background image

036-21411-002-A-0204

4

Unitary Products Group

voltage terminal strip. An additional set of pin connectors is
also provided to simplify the field interface of external con-
trols. Mate--n--lock plug connectors are used where line and
low voltage wires pass through internal bulkheads. This
allows for easier troubleshooting and component replace-
ment. The electrical control box is not located in the compres-
sor compartment so the access cover can be removed for
troubleshooting without affecting the normal system operat-
ing pressures.

AIR FILTERS -- Units are shipped with 1" throwaway filters.
The unit filter racks can accommodate 1" or 2" filters without
any modifications.

FACTORY-INSTALLED OPTIONS

ECONOMIZERS: Units equipped with a factory-installed
economizer option have dampers that are positioned by a
spring return, fully modulating damper actuator and are capa-
ble of introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is determined by a single input electronic enthalpy
control or by a dual input electronic enthalpy control. Simulta-
neous compressor and economizer operation is also possi-
ble.

The single enthalpy system contains a sensor that monitors
the outdoor air which automatically operates the damper
actuator allowing the dampers to open or close.

The dual enthalpy system contains a second sensor that
monitors both the temperature and the humidity of the return
air in addition to the outdoor air sensor described for a single
enthalpy system. The logic module compares the inputs from
both sensors and switches to economizer operation when-
ever the outdoor air is cooler than the return air for maximum
efficiency of the economizer system.

The economizer is completely wired and installed at the fac-
tory. Only the outdoor air hood, including its filters, need be
assembled and installed in the field.

BELT DRIVE BLOWERS: Adjustable belt-drive blowers pro-
viding maximum flexibility to handle many airflow require-
ments, are available on all models.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -
Includes a slide-in / plug-in damper assembly with fully modu-
lating spring return motor actuator capable of introducing up
to 100% outdoor air, one outdoor air electronic enthalpy sen-
sor and a rain hood with filters. The rain hood is painted to
match the basic unit and must be field-assembled before
installation. Economizer dampers are 2% low leakage type.

DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER -
Includes the same damper system and rain hood with filters
as described for a single enthalpy economizer except this
accessory contains two enthalpy sensors. It uses a differen-
tial enthalpy control that compares the outdoor air versus the
return air. The logic module then optimizes the economizer
operation for additional savings over the single input econo-
mizer.

MOTORIZED AIR DAMPER - Includes a slid-in/plug-in
damper assembly with a rainhood and filters. The outdoor air
dampers open when the indoor fan motor is energized. The
damper is capable of providing 0% through 100% of outdoor
return air opening.

MANUAL OUTDOOR DAMPER - Provides 0% through 35%
or 0% through 100% of return air opening (field adjustable).
Designed for duct mounted side or bottom supply/return
applications. Includes rain hood assembly and filter.

ELECTRIC HEATERS - Include nickel chromium elements, a
terminal block, fuses (where required by UL), all the neces-
sary connectors and hardware. All heaters utilize single point
power supply hookup. Capacities from 5 KW through 30 KW
heating are available.

FUSE BLOCK KITS - These kits have a fuse box with a fuse
block and fuses. They're available for all 460-3-60 volt heat-
ers and 208/230-3-60 volt heaters 7 KW and smaller.

OUTDOOR THERMOSTAT - A 24-volt thermostat providing
two stages of control for units equipped with electric heat
accessories.

ROOF CURB - This 14" high full perimeter roof curb is
shipped knocked down for field assembly and contains duct
supports that can easily be shifted for the desired unit duct
arrangement. No insulated deck is required because the unit
underside is insulated.

START ASSIST KIT - Provides increased starting torque for
single phase units in areas with low voltage conditions. It con-
tains a 12.5 OHM PTCR temperature resistor with a support
clip and hardware for mounting.

LOW AMBIENT KIT - A head pressure controller maintains
stable system operation by reducing the speed of the con-
denser fan motor when the outdoor temperature is between
45 and 0 ºF. Condenser fan motors with ball bearings and
heavier windings are also available for these low ambient
applications.

ANTI-RECYCLE TIMER - A timer to prevent the unit com-
pressor from short cycling. It assures a 5-minute off-time
between compressor cycles.

