5188235-YIM-E-0518
6
Johnson Controls Ducted Systems
Figure 1: ZE036-060 Component Location
Smoke
Detector
3/4” PVC Female
Condensate Drain
GFCI
Convenience Outlet
Knockout
For Side
Control Entry
Simplicity
® Lite™
Or Smart Equipment™
Control Board
Knockout For Side
Gas Supply Entry
Full Perimeter Baserails
With Forklift Slots And
Lifting Holes
Highly Efficient
Enhanced Copper
Tube/Enhanced
Aluminum Fin
Or
Micro-Channel
Aluminum
Tube/Aluminum
Fin Condenser
High Efficiency
Compressor
Power Ventor Motor With
Post Purge Cycle
20 Gauge Aluminized
Steel Tubular Heat Exchanger
Belt Drive Or
Direct Drive
Blower
HACR
Breaker
Economizer
Hood
Knockout
For Side
Power Entry
Slide-In
Economizer
Table 1: ZE036-060 Unit Limitations
Size
(Tons)
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
ZE036
(3.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
ZE048
(4.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
ZE060
(5.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125