036-21539-003-B-0305
30
Unitary Products Group
TABLE 16: COOLING CAPACITIES FOR DR300 AT 85°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 85
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
TOTAL
INPUT
2
(kW)
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86
83
80
77
74
71
7500
67
126
23.7
52
31
10
62
114
22.7
114
108
87
65
44
22
57
93
22.3
93
93
93
72
50
29
7750
67
127
23.7
54
31
9
62
115
22.7
115
101
79
57
34
12
57
94
22.3
94
94
94
72
50
27
8000
67
128
23.7
55
31
8
62
115
22.7
115
95
72
48
25
2
57
94
22.3
94
94
96
72
49
26
9750
67
136
23.5
72
43
14
62
123
22.5
123
113
101
73
44
15
57
101
22.1
101
101
101
72
44
15
11500
67
145
23.3
89
55
21
62
131
22.3
131
131
131
97
62
28
57
107
21.9
107
107
107
73
38
4
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
No Sensible Cooling Capacity
TABLE 17: COOLING CAPACITIES FOR DR300 AT 95°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 95
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
TOTAL
INPUT
2
(kW)
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86
83
80
77
74
71
7500
67
118
24.6
47
26
4
62
106
23.5
71
50
28
7
57
87
23.1
82
60
39
18
7750
67
119
24.7
52
30
7
62
107
23.6
89
69
47
25
2
57
88
23.3
85
74
65
43
21
8000
67
120
24.9
57
34
10
62
107
23.7
107
89
66
42
19
57
88
23.4
88
88
91
68
45
21
9750
67
120
24.8
67
38
9
62
108
23.7
108
88
59
30
2
57
88
23.3
88
88
82
54
25
11500
67
121
24.7
77
42
8
62
108
23.6
108
87
53
18
57
89
23.2
89
89
73
39
5
No Sensible Cooling Capacity