Summary of Contents for SUNLINE PLUS D1EE036

Page 1: ...d gas heat The units are completely assembled on rigid permanently attached base rails All piping refriger ant charge and electrical wiring is factory installed and tested The units require only electric power and duct con nections at the point of installation FEATURING COMMON FOOTPRINT COMMON CABINET HIGH EFFICIENCY CONVERTIBLE AIRFLOW DESIGN OPTIONAL MOTORIZED AIR DAMPER OPTIONAL MANUAL OUTDOOR ...

Page 2: ...NG ELECTRIC HEATING 7 2 CAPACITY RATINGS COOLING GAS HEATING 7 3 SOUND POWER RATINGS 7 4 PHYSICAL DATA BASIC UNIT 8 5 COOLING CAPACITIES 3 TON DEE DEG036 9 6 COOLING CAPACITIES 4 TON DEE DEG048 10 7 COOLING CAPACITIES 5 TON DEE DEG060 11 8 SUPPLY AIR BLOWER PERFORMANCE DEE DEG036 W BELT DRIVE SIDE DUCT 12 9 SUPPLY AIR BLOWER PERFORMANCE DEE DEG048 W BELT DRIVE SIDE DUCT 13 10 SUPPLY AIR BLOWER PER...

Page 3: ...ain hood needs to be field assembled and installed Field labor dollars can be saved by having the components arrive already installed Adjustable belt drive blowers are available on all models from the factory for complete airflow flexibility FIELD INSTALLED ACCESSORIES Accessories were designed for quick and easy installation The motorized damper and economizers simply slide in and electrical con ...

Page 4: ... outdoor air electronic enthalpy sen sor and a rain hood with filters The rain hood is painted to match the basic unit and must be field assembled before installation Economizer dampers are 2 low leakage type DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER Includes the same damper system and rain hood with filters as described for a single enthalpy economizer except this accessory contains two enthalpy ...

Page 5: ... E C T D R I V E B L O W E R M O T O R B e l t D r i v e O p t i o n a l s o a v a i l a b l e o n s o m e m o d e l s 2 0 G A U G E A L U M I N I Z E D S T E E L T U B U L A R H E A T E X C H A N G E R L O N G L A S T I N G P O W D E R P A I N T F I N I S H E L E C T R I C A L D I S C O N N E C T M O U N T I N G L O C A T I O N F i e l d I n s t a l l e d E C O N O M I Z E R H O O D O U T D O O R...

Page 6: ... 49 5 11 0 10 0 86 125 99 80 3 80 6 45 75 1 2 DEG060N079 58 5 11 0 10 05 86 100 79 80 5 80 8 25 55 1 2 DEG060N099 58 5 11 0 10 05 86 125 99 80 3 80 6 35 65 1 2 1 Ratings are in accordance with ARI Standard 210 2 Sound ratings are in accordance with ARI Standard 270 3 AFUE Annual Fuel Utilization Efficiency determined in accordance with DOE test procedure 4 S S E Steady State Efficiency Percent Out...

Page 7: ...Sq Ft 3 13 3 6 3 13 4 3 3 13 5 1 CONDENSER FAN Propeller Dia in Fan Motor HP Nom CFM Total 22 1 2 4 500 22 1 2 4 200 22 1 2 4 500 CONDENSER COIL Rows Deep Fins Per Inch Face Area Sq Ft 2 18 17 1 2 18 17 1 2 18 17 1 AIR FILTERS1 Quantity Per Unit 15 x 20 x 1 Quantity Per Unit 14 x 25 x 1 Total Face ARea Sq Ft 2 1 6 6 2 1 6 6 2 1 6 6 SYSTEM CHARGE Refrigerant 22 Lbs Oz 9 12 9 8 9 8 COMPRESSOR Quanti...

Page 8: ...SENSIBLE CAPACITY1 MBH TOTAL CAP 1 MBH POWER INPUT2 kW SENSIBLE CAPACITY1 MBH ENTERING DRY BULB F ENTERING DRY BULB F CFM WB F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 1500 72 47 3 9 33 29 25 20 16 43 4 1 32 28 23 19 14 67 44 3 8 43 39 35 30 26 22 17 40 4 1 40 38 33 29 24 20 16 62 36 3 7 36 36 36 31 27 22 18 33 4 0 33 33 33 28 24 19 15 57 36 3 7 36 36 36 31 27 23 18 33 3 9 33 33 33 28 24 20 15 13...

