![background image](http://html1.mh-extra.com/html/york/tche24/tche24_technical-manual_4183573005.webp)
5371951-YTG-A-0517
Johnson Controls Unitary Products
5
— = Not applicable.
MP Modular Air Handlers use Coil Only Ratings.
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
COIL
MODEL
1
COOLING
MODEL
WIDTH
RATED
CFM
NET MBH
SEER
EER
TOTAL
SENS.
TCHE24S41S
AE30BX21
17.5
–
800
24.0
18.5
15.50
12.75
TCHE24S41S
AE36BX21
17.5
–
800
24.0
18.7
15.75
13.00
TCHE24S41S
AE36CX21
21.0
–
800
24.0
18.7
16.00
13.00
TCHE24S41S
AP30BX21
17.5
–
800
23.8
18.5
14.00
12.25
TCHE24S41S
AVC30BX21
17.5
–
825
24.0
18.6
15.75
13.00
TCHE24S41S
AVC36BX21
17.5
–
800
24.0
18.7
16.00
13.00
TCHE24S41S
AVC36CX21
21.0
–
800
24.0
18.6
16.00
13.00
TCHE24S41S
ME08BN21
17.5
CF/CM30B
825
24.0
18.6
15.50
12.75
TCHE24S41S
ME08BN21
17.5
CF/CM36B
775
24.0
18.4
15.75
13.00
TCHE24S41S
ME12BN21
17.5
CF/CM30B
825
24.0
18.6
15.50
12.75
TCHE24S41S
ME12BN21
17.5
CF/CM36B
825
24.0
19.1
15.75
13.00
TCHE24S41S
ME14DN21
24.5
CF/CM30D
825
24.0
18.5
15.75
13.00
TCHE24S41S
ME14DN21
24.5
CF/CM36D
825
24.0
19.1
16.00
13.00
TCHE24S41S
ME16CN21
21.0
CF/CM30C
800
24.0
18.5
15.00
12.50
TCHE24S41S
ME16CN21
21.0
CF/CM36C
825
24.0
19.0
15.00
12.50
TCHE24S41S
MVC08BN21
17.5
CF/CM30B
725
24.0
18.0
15.75
13.00
TCHE24S41S
MVC08BN21
17.5
CF/CM36B
750
24.0
18.3
15.25
12.75
TCHE24S41S
MVC12BN21
17.5
CF/CM30B
775
24.0
18.4
15.25
12.75
TCHE24S41S
MVC12BN21
17.5
CF/CM36B
775
24.0
18.5
15.50
12.75
TCHE24S41S
MVC14DN21
24.5
CF/CM30D
750
24.0
18.0
15.50
12.75
TCHE24S41S
MVC14DN21
24.5
CF/CM36D
825
24.0
19.1
16.00
13.00
TCHE24S41S
MVC16CN21
21.0
CF/CM30C
850
24.0
19.0
15.00
12.50
TCHE24S41S
MVC16CN21
21.0
CF/CM36C
850
24.0
19.0
15.25
12.75
TCHE36S41S
ME16CN21
21.0
FC38C
1200
36.0
27.2
16.00
13.00
TCHE36S41S
MVC16CN21
21.0
FC38C
1200
35.8
27.2
15.50
12.75
TCHE48S41S
ME14DN21
24.5
FC49D
1425
46.5
34.6
15.10
12.50
TCHE48S41S
ME20DN21
24.5
FC49D
1425
46.5
34.6
15.50
12.50
TCHE48S41S
MVC14DN21
24.5
FC49D
1175
45.5
31.8
15.50
12.75
TCHE48S41S
MVC20DN21
24.5
FC49D
1375
46.5
34.2
15.50
12.75
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI/AHRI Standard 210/240.
Cooling MBH based on 80°
F entering air temperature, 50% RH (Relative Humidity), and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTUs at 95°
F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided by the total
electric power input in watt-hours during the same period.
1. CM coils available with a factory installed horizontal drain pan. See price pages for specific model number.