OPERATION

COOLING SYSTEM

The cooling section is a complete factory package utilizing an 
air-cooled condenser. The system is factory-charged with 
Refrigerant-22. The compressor is hermetically sealed and 
internally sprung.

The compressors have inherent (internal) protection. If there 
is an abnormal temperature rise in the compressor, the pro-
tector will open to shut down the compressor.

PRELIMINARY OPERATION COOLING

After the installation has been completed, the crankcase 
heater of the compressor must be energized for at least 4 
hours before starting the unit. After this initial warm-up, the 
compressor should be given three false starts (energized just 
long enough to make a few revolutions) with a 5 minute delay 
between each start before being put into full time service.

NOTE: Prior to each cooling season, the crankcase heater 

must be energized at least 10 hours before the sys-
tem is put into operation.

COOLING SEQUENCE OF OPERATION

Single-Stage Cooling: When the thermostat calls for “cool-
ing”, “R” is closed to “G” and “Y1" (wiring schematic) which 
completes the low voltage control circuit, immediately ener-
gizing the compressors, condenser fan motor and blower 
motor simultaneously.

 Two-Stage Cooling: A two-stage cooling thermostat may be 
used if the unit has an economizer. First-stage cooling is pro-
vided by the economizer if the outdoor air enthalpy is accept-
able, and second-stage cooling is provided by the 
compressor. Jumper wire J1 must be removed. Refer to unit 
wiring diagram.

After the thermostat is satisfied and opens, the blower will 
continue to run for a short time. All other components will 
stop.

SAFETY CONTROLS

The refrigerant system is equipped with the following safety 
controls:

1.

A Suction Line Freezestat to protect against low evapo-
rator temperatures due to a low air flow or a low return 
air temperature.

2.

A  High Pressure Cutout Switch to protect against exces-
sive discharge pressures due to a blocked condenser 
coil or a condenser motor failure.

3.

A Low Pressure/Loss of Charge Switch to protect 
against loss of refrigerant charge.

If either of the above safety controls opens, the refrigerant 
system will be locked out. The lock out of the system can be 
reset by opening the 24V circuit either at the room thermostat 
or at the unit disconnect.

HEATING SEQUENCE OF OPERATION

The following sequence of operation is based on using a 
standard single-stage or two-stage heating thermostat.

WITH POWER TO UNIT AND THERMOSTAT IN THE HEAT-
ING MODE

Single-Stage Heating:

a.

If the fan switch is in the “ON” position, the evapora-
tor blower motor relay (BR) will be energized 
through terminal G to provide continuous blower 
operation. If the fan switch is in the “AUTO” position, 
the blower will operate only when there is a call for 
heating by the thermostat.

b.

Upon a call for heat by the thermostat, the first stage 
of heat will be energized. Sequencer 1S (or 

 

contactor 2M) is al-ways the first and last to com-
plete its timing cycle and controls power to the evap-
orator blower motor.

c.

The thermostat will cycle the electric heat to satisfy 
the heating requirements of the conditioned space.

Summary of Contents for SUNLINE ULTRA D1HE 036

Page 1: ...NING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if instal lation procedure is not handled properly CAUTION READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR FURNACE SAVE THIS MANUAL INSTALLATION MANUAL MODELS D1HE 036 048 and D2HE 060...

Page 2: ...OINTS 16 CHECKING SUPPLY AIR CFM 16 BELT DRIVE BLOWER 16 SECURE OWNER S APPROVAL 17 MAINTENANCE 17 NORMAL MAINTENANCE 17 LIST OF FIGURES Fig Pg 1 CENTER OF GRAVITY 5 2 RECOMMENDED DRAIN PIPING 6 3 ECOMONIZER RAIN HOOD ASSEMBLY OPTION 8 4 ENTHALPY SET POINT ADJUSTMENT 9 5 DIMENSIONS CLEARANCES 3 4 5 TONS 10 6 TYPICAL FIELD WIRING 11 7 BELT ADJUSTMENT 16 8 PRESSURE DROP ACROSS A DRY EVAPORATOR COIL ...

Page 3: ...age should be noted on the carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Refer to Form 50 15 NM for additional information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following ref erence forms RENEWAL PARTS Refer to Parts Manual for complete listing of replacemen...

Page 4: ... side of building 3 For ground level installation a level pad or slab should be used The thickness and size of the pad or slab used should meet local codes and unit weight Do not tie the slab to the building foundation 4 Roof structures must be able to support the weight of the unit and its options and or accessories Unit must be installed on a solid level roof curb or appropriate angle iron frame...