Page 9: ...ENSIBLE CAPACITY1 MBH TOTAL CAP 1 MBH POWER INPUT2 kW SENSIBLE CAPACITY1 MBH ENTERING DRY BULB F ENTERING DRY BULB F CFM WB F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2000 72 56 4 7 42 36 30 25 19 53 5 2 41 35 29 23 17 67 50 4 6 50 45 39 33 28 22 16 47 5 1 47 44 38 32 26 20 14 62 47 4 5 47 47 47 41 35 29 23 44 5 0 44 44 44 38 32 26 20 57 47 4 5 47 47 47 44 38 32 26 44 5 0 44 44 44 42 36 30 24 180...

Page 10: ...NSIBLE CAPACITY1 MBH TOTAL CAP 1 MBH POWER INPUT2 kW SENSIBLE CAPACITY1 MBH ENTERING DRY BULB F ENTERING DRY BULB F CFM WB F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2500 72 66 5 5 51 44 36 29 21 60 6 0 49 41 34 26 19 67 59 5 5 58 54 46 39 31 24 16 53 6 0 53 51 43 36 28 21 13 62 55 5 4 55 55 55 47 40 32 25 49 5 9 49 49 49 42 34 27 19 57 49 5 4 49 49 49 42 35 27 20 44 5 9 44 44 44 37 29 22 15 2250...

Page 11: ... 922 835 962 895 1400 833 650 867 705 904 765 942 820 1300 858 665 893 725 932 785 1200 847 640 880 680 916 730 MODEL DEE DEG AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG3 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 036 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 10...

Page 12: ... 922 835 962 895 1400 833 650 867 705 904 765 942 820 1300 858 665 893 725 932 785 1200 847 640 880 680 916 730 MODEL DEE DEG AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG3 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 048 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 10...

Page 13: ... 988 940 1022 970 1700 884 815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 MODEL DEE DEG AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG3 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 14...

Page 14: ... 1629 855 MED 1990 950 1911 920 1828 885 1724 835 1604 798 LOW 1905 880 1816 838 1724 800 1644 770 1531 710 1 Side Duct application 230 460 575 Volts 2 Includes allowances for a wet evaporator coil 1 filters and the heat exchangers Refer to Table 12 for resistance val ues on applications other than gas electric units with side duct airflows TABLE 12 STATIC RESISTANCES DESCRIPTION RESISTANCE IWG CF...

Page 15: ...NIT W DIRECT DRIVE ELECTRICAL DATA MODEL DEE DEG POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR CON FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA MINIMUM CIRCUIT AMPACITY MAX FUSE SIZE2 AMPS MAX HACR BREAKER SIZE AMPS MIN MAX RLA LRA 036 208 230 1 60 187 253 16 7 87 2 3 4 4 27 5 40 40 208 230 3 60 187 253 13 1 110 2 3 4 4 23 1 35 35 460 3 60 414 504 6 7 54 1 4 2 2 12 0 15 15 575 3 603 518 630 5 1 44 1 4...

Page 16: ... 35 35 460 3 60 414 504 6 7 54 1 4 2 6 12 4 20 20 575 3 603 518 630 5 1 44 1 4 2 0 9 8 15 15 048 208 230 1 60 187 253 18 7 135 2 3 8 6 42 6 60 60 208 230 3 60 187 253 11 9 130 2 3 5 2 26 3 40 40 460 3 60 414 504 6 3 64 1 4 2 6 14 3 20 20 575 3 603 518 630 4 9 52 1 4 2 0 11 4 15 15 060 208 230 1 60 187 253 32 1 169 2 3 8 6 51 0 80 80 208 230 3 60 187 253 19 3 123 2 3 6 0 32 4 50 50 460 3 60 414 504...

