background image

Before brazing the refrigerant lines to these connections,
remove the short panel from the unit frame and slide it
(along with the grommets) onto the refrigerant lines. Af-
ter the brazed joints have cooled, slide the panel back
into place and secure it to the unit frame.

NOTE: These units can only be piped from one side of

the unit.

EXPANSION VALVE BULB

On KEU090 units the expansion valve bulb must be fas-
tened in a 4 o'clock position to the suction line outside the
cabinet after the piping connections have been made.

On KEU120 units fasten the expansion valve bulb on the
suction header 8" (203mm) below the top of the header
and adjacent to the coil.

Use the clamps provided with the valve to secure the
bulb in position.

DRAIN CONNECTION

The drain line

MUST

be trapped because the coil is lo-

cated on the negative side of the supply air blower. It
must also be protected from freezing temperatures.

A

7

8

" (22.2mm) OD stub connection is provided within

the cabinet on both ends of the condensate drain pan for
either left hand or right hand piping connections. Refer to
Figure 5 for recommended drain piping.

The drain line is located on the same end of the coil sec-
tion as the refrigerant connections. The line should be in-
sulated where moisture drippage will be objectionable or
cause damage to the area. Seal the unused drain con-
nection with a suitable mastic.

The 3" (76mm) dimension must equal or exceed the
negative static pressure developed by the supply air
blower. If it does not, condensate will not drain properly
and may overflow the drain pan. The trap must be at least
2

1

2

" (63mm) deep to maintain a water seal under all oper-

ating conditions, especially during blower start-up.

NOTE: Refer to Figure 9 for minimum clearance require-

ments.

SUPPLY AIR BLOWER ADJUSTMENT

The RPM of the supply air blower will depend on the re-
quired airflow, the unit accessories and the static resis-
tances of both the supply and the return air duct
systems. With this information, the RPM for the supply
air blower can be determined from the blower perform-
ance in Table 4.

Knowing the required blower RPM and the blower motor HP,
the setting (turns open) for the supply air motor pulley can be
determined from Table 3.

Each motor pulley has:

1. A threaded barrel with two flats (or notched recesses) 180

degrees apart.

2. A movable flange with one set screw.

After the movable flange has been rotated to the proper
number of “turns open”, the set screw should be tight-
ened against the flat on the barrel to lock the movable
flange in place. If the pulley includes a locking collar, the
locking collar must be loosened to adjust the setting of
the movable flange.

Note the following:

1. The supply airflow must be within the limitations shown in

Table 1.

2. All pulleys can be adjusted in half-turn increments.

3. The tension on the belt should be adjusted for a deflection

of

3

16

" (5mm) per foot (305mm) of belt span with an applied

force of approximately 3 lbs (1.4kg). This adjustment is
made by moving the blower motor mounting plate. Refer to
Figure 6. Turning the adjustment bolt (B) moves the motor
mounting plate up or down. Note - Never loosen the two
nuts (C). Four hex nuts (A) have to be loosed to move the
mounting plate and retightened after the mounting plate
has been moved to the proper position.

4. All pulleys are factory aligned.

5. All supply air motor pulleys are factory set at three “turns

open.”

After the supply air blower motor is operating, adjust the
resistances in both the supply and the return duct sys-
tems to balance the air distribution throughout the condi-
tioned space. The job specifications may require that
this balancing be done by someone other than the equip-
ment installer.

To check the supply air airflow after the the initial balancing has
been completed:

1. Drill two holes

5

16

" (8mm) dia. in the side panel as shown in

Figure 8.

2. Insert at least 8" (200mm) of

1

4

" (6.3mm) O.D. tubing into

each of these holes for sufficient penetration into the air
flow on both sides of the evaporator coil.

NOTE: The tubes must be inserted and held in a position per-

pendicular to the air flow so that velocity pressure will

not affect the static pressure reading.

6

Unitary Products Group

550.39-N4YI

FIG. 5

- RECOMMENDED DRAIN PIPING

(64)

(76)

Summary of Contents for SUNLINE K4EU120A50A

Page 1: ...nt parts on this equipment All forms may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York PA 17405 INSPECTION As soon as a unit is received it should be inspec...

Page 2: ...pA 9 6 Electrical Data 9 7 Blower Motor and Drive Data 11 FIGURES No Description Page 1 Unit Suspension Mounting Horizontal 3 2 Vertical and Horizontal Appplication 4 3 Supply Air Duct Connection 4 4...

Page 3: ...m or they can be supported by metal or wooden beams Units being installed horizontally can be suspended from above Four 3 8 9 5mm weld nuts are provided in the unit frame to accommodate hanger rods Kn...

Page 4: ...designed and installed in accordance with applicable national and or local codes Refer to Figure 3 for suggested method of connecting supply air ductwork Ducts should be sized no smaller than the duct...

Page 5: ...has no leaks and proceed with the installation Make sure the refrigerant in the lines has been recovered then drill a small hole through the discs to prevent any internal pres sure from blowing them o...

Page 6: ...be determined from the blower perform ance in Table 4 Knowing the required blower RPM and the blower motor HP the setting turns open for the supply air motor pulley can be determined from Table 3 Eac...

Page 7: ...G Failure to properly adjust the total system air quan tity can result in extensive blower damage After readings have been obtained remove the tubes and seal up the drilled holes in the side panel wit...

Page 8: ...FORMANCE1 CFM BLOWE R SPEED RPM AIRFLOW ESP2 IWG OUTPUT BHP INPUT kW ESP2 IWG OUTPUT BHP INPUT kW ESP2 IWG OUTPUT BHP INPUT kW ESP2 IWG OUTPUT BHP INPUT kW ESP2 IWG OUTPUT BHP INPUT kW 3200 3600 4000...

Page 9: ...STATIC PRESSURE DROP RESISTANCE IWG pA BLOWER CFM m3 s 3200 1 5 3600 1 7 4000 1 9 4400 2 1 4800 2 3 Electric Heat 10 kW 0 02 5 0 0 02 5 0 0 03 7 4 0 03 7 4 0 04 10 0 16 kW 0 03 7 4 0 04 10 0 0 05 12 4...

Page 10: ...access if the piping connections are made on the opposite side of the unit Allow enough clearance to trap the condensate drain line ACCESSORIES ELECTRIC HEATER Add 15 381mm to Unit Height when using 1...

Page 11: ...KEU090 11 2 1 1 650 850 3 4 4 4 86 112 7 8 22 2 7 5 190 1 25 A37 38 3 973 KEU120 2 1 5 700 910 3 4 4 4 86 112 7 8 22 2 7 0 178 1 25 A37 38 3 973 TABLE 7 BLOWER MOTOR AND DRIVE DATA All motors are 1450...

Page 12: ...the filter access panel EVAPORATOR COIL Do not allow dirt to accumulate on the evaporator coil or other parts of the evaporator air circuit Clean as often as necessary to assure good system performan...

Reviews: