035-13329-001-B-0504
14
Unitary Products Group
TABLE 5: STATIC RESISTANCES
EXTERNAL STATIC PRESSURE DROP
DESCRIPTION
RESISTANCE, IWG
CFM
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
Economizer
* †
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.30
Electric Heaters
1
5 - 15 KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.19
0.22
20 - 30 KW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
0.19
0.22
Cooling Only
‡
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
*.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
†.
The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG,
the unit will deliver less CFM
‡.
Add these resistance values to the available static resistance in the respective Blower Performance Table.
TABLE 6: MOTOR AND DRIVE DATA- BELT-DRIVE BLOWER
MODEL
BLOWER
RANGE
(RPM)
MOTOR
*
ADJUSTABLE
MOTOR PULLEY
FIXED
BLOWER PULLEY
BELT
HP
RPM
FRAME
SIZE
SERVICE
FACTOR
PITCH
DIA. (IN.)
BORE
PITCH DIA. (IN.)
BORE
PITCH
LENGTH
DESIGNATIONS-
DHE036
790 - 1,120
1-1/2
1,725
56
1.15
2.4 - 3.4
7/8
5.7
1
37.3
A36
DHE048
790 - 1,120
1-1/2
1,725
56
1.15
2.4 - 3.4
7/8
5.7
1
37.3
A36
DHE060
850 - 1,220
1-1/2
1,725
56
1.15
2.4 - 3.4
7/8
5.2
1
37.3
A36
*.
All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air,
upstream of any
heating device
TABLE 7: ELECTRICAL DATA- BASIC UNIT
MODEL
DHE
POWER
SUPPLY
VOLTAGE LIMITATIONS
(SEE NOTE 1)
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
TOTAL UNIT
AMPACITY
AMPS
MAX. FUSE
SIZE (SEE
NOTE 2) AMPS
MAX HACR
BREAKER
SIZE AMPS
MIN.
MAX.
RLA
LRA
FLA
036
208/230-3-60
187
253
14.1
110.0
2.3
5.3
25.2
35
35
460-3-60
414
504
7.1
54.0
1.4
3.1
13.3
20
20
048
208/230-3-60
187
253
10.0
110.0
2.3
5.2
23.9
35
35
460-3-60
414
504
5.2
54.0
1.4
2.6
12.4
15
15
060
208/230-3-60
187
253
16.0
137.0
2.3
6.0
28.3
40
40
460-3-60
414
504
8.3
69.0
1.4
3.0
14.8
20
20
Note: 1. Rated in accordance with ARI Standard 110, utilization range “A”. 2. Dual Element, time delay type. 3. Based on 75º copper conductors.