Page 17: ... 5 6 1 15 6 25 0 35 35 2CE04501025 8 0 1 22 1 33 1 35 35 2CE04501525 11 9 2 33 1 46 9 50 50 2CE04502025 15 9 2 44 2 60 7 70 70 230 3 60 2CE045005253 4 4 5 3 1 12 7 24 3 35 35 2CE045007253 7 5 1 18 0 28 1 35 35 2CE04501025 10 6 1 25 5 37 4 40 40 2CE04501525 15 9 2 38 2 53 3 60 60 2CE04502025 21 2 2 51 0 69 2 70 70 460 3 60 2CE045007463 2 2 6 8 1 8 2 13 0 15 15 2CE045010463 10 1 1 12 1 17 9 20 20 2C...

Page 18: ...61 4 70 70 230 3 60 2CE045005253 5 0 5 3 1 12 7 25 7 40 40 2CE045007253 7 5 1 18 0 28 8 40 40 2CE04501025 10 6 1 25 5 38 0 40 40 2CE04501525 15 9 2 38 2 54 0 60 60 2CE04502025 21 2 2 51 0 70 0 70 70 460 3 60 2CE045007463 2 2 6 8 1 8 2 13 2 20 20 2CE045010463 10 1 1 12 1 17 9 20 20 2CE045015463 13 6 1 16 4 23 2 25 25 2CE045020463 19 5 2 23 5 32 1 35 35 575 3 60 2CE04501058 2 2 10 6 1 10 2 15 5 20 2...

Page 19: ...E04501025 8 0 1 22 1 35 9 50 50 2CE04501525 11 9 2 33 1 49 7 50 50 2CE04502025 15 9 2 44 2 63 5 70 70 2CE04503025 22 2 2 61 7 85 4 90 90 230 3 60 2CE045005253 6 0 5 3 1 12 7 33 0 50 50 2CE045007253 7 5 1 18 0 33 0 50 50 2CE04501025 10 6 1 25 5 40 1 50 50 2CE04501525 15 9 2 38 2 56 1 60 60 2CE04502025 21 2 2 51 0 72 0 80 80 2CE04503025 29 6 2 71 2 97 3 100 100 460 3 60 2CE045007463 3 0 6 8 1 8 2 17...

Page 20: ...1 10 2 16 6 20 20 2CE04501558 15 9 1 15 3 23 0 25 25 2CE04502058 21 2 2 20 4 29 4 30 30 048 208 1 60 2CE04500506 8 6 4 0 1 19 1 42 2 60 60 2CE04500706 5 6 1 27 1 44 4 60 60 2CE04501006 8 0 1 38 3 58 8 60 60 2CE04501506 11 9 2 57 4 82 3 90 90 2CE04502006 15 9 2 76 6 106 3 110 110 230 1 60 2CE04500506 8 6 5 3 1 22 1 42 2 60 60 2CE04500706 7 5 1 31 2 49 8 60 60 2CE04501006 10 6 1 44 2 66 0 70 70 2CE0...

Page 21: ...50 50 2CE04501025 8 0 1 22 1 35 1 50 50 2CE04501525 11 9 2 33 1 48 9 50 50 2CE04502025 15 9 2 44 2 62 7 70 70 2CE04503025 22 2 2 61 7 84 6 90 90 230 3 60 2CE045005253 6 0 5 3 1 12 7 32 4 50 50 2CE045007253 7 5 1 18 0 32 4 50 50 2CE04501025 10 6 1 25 5 39 4 50 50 2CE04501525 15 9 2 38 2 55 3 60 60 2CE04502025 21 2 2 51 0 71 2 80 80 2CE04503025 29 6 2 71 2 96 5 100 100 460 3 60 2CE045007463 3 0 6 8 ...

Page 22: ... E 2 S E C O N D S T A G E C O O L I N G I S N O T R E Q U I R E D O N U N I T S L E S S E C O N O M I Z E R 3 S E C O N D S T A G E H E A T I N G I S O N L Y R E Q U I R E D O N U N I T S W I T H A T W O S T A G E E L E C T R I C H E A T E R 4 R E M O V E J U M B E R J 2 F R O M T E R M I N A L S 4 A N D 9 O N J U M P E R P L U G C O N N E C T O R P 6 O N U N I T S W I T H E C O N M I Z E R T E R...

Page 23: ... U N I T H A S A N D E C O N O M I Z E R R E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D 1 0 O N T H E R E L A Y B O A R D T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C O M P R E S S O R A N D T H E E C O N O M I Z E R I F Y O U W A N T T O C O N T R O L T H E E C O N O M I Z E R O N A S E C O N D S T A G E O F C O O L I N G U S E T H E R M O S T A T 2 E T 0...

Page 24: ...e slice in the insulation Control Wiring Side or Bottom 2 2 DO NOT remove the 2 knockout ring B 2 Power Wiring Side or Bottom C 1 5 8 Gas Piping Front D 1 1 2 Gas Piping Bottom FIGURE 10 ACCESS PANELS AND DISCONNECT R E T U R N A I R S U P P L Y A I R O U T D O O R A I R O U T D O O R A I R E c o n o m i z e r All dimensions are in inches They are subject to change without notice Cer tified dimens...

Page 25: ...feet from or 1 foot above any door or gravity air inlet into the building Four feet from electric meters gas meters regulators and relief equipment FIGURE 11 UNIT DIMENSIONS DEG 3 4 5 TON DEG UNITS 3 5 TON TABLE 24 DEE DEG UNIT CLEARANCES FRONT DEE UNITS 24 DEG UNITS 32 BACK 12 Less Economizer 36 With Economizer or Fixed Air Motorized Damper LEFT SIDE Filter Access 24 Less Economizer 36 With Econo...

Page 26: ... the unit For bottom duct applications Remove the side supply air duct cover to gain access to the bottom supply air knockout panel Remove and discard the bottom knockout panel Replace the side duct cover With filter section access panel removed from the unit remove and discard the bottom return air knockout panel Replace the filter Access panel FIGURE 12 DEE DEG DIMENSIONS REAR VIEW 3 4 5 TON 17 ...

Page 27: ...IT DIMENSIONS WITH DAMPER RAINHOOD FIGURE 14 UNIT CURB APPLICATION 2 7 1 2 7 1 4 2 7 1 2 1 9 1 8 A 4 4 7 8 4 3 8 3 1 2 8 1 4 1 0 1 4 L H E N D V I E W R E A R V I E W D I M E N S I O N A F I X E D O U T D O O R A I R D A M P E R 1 2 M O T O R I Z E D D A M P E R 1 6 1 2 ...

Page 28: ...5 173 170 135 137 DEG060 640 180 177 140 143 FIGURE 16 CENTER OF GRAVITY C O N D E N S E R C O I L E N D O F U N I T A P P R O X I M A T E C E N T E R O F G R A V I T Y F R O N T B A C K 4 4 7 8 8 2 1 2 4 0 3 4 1 9 3 4 C O R N E R A C O R N E R B C O R N E R C C O R N E R D TABLE 26 ACCESSORY S WEIGHT DESCRIPTION ECONOMIZER 50 MOTORIZED OUTDOOR AIR DAMPER 26 ELECTRIC HEAT nom kW DEE only 5 7 kW 18...

Page 29: ...036 21411 002 A 0204 Unitary Products Group 29 FIGURE 17 TYPICAL APPLICATIONS FIGURE 18 TYPICAL ROOF TOP INSTALLATION ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION ...

Page 30: ...llow accurate air measure ments of evaporator fan performance without removing panels or creating air by pass of the coils 7 Units vertical discharge and return duct configuration shall be designed to fit between standard 24 O C beams without modification to building structure duct work and base unit 8 Condensate pan shall be internally sloped and conform to ASHARE 62 89 self draining standards Co...

Page 31: ... adjustments 4 All gas piping shall enter the unit cabinet at a single loca tion through either the side or bottom without any field modifications 5 An integrated control board shall provide timed control of evaporator fan functioning and burner ignition 6 Heating section shall be provided with the following mini mum protection a Primary and auxiliary high temperature limit switches b Induced draf...

Page 32: ... temperature from dropping below 55 ºF Changeover from compressor to economizer operation shall be pro vided by two integral electronic enthalpy controls one that senses outdoor air and one that senses indoor air Both enthalpy sensors supply input to the logic module which modulates both sets of dampers for maximum economizer savings The outdoor intake opening shall be covered with a rain hood tha...

Reviews: