background image

ENGINEERING MANUAL

INVERTER-DRIVEN MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS

Engineering Manual

TC-17006

Technical Catalog for Outdoor Unit

< Indoor Units >

  ● Wall Mount

   

TIWM006B21S

   

TIWM008B21S

   

TIWM012B21S

   

TIWM015B21S

   

TIWM018B21S

   

TIWM024B21S

   

TIWM030B21S

Summary of Contents for TIWM006B21S

Page 1: ...R DRIVEN MULTI SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS Engineering Manual TC 17006 Technical Catalog for Outdoor Unit Indoor Units Wall Mount TIWM006B21S TIWM008B21S TIWM012B21S TIWM015B21S TIWM018B21...

Page 2: ......

Page 3: ...against possible damage or injury that might occur in an earthquake if the unit is not installed correctly injuries may occur due to a falling unit Use appropriate Personal Protective Equipment PPE s...

Page 4: ...in any location where animals and plants can come into direct contact with the outlet air stream Exposure could adversely affect the animals and plants Do not install the unit with any downward slope...

Page 5: ...ases can be generated from decomposition Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive gases may be present If you do toxic gases can seep into breat...

Page 6: ...he cycle the sizes of the charging connections have been changed from R407C type and R22 type It is necessary to verify the appropriate tools are on hand before performing installation work Use refrig...

Page 7: ...n cable must be a minimum of AWG18 0 82mm2 2 Conductor Stranded Copper Shielded cable must be used for applications and routing in areas of high EMI and other sources of potentially excessive electric...

Page 8: ...Kit CWDIRK01 3 3 3 3 1 Specifications 3 3 3 3 2 Dimensions 3 3 3 3 3 Applicable Models 3 3 3 3 4 Accessories Options 3 4 3 3 5 Installation 3 4 3 3 6 Electrical Wiring 3 7 3 3 7 Setting DIP Switches...

Page 9: ...combination of the scroll compressor and inverter provides the best air conditioning for small and medium office buildings VRF System Johnson Controls has developed the VRF system with its customers i...

Page 10: ...without removing the front panel Open the electrical box cover and perform the field electrical wiring work without removing the front panel 2 Operation control with wireless controller Each unit can...

Page 11: ...or Unit I Indoor Unit Type WM Wall Mount WM Capacity MBH 006 Refrigerant Type B R410A B Power Supply 2 208 230Volts 1Phase 60Hz 2 1 1st Generation 1 S Standard Type S 2 2 Line up Type Capacity Model R...

Page 12: ...Connection with Flare Nuts Liquid Line in mm 3 8 9 52 3 8 9 52 3 8 9 52 Gas Line in mm 5 8 15 88 5 8 15 88 5 8 15 88 Condensate Drain OD in mm 7 8 22 7 8 22 7 8 22 ID in mm 5 8 16 5 8 16 5 8 16 VP16...

Page 13: ...Option 2 NOTES 1 Removal of the condensate pipe is possible from either side of the knockout holes If using the left side install a condensate hose to the condensate pipe connection at the left side 2...

Page 14: ...TE Removal of the condensate pipe is possible from either side of the knockout holes If using the left side install a condensate hose to the condensate pipe connection at the left side Opening Directi...

Page 15: ...the knockout holes If using the left side install a condensate hose to the condensate pipe connection at the left side Unit inch mm Opening Direction Option 2 Opening Direction Option 3 Opening Direc...

Page 16: ...ontrol Box 15 Air Inlet 8 Refrigerant Gas Pipe with f1 2 12 7 Flare Nut 16 Receiver Part No Part Name Remarks No Part Name Remarks 1 Fan 9 Refrigerant Liquid Pipe with f1 4 6 35 Flare Nut 2 Fan Motor...

Page 17: ...Motor for Auto Swing 4 Distributor 12 Condensate Pan 5 Strainer 13 Air Filter 6 Electronic Expansion Valve 14 Air Outlet 7 Electrical Control Box 15 Air Inlet 8 Refrigerant Gas Pipe with fa Flare Nut...

Page 18: ...353 282 247 229 10 8 7 6 5 46 52 Heat Exchanger Type 2 2 Indoor Fan Motor 38 38 1 1 E E 2 52 TIWM030B21S Model Heat Exchanger Type 2 2 Model 34 34 Maximum Operating Pressure Total Face Area 76 4 90 4...

Page 19: ...binations within the VRF system and the following conditions Cooling Operation Conditions Indoor Air Inlet Temperature 80o F DB 26 7o C DB 67o F WB 19 4o C WB Outdoor Air Inlet Temperature 95o F DB 35...

Page 20: ...TIWM015B21S 0 4 15 0 038 0 3 TIWM018B21S 0 6 15 0 038 0 5 TIWM024B21S 0 7 15 0 038 0 6 TIWM030B21S 0 7 15 0 038 0 6 VOL Rated Unit Power Supply Voltage V PH Phase HZ Frequency Hz MCA Minimum Circuit...

Page 21: ...WALL MOUNT TC 17006 rev 1 2 11 2 10 Sound Data NOTE Operation sound is equivalent to an anechoic chamber free space Noise level will be increased by the surrounding noise and echoes...

Page 22: ...WALL MOUNT 2 12 TC 17006 rev 1 NOTE Operation sound is equivalent to an anechoic chamber free space Noise level will be increased by the surrounding noise and echoes...

Page 23: ...70 f1 4 6 35 f3 8 t0 031 9 52 0 7 f1 4 t0 031 6 35 0 7 TIWM012B21S 3 Pass f1 2 12 70 f1 4 6 35 f3 8 t0 031 9 52 0 7 f1 4 t0 031 6 35 0 7 TIWM015B21S 4 Pass f1 2 12 70 f1 4 6 35 f1 2 t0 031 12 7 0 7 f...

