556454-YTG-B-0410
6
Johnson Controls Unitary Products
— = Not applicable.
13 SEER AC WITH AHP / SHP / AHX / F*FP
TCHD18S41S3
AHX18
17
–
630
18.2
13.1
14.25
11.75
AHX24
17
–
590
18.3
13.0
14.25
11.75
AHX30
17
–
610
18.6
13.3
14.50
12.00
F6FP018
17
–
600
17.9
12.6
13.50
11.25
F6FP024
17
–
600
18.5
13.1
14.00
11.50
F6FP030
17
–
620
18.5
13.2
14.00
11.50
TCHD24S41S3
AHP24 17
–
850
23.0
16.8
13.15
11.05
AHX18
17
–
835
23.2
17.2
14.00
11.50
AHX24
17
–
800
23.6
17.3
14.00
12.75
AHX30
17
–
820
23.8
17.8
14.50
12.75
AHX36
21
–
815
24.2
18.1
15.00
12.25
F*FP030 17
–
800
23.0
16.7
13.10
11.00
F6FP024
17
–
840
23.4
17.4
14.00
11.50
F6FP030
17
–
850
23.4
17.4
13.75
11.25
F6FP036
21
–
855
23.8
17.9
14.25
11.75
TCHD30S41S3
AHP36 21
–
1000
28.4
21.2
13.75
12.20
AHX30
17
–
1025
28.4
21.3
14.50
12.50
AHX36
21
–
1005
29.0
21.7
15.25
13.25
AHX42
21
–
990
29.4
22.1
15.50
13.75
AHX48
24
–
1090
29.8
23.0
15.50
13.75
F*FP030 17
–
1000
27.6
20.0
13.20
11.85
F*FP036 21
–
1000
27.8
20.6
13.40
12.00
F*FP040 21
–
1000
27.8
20.4
13.40
12.00
F6FP030
17
–
1035
28.2
20.9
13.75
12.00
F6FP036
21
–
980
28.2
20.7
14.50
12.75
F6FP042
21
–
1065
29.6
22.4
15.25
13.50
F6FP048
24
–
1055
28.0
21.0
14.50
12.50
TCHD36S41S3
AHP36 21
–
1200
34.2
25.0
14.00
12.15
AHX36
21
–
1225
34.4
25.7
14.75
12.50
AHX42
21
–
1190
35.0
25.9
15.25
12.75
AHX48
24
–
1255
35.2
26.3
15.25
12.75
AHX60
24
–
1300
35.6
26.8
15.00
12.75
F*FP036 21
–
1200
33.0
23.8
13.00
11.35
F*FP040 21
–
1200
33.0
24.0
13.00
11.40
F*FP042 21
–
1200
33.0
24.0
13.00
11.40
F5FP048 24
–
1250
35.0
25.8
15.20
13.00
F6FP036
21
–
1210
33.4
24.3
13.75
11.75
F6FP042
21
–
1290
35.2
26.4
14.75
12.50
F6FP048
24
–
1125
32.2
23.3
14.00
11.75
F6FP060
24
–
1240
35.2
26.3
15.00
12.75
TCHD48S41S3
AHP/SHP60 24
–
1600 45.5 33.2 13.40
11.50
AHX48
24
–
1660
47.0
34.6
13.75
11.75
AHX60
24
–
1680
47.5
34.8
13.50
11.75
F5FP048 24
–
1700
47.5
35.0
13.75
12.00
F5FP060 24
–
1700
46.0
33.4
13.35
11.55
F6FP048
24
–
1625
45.0
33.2
13.00
11.00
F6FP060
24
–
1710
48.0
35.0
13.50
11.50
TCHD60S41S3
AHX60
24
–
1905
57.5
40.2
13.00
11.00
F6FP060
24
–
1710
56.5
38.7
13.00
11.00
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8
°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
AIR HANDLER
COIL
MODEL
1
COOLING
MODEL
W
RATED
CFM
NET MBH
SEER
EER
TOTAL
SENS.