Page 5: ...e certain clearances for proper operation and service Installer must make provisions for adequate combus tion and ventilation air in accordance with Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 in U S A or Sections 7 2 7 3 or 7 4 of Gas Installation Codes CAN CGA B149 1 and 2 in Canada and or applicable provisions of the local building codes Refer to Fig...

Page 6: ...pre vent simultaneous operation of the compressor and the economizer If you want to control the econo mizer on a second stage of cooling use a thermo stat with two stages of cooling POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the National Electrical Code NEC ANSI NFPA 70 in USA cur rent Canadian Electric Code CEC C22 1 in Canada and or local ordinances The unit ...

Page 7: ...ollows Wire 73 to terminal Wire 74 to terminal S 5 Assemble the LH and RH side plates to the top cover 2 screws each side to form the hood Apply gasketing to the flange surface on each side plate Extend gasketing 1 4 beyond top and bottom of each flange to insure adequate corner sealing Secure this assembly to the unit back panel upper right hand corner First remove screw C on unit top cover Then ...

Page 8: ...to the A B C or D setting corresponding to the lettered curve For a dual enthalpy economizer carefully turn the set point adjusting screw fully clockwise past the D setting 10 To check that the damper blades move smoothly without binding carefully turn the minimum position adjusting screw fully clockwise and then energize and de energize terminals R to G With terminals R to G energized turn the mi...

Page 9: ...ighten screws after bracket is in place to ensure panels will remain leak tight Electric heaters are available as field installed accessories Refer to Form 530 18 N7 1V for installation instruction These UL approved heaters are located within the central compart ment of the unit see Figure 5 for access panel with the heat ing elements extending into the supply air chamber The heaters are wired for...

Page 10: ...035 13329 001 B 0504 10 Unitary Products Group FIGURE 5 DIMENSIONS CLEARANCES 3 4 5 TONS ...

Page 11: ... H E R M O S T A T 1 T E R M I N A L S U N I T T E R M I N A L S T R I P T B 1 2 4 V O L T T R A N S F O R M E R T O R E M O T E S E N S O R 2 T H 0 4 0 7 0 2 2 2 4 I F U S E D N O T U S E D A D D J U M P E R A D D J U M P E R 4 4 3 2 1 E L E C T R O N I C P R O G R A M M A B L E T H E R M O S T A T 2 E T 0 4 7 0 0 2 2 4 I N C L U D E S S U B B A S E 2 S E C O N D S T A G E C O O L I N G I S N O T...

Page 12: ...r to the Static Resistances Table for resistance values on applications other than gas electric units with side duct air flows TABLE 3 SUPPLY AIR PERFORMANCE 4 TON 4 TON GAS HEAT VALUES SHOWN 230 460 VOLTS SIDE DUCT CONNECTIONS UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 0...

Page 13: ...60 950 905 988 940 1022 970 1700 884 815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 142...

Page 14: ...ANGE RPM MOTOR ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT HP RPM FRAME SIZE SERVICE FACTOR PITCH DIA IN BORE PITCH DIA IN BORE PITCH LENGTH DESIGNATIONS DHE036 790 1 120 1 1 2 1 725 56 1 15 2 4 3 4 7 8 5 7 1 37 3 A36 DHE048 790 1 120 1 1 2 1 725 56 1 15 2 4 3 4 7 8 5 7 1 37 3 A36 DHE060 850 1 220 1 1 2 1 725 56 1 15 2 4 3 4 7 8 5 2 1 37 3 A36 All motors have solid bases and are inherently pr...

Page 15: ...umper wire J1 must be removed Refer to unit wiring diagram After the thermostat is satisfied and opens the blower will continue to run for a short time All other components will stop SAFETY CONTROLS The refrigerant system is equipped with the following safety controls 1 A Suction Line Freezestat to protect against low evapo rator temperatures due to a low air flow or a low return air temperature 2...

Page 16: ... for blower motor and drive data The tension on the belts should be adjusted as shown in Figure 7 Start the supply air blower motor Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be done by someone other than the equipment installer To check the supply ...

Page 17: ... the owner s approval Show him the location of all disconnect switches and the thermostat Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system MAINTENANCE NORMAL MAINTENANCE FILTERS Inspect once a month Replace disposable or clean permanent type as necessary DO NOT replace perma nent type with disposable MOTORS Indoor fan and outdoor ...

Page 18: ...035 13329 001 B 0504 18 Unitary Products Group ...

Page 19: ...035 13329 001 B 0504 Unitary Products Group 19 ...

Page 20: ...to change without notice Printed in U S A 035 13329 001 B 0504 Copyright 2004 by Unitary Products Group All rights reserved Supersedes 035 13329 001 A 0204 Unitary 5005 Norman Products York OK Group Drive 73069 ...

Reviews: