5188235-YIM-E-0518
Johnson Controls Ducted Systems
47
* Field Option Sheave.
ZE036 - 060 (3-5 Ton Direct Drive) Bottom Duct
UNIT
TONNAGE
MOTOR
1
SPEED
1. Factory set on medium speed tap.
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
3
3
3. Bottom Duct application (230 Volts)
5 (HI)
1520
320
1478
335
1438
349
1401
363
1363
376
1327
390
1286
403
1248
417
1207
430
4 (MED/HI)
1430
263
1384
276
1342
290
1302
303
1259
316
1215
329
1168
343
1114
358
1044
374
3 (MED)
1287
208
1242
221
1199
234
1155
246
1108
258
1060
272
997
288
930
303
889
313
2 (MED/LOW)
1185
171
1138
183
1091
195
1041
207
987
220
921
235
862
248
-
-
-
-
1 (LOW)
1040
130
959
134
900
145
-
-
-
-
-
-
-
-
-
-
-
-
4
3
5 (HI)
-
-
1995
696
1957
714
1922
734
1885
749
1844
764
1795
769
1709
743
1566
685
4 (MED/HI)
1846
539
1812
557
1776
571
1736
585
1704
602
1662
619
1619
638
1566
653
1492
639
3 (MED)
1662
408
1624
426
1577
438
1542
455
1501
472
1454
490
1400
505
1356
521
1323
536
2 (MED/LOW)
1566
362
1526
380
1480
391
1450
406
1411
423
1363
440
1312
455
1279
469
1235
485
1 (LOW)
1287
223
1246
237
1190
247
-
-
-
-
-
-
-
-
-
-
-
-
5
3
5 (HI)
2166
883
2169
931
2158
950
2134
964
2095
979
2040
971
1963
940
1881
898
1791
854
4 (MED/HI)
2060
771
2042
784
2035
808
2006
826
1970
844
1934
859
1888
861
1821
843
1730
806
3 (MED)
1940
637
1920
656
1907
675
1870
696
1834
715
1802
730
1759
740
1722
756
1657
748
2 (MED/LOW)
1688
413
1645
432
1611
451
1575
468
1534
479
1498
497
1461
513
-
-
-
-
1 (LOW)
1509
327
1477
339
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Table 16: Belt Drive RPM Selection
Size
(Tons)
Model
HP
Max
BHP
Motor
Sheave
Blower
Sheave
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Fully
Closed
036
(3)
ZE
1.5
1.73
1VL44
AK64
805
865
920
980
1035
1095
1.5
1.73
1VP56
AK66
1115
1170
1225
1280
1335
1390
048
(4)
ZE
1.5
1.73
1VL44
AK56
930
995
1060
1130
1195
1260
1.5
1.73
1VP56
AK61
1210
1270
1330
1390
1455
1515
060
(5)
ZE
1.5
1.73
1VL44
AK56
930
995
1060
1130
1195
1260
2
2.3
1VP56
AK56
1325
1395
1460
1525
1590
1660
Table 17: Indoor Blower Specifications (Belt Drive)
Size
(Tons)
Motor
Motor Sheave
Blower Sheave
Belt
HP
RPM
Eff.
SF
Frame
Datum Dia.
(in.)
Bore (in.) Model
Datum Dia.
(in.)
Bore (in.) Model
036
(3.0)
1-1/2
1725
0.8
1.15
56
2.8 - 3.8
7/8
1VL44
6.0
1
AK64
A37
1-1/2
1725
0.8
1.15
56
4.0 - 5.0
7/8
1VP56
6.2
1
AK66
A39
048
(4.0)
1-1/2
1725
0.8
1.15
56
2.8 - 3.8
7/8
1VL44
5.2
1
AK56
A36
1-1/2
1725
0.8
1.15
56
4.0 - 5.0
7/8
1VP56
5.7
1
AK61
A38
060
(5.0)
1-1/2
1725
0.8
1.15
56
2.8 - 3.8
7/8
1VL44
5.2
1
AK56
A36
2
1725
0.8
1.15
56
4.0 - 5.0
7/8
1VP56
5.2
1
AK56
A38
Table 18: Power Exhaust Specifications
Model
Voltage
Motor
Motor
Fuse
Size
CFM @
0.1 ESP
HP
RPM
QTY
LRA
FLA
MCA
2PE04703725
208/230-1-60
1/2
1725
1
1. Motors are multi-tapped and factory wired for high speed.
1
23.7
4.4
5.5
8
1350
2PE04703746
460-1-60
1/2
1725
1
1
4.1
1.7
2.1
5
1350
2PE04703758
575-3-60
1/2
1725
1
4.5
0.9
1.1
2
1350