4
Unitary Products Group
550.39-TG5YI
SUPPLY AIR BLOWER PERFORMANCE
1
- (m
3
/s)
BLOWER
SPEED
RPM
AIRFLOW
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
2.26 m
3
/s
2.55 m
3
/s
2.83 m
3
/s
3.11 m
3
/s
3.40 m
3
/s
600
114
1.07
1.34
74
1.25
1.56
27
1.46
1.80
-
-
-
-
-
-
615
136
1.15
1.43
99
1.33
1.64
55
1.55
1.90
3
1.08
2.20
-
-
-
700
208
1.36
1.68
174
1.58
1.94
134
1.81
2.22
89
2.06
2.54
30
2.32
2.82
800
312
1.77
2.17
285
2.01
2.47
248
2.26
2.74
206
2.51
3.05
154
2.79
-
900
422
2.20
2.68
404
2.46
2.99
311
2.73
-
-
-
-
-
-
-
SUPPLY AIR BLOWER PERFORMANCE
1
- (CFM)
BLOW
SPEED
ER
RPM
AIRFLOW
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(KW)
ESP
2
(IWG)
OUTPUT
(BHP
)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP
)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW
4800 CFM
5400 CFM
6000 CFM
6600 CFM
7200 CFM
600
0.46
1.44
1.34
0.30
1.68
1.56
0.11
1.96
1.80
-
-
-
-
-
-
615
0.55
1.54
1.43
0.40
1.79
1.64
0.22
2.08
1.90
0.01
2.41
2.20
-
-
-
700
0.84
1.83
1.68
0.70
2.12
1.94
0.54
2.43
2.22
0.36
2.77
2.54
0.12
3.12
2.82
800
1.26
2.38
2.17
1.15
2.70
2.47
1.00
3.03
2.74
0.83
3.37
3.05
0.62
3.75
-
900
1.70
2.95
2.68
1.63
3.30
2.99
1.52
3.67
-
-
-
-
-
-
-
1
Unit resistance is based on a wet evaporator coil and clean filters.
2
Available static pressure in Pa (IWG) to overcome the resistance of the duct system and any accessories added to the unit.
NOTE: Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any
heating device.
LEGEND:
SUPPLY AIR BLOWER PERFORMANCE
Exceeds the output limitation of the standard
factory-mounted blower motor.
RPM range for standard factory-
mounted drive components.