when the compressor is running or has  ust stopped running. This is
 

 

caused by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.

 

•  A noise may be heard due to louver restoring to its original position when power is  rst turned on.

 

D

 

 

 

 

 

 

 

This is a normal condition when the air conditioner has not been used for a long time or during 

rst use of the unit.

 A 

 

 

 

 

 

 

 

 

This is caused by the indoor unit giving o  smells permeated from building material, from furniture, or smoke.

  T    

 

    AN 

 

 

 COOL   HEAT 

 

 

 

 

 

 

 

When indoor temperature reaches the temperature setting on air conditioner, the compressor will stop automatically, 

and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises 
on COOL mode or falls on  EAT mode (For cooling and heating models only) to the set point.

  ripping water may generate on the surface of the indoor unit when cooling in a high relatively humidity (relative 

humidity higher than 80 ). Ad ust the horizontal louver to the maximum air outlet position and select  I

 fan speed.

 

H

 

 

 

 

 

 

 

 

The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating operation. 

When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time, 

heat 

loading of the air conditioner increases due to larger di erence between indoor and outdoor temperature. If a comfortable 
temperature cannot be achieved by the air conditioner, we suggest you use a supplementary heating device.

 

A

 

 

Power failure during operation will stop the unit completely.

  For the unit without Auto restart feature, when the power restores, the OPERATION indicator on the indoor unit 

starts ashing.  To restart the operation, push the ON/OFF button on the remote controller. For the unit with Auto
restart feature, when the power restores, the unit restarts automatically with all the previous settings preserved by 
the memory function.

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

isconnect the unit with power and then re connect the unit with power again. Push the ON/OFF button on the 

remote controller to restart operation.

Summary of Contents for TLHA18-30OSAAAD

Page 1: ...and operation Make sure that it iswell kept for later reference Read this manual before installation and operation Make sure that it is well kept for later reference Mini Split Air Conditioner TLCA TL...

Page 2: ...0 Troubleshooting guide 21 n o i t a l l a t s n i s i h t d a e r e s a e l P manualcarefullybeforestarting the installation It will tell you necessary information QualityPOLICY We will continuously...

Page 3: ...an cause in ury Installation and maintenance of this air conditioning system should only be car ried out by trained and quali ed personnel After unpac ing please chec the unit carefully for possible d...

Page 4: ...sensor top valve 7 isplay panel A C lectrostatic iber ilter tandard OPERATING TE PERATURE Mode emperature oom temperature utdoor temperature ooling operation 1 18 43 15 43 or the models with low temp...

Page 5: ...ION When you set the air conditioner in AUTO mode it will automatically select cooling heating cooling heating models only or fan only operation depending on what temperature you have selected and the...

Page 6: ...nce may be reduced o not operate unit with horizontal louver in closed position PREPARATION E ORE INSTALLATION efore doing any work check the interior power supply cord and the main breaker capacity a...

Page 7: ...ENGLISH EN OUTDOOR UNIT PICTURES D I O Dimension Mo el D 1 2 1 2 1 1 221 1 1 221 Dimension Mo e D 1 2 1 2...

Page 8: ...he designated installation place and mark the hole position rill a hole and mount installation plate 5 mm Outdoor Indoor Note When installing the refrigerant pipes from others side A hole must be plac...

Page 9: ...U bend Connect a plastic condensate pipe with an internal diameter of 12 mm The drain hose can be connected to the left or the right side Verification of condensate water drainage Fill the drain pan w...

Page 10: ...the piping Align the central of the connecting pipes and tighten the are nut Fix piping with pipe clamps and check that any pipe vibrations cannot be transmitted to the building structure Connect the...

Page 11: ...tion Low pressure igh pressure Manifold as valve Li uid valve Pressure tap Outdoor Unit Indoor Unit as Line Li uid Line R 22 Outdoor heat pump unit install the unit at least 10 cm above ground level t...

Page 12: ...main power distribution The distribution has to be of an low impedance normally the re uired impedance reaches at a 32 A fusing point 2 No other e uipment has to be connected with this power line 3 F...

Page 13: ...ENGLISH EN I U TLHA OSAAA D R 5 5 8 8 5 10 5 5 I U TLC H A OSAA D R 21 3 4...

Page 14: ...ITOR C RED TO INDOOR NIT O TDOOR NIT Y G This symbol indicates the element is optional the actual shape shall prevail 1 2N E S R ITE C C COM RESSOR O ER O D RE Y C COM RESSOR C CITOR F N MOTOR E RED F...

Page 15: ...O U TLCA OSAAAR O U TLCA OSAADR 5 ENGLISH 3 4 3 3...

Page 16: ...CN CN RED RED RED RED C S R IRING DI GR M O TDOOR NIT CN1 CN11 ITE RT CODE NIT1 COM C 1 C 2 T1 t2 1 S1 RT M1 CT TR NS1 CN1 CN11 F N2 RT N ME O TDOOR CONTRO C COM RESSOR COM RESSOR R N C CITOR O TDOOR...

Page 17: ...ENGLISH O U TLHA OSAAAR 3 4 3 3...

Page 18: ...aches 55 C outdoor unit will turn o external unit fan but still keep compressor running 2 Condition to stop defrosting Units will switch back to heating mode when either of the following conditions is...

Page 19: ...r conditioner and disconnect power Remove the batteries from the remote controller 3 The outdoor unit re uires periodic maintenance and cleaning o not attempt to do this yourself Contact your dealer o...

Page 20: ...is changing A noise may be heard due to louver restoring to its original position when power is rst turned on D This is a normal condition when the air conditioner has not been used for a long time or...

Page 21: ...when you started the system 1 Remove charge repair evacuate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room The compressor runs continuously 1 Thermostat ad...

Page 22: ...acturer for disposal U N Where appropriate drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal of oily wastes...

Page 23: ...www johnsoncontrols com Form No 035M000349 003 2008 Johnson Controls Inc Johnson Controls reserve the right to change product features without prior notice...

Reviews: