036-21539-003-B-0305
Unitary Products Group
29
TABLE 14: COOLING CAPACITIES FOR DR240 AT 105°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 105
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
TOTAL
INPUT
2
(kW)
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86
83
80
77
74
71
6000
67
46
9.4
20
11
3
62
42
9.1
25
17
8
57
40
9.0
27
18
10
6875
67
70
14.5
40
24
9
62
64
14.1
56
51
37
57
61
13.9
54
50
42
7750
67
95
19.6
60
38
15
62
86
19.0
86
86
66
44
21
57
82
18.8
82
82
75
52
30
7
8725
67
72
14.5
49
30
12
62
65
14.1
65
64
47
21
57
62
13.9
62
62
54
28
2
9400
67
48
9.4
37
23
8
62
44
9.1
44
42
28
57
42
9.0
42
42
32
4
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
No Sensible Cooling Capacity
TABLE 15: COOLING CAPACITIES FOR DR240 AT 115°F (ALTERNATE REHEAT MODE)
AIR ON
EVAPORATOR COIL
TEMPERATURE OF AIR ON CONDENSER COIL (°F): 115
CFM
WB
°F
TOTAL
CAPACITY
1
(MBH)
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
TOTAL
INPUT
2
(kW)
2. These ratings include condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
SENSIBLE CAPACITY
1
(MBH)
RETURN DRY BULB (°F)
86
83
80
77
74
71
6000
67
62
57
6875
67
43
10.3
27
16
4
62
39
10.0
39
39
31
11
57
38
9.9
38
38
34
14
7750
67
86
20.6
54
31
9
62
78
20.0
78
78
62
39
17
57
75
19.9
75
75
68
45
22
8725
67
43
10.3
27
16
4
62
39
10.0
39
39
31
5
57
38
9.9
38
38
34
8
9400
67
62
57
No Sensible Cooling Capacity