Page 24: ...e outdoor unit model to be connected Refer to the Outdoor Unit Engineering Manual for details Dry Operation The sequence may be different depending on the outdoor unit model to be connected Refer to t...

Page 25: ...y Operation Is compressor operated for more than 15 min The check interval differs depending on the conditions I U Electronic Expansion Valve Completely Closed No No Yes MIF Operation at Set Fan Speed...

Page 26: ...ON Set Temp is lower than Air Intake Temp Prevention Control for Excessively High Outlet Air Temperature High Outlet Air Temperature Heat Lockout NOTE Thermo ON The outdoor unit and some indoor units...

Page 27: ...Safety and Control Device Setting Model TIWM006B21S TIWM008B21S TIWM012B21S TIWM015B21S TIWM018B21S TIWM024B21S TIWM030B21S For Evaporator Fan Motor o F o C 176 80 140 60 Chip Ceramic PTC Thermistor...

Page 28: ...WALL MOUNT 2 18 TC 17006 rev 1 2 11 4 Wiring Diagram Models TIWM006B21S TIWM008B21S and TIWM012B21S...

Page 29: ...WALL MOUNT TC 17006 rev 1 2 19 Models TIWM015B21S TIWM018B21S TIWM024B21S and TIWM030B21S...

Page 30: ......

Page 31: ...ed IR Receiver Kit CWDIRK01 3 4 3P Connector Cable PCC 1A 3 5 Remote Sensor THM R2A 3 6 Relay and 3 Pin Connector Kit PSC 5RA 3 7 Wired Controller CIW01 3 8 Simplified Wired Controller CIS01 3 9 Wirel...

Page 32: ...35 Copper Pipe Connection Gas Side 1 2 12 7 Copper Pipe Connection 1 4 6 35 Strainer Liquid Side Strainer Gas Side Strainer 1 2 12 7 Strainer Pay attention to the arrow direction Pay attention to the...

Page 33: ...ERGENCY 3 3 2 Dimensions 3 3 3 Applicable Models Model CWDIRK01 Applicable Indoor Unit Model General Purpose Ducted and Wall Mount Type Applicable Wireless Controller CIR01 3 3 Infrared IR Receiver Ki...

Page 34: ...is not completed correctly heat generation at the connection a fire or an electric shock may occur Make sure that the electrical wires are securely fixed so that no external force affects the termina...

Page 35: ...r unit if the IR receiver kit is attached after the indoor unit is installed 5 Mount the IR receiver kit onto the wall or the ceiling surface as shown below Situation A 1 Secure the bracket Situation...

Page 36: ...onto the bracket Click sound is heard when the cover is completely hooked onto the bracket Connecting Cable The connecting cable should not be exposed Lead it through the metal conduit in the wall Co...

Page 37: ...doing so the operation is not available 2 Turn OFF the power supply of the indoor and outdoor units completely before setting the DIP switch If not turning off the power the setting becomes invalid 3...

Page 38: ...2 5 6 ON RUN DEF FILTER TIMER COOL HEAT EMERGENCY COOL Button HEAT Button Cover PCB Outlet for Connecting Cable Case Mounting Bracket DIP Switch DSW1 Factory Setting 1 Remove the mounting bracket 2 Re...

Page 39: ...Setting Set the Number 2 pin of the IR receiver kit DIP switch DSW1 at the Identified Unit B ON side 2 Wireless Controller Set the wireless controller according to the Installation and Maintenance Man...

Page 40: ...rolled using one wireless controller When multiple indoor units are installed in a large room all the indoor units can be controlled to start stop with only one wireless controller NOTE Do not apply a...

Page 41: ...0V Keep a separation of more than 12 inches 30cm or run the cable through a grounded metal conduit OFF ON Unit Number Setting DSW6 Tens Digit RSW1 Units Digit 1 2 3 4 5 6 Set No 1 pin ON OFF ON 1 2 3...

Page 42: ...ht and FILTER yellow light The first LED light is green The number of times this LED flashes 0 5 second ON and OFF will tell you the DEF Alarm Code The second LED light is yellow The number of times t...

Page 43: ...upplied wires AWG22 0 3 to 0 5mm2 with soldering Name 3P Connector Cable Model PCC 1A Remarks One set contains five 3P connector cables Specifications Item Specification Model THM R2A Case Material AB...

Page 44: ...nput 1 Input level signal or pulse signal for voltage from the third party controller or BMS Voltage 12VDC 10mA Voltage 24VDC 10mA Pulse Range 500ms or more Input 2 Third Party Controller or BMS Outpu...

Page 45: ...11 9 16 8 12 1 17 3 12 3 17 7 12 2 80 15 1 11 8 15 3 11 6 15 6 11 7 15 8 11 9 16 3 11 9 16 8 11 9 17 1 12 0 95 14 1 11 1 14 4 10 4 14 7 10 7 15 0 11 3 15 5 11 3 16 0 11 0 16 3 11 2 110 10 1 8 1 9 9 7...

Page 46: ...9 6 19 6 19 6 19 1 18 7 43 9 0 9 0 9 0 9 0 8 7 8 5 43 20 1 20 0 20 0 20 0 19 4 19 0 47 9 4 9 4 9 4 9 3 9 0 8 5 47 20 8 20 8 20 8 20 8 20 0 19 0 51 9 7 9 7 9 7 9 6 9 0 8 5 51 21 6 21 6 21 6 21 4 20 0 1...

Page 47: ......

Page 48: ...2017 Johnson Controls Inc TC 17006 rev 1 Code No LIT 12012568 Revised February 2018...

Reviews: