359315-YTG-B-0408
2
Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.
Physical and Electrical Data
MODEL
TCGD18
S41S1(H)
TCGD24
S41S1(H)
TCGD30
S41S1(H)
TCGD36
S41S1(H)
TCGD42
S41S1(H)
TCGD48
S41S1(H)
TCGD60
S41S1
Unit Supply Voltage
208-230V, 1
φ,
60Hz
Normal Voltage Range
1
187 to 252
Minimum
Circuit
Ampacity
10.0 12.4 14.7 17.9 21.5
21.1 34.3
Max. Overcurrent Device Amps
2
15 20 25 30 35 35 60
Min. Overcurrent Device Amps
3
15 15 15 20 25 25 35
Compressor Type
Rotary
Recip
Recip
Recip
Recip
Recip
Scroll
Compressor Amps
Rated
Load
7.6 9.3 10.6 13.1 16.0 15.7 26.2
Locked
Rotor
40.0 43.0 54.0 74 84 84 150
Crankcase
Heater
No No No No No No No
Fan
Motor
Amps
Rated
Load
0.5 0.8 1.4 1.5 1.5 1.5 1.5
Fan
Diameter
Inches
17.5
17.5
17.5 22 22 22 24
Fan Motor
Rated
HP
1/12 1/8 1/4 1/4 1/4 1/4 1/4
Nominal
RPM
1100
1075
1100 850 850 850 850
Nominal
CFM
1400 1950 2050 3200 2950 2950 3600
Coil
Face Area Sq. Ft.
9.60
9.60
9.60
13.07
14.16
14.16
18.68
Rows
Deep
1 1 1 1 1 1 1
Fin
/
Inches
23 23 23 23 23 23 23
Liquid
Line
Set
OD
(Field
Installed)
3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor
Line
Set
OD
(Field
Installed)
5/8 3/4 3/4 3/4 7/8 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
3 - 3
3 - 13
3 - 14
4 - 9
4 - 5
4 - 9
5 - 6
Charge
Per
Foot,
Oz.
0.58 0.62 0.62 0.62 0.67 0.67 0.67
Operating Weight Lbs.
97
129
131
145
173
173
195
Models with “H” on the end of the model number have a factory installed start kits.
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B
C
Liquid
Vapor
18
28
23-1/2
23-1/2
3/8”
3/4”
24
28
23-1/2
23-1/2
30
28
23-1/2
23-1/2
36
28
29
29
42
30
29
29
7/8”
48
30
29
29
60
32
33-5/8
33-5/8