NOTES: 

1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 1

5° 

superheat and 1

5° 

sub-cooling at condensing unit.

a. Increase capacity 1% for each 

2° 

increase in sub-cooling.

b. Decrease capacity 1% for each 

2° 

decrease in sub-cooling.

3. Sub-cooling in excess of 2

0° 

may result in excessively high condensing temperature with air on condenser above 115°F.

Maximum recommended condensing temperature is 140°F.

ACCESSORIES

Refer to Price Manual for specific model numbers.

Off Cycle Timer -

 Provides a 5 minute off cycle to prevent

rapid recycling of the compressor.

Room Thermostats -

 A wide selection of matching thermo-

stats is available to provide features required for any installa-
tion.

Start Assist Kit - 

Provides increased starting torque for

areas with low voltage conditions.

Compressor Blanket -

 Designed to further reduce the nor-

mal operating sounds of H3DA units.

COOLING PERFORMANCE 

MODEL

SUCT.T/P @ COMPR.

AIR TEMP ON CONDENSER

75 °F

95°F

115°F

125°F

TEMP

PSIG

MBH

KW

MBH

KW

MBH

KW

MBH

KW

H3DA012

35

61.5

13.0

1.31

10.9

1.41

9.0

1.53

8.0

1.59

40

68.5

14.5

1.36

12.3

1.49

10.2

1.62

9.1

1.69

45

76.0

16.1

1.41

13.7

1.54

11.3

1.69

10.1

1.76

50

84.0

17.7

1.44

15.2

1.58

12.4

1.74

11.1

1.82

H3DA018

35

61.5

18.7

1.83

15.6

1.99

12.5

2.09

10.9

2.13

40

68.5

20.8

1.90

17.6

2.07

14.3

2.20

12.6

2.24

45

76.0

22.9

1.97

19.6

2.17

16.2

2.31

14.5

2.37

50

84.0

25.2

2.05

21.8

2.27

18.3

2.43

16.5

2.49

H3DA024

35

61.5

21.9

2.34

18.7

2.54

15.6

2.71

14.0

2.77

40

68.5

24.3

2.41

20.9

2.63

17.6

2.84

15.9

2.91

45

76.0

26.7

2.47

23.2

2.73

19.7

2.97

18.0

3.06

50

84.0

29.3

2.53

25.6

2.82

21.9

3.10

20.0

3.20

H3DA030

35

61.5

27.6

2.64

23.9

2.88

20.2

3.11

18.3

3.20

40

68.5

30.4

2.71

26.5

2.99

22.5

3.24

20.5

3.34

45

76.0

33.3

2.78

29.2

3.08

25.0

3.37

22.8

3.48

50

84.0

36.3

2.85

31.9

3.18

27.5

3.49

25.5

3.62

H3DA036

35

61.5

33.6

3.07

28.8

3.43

24.0

3.82

21.6

4.01

40

68.5

37.3

3.09

32.1

3.48

26.9

3.88

24.3

4.08

45

76.0

40.9

3.23

35.2

3.69

30.2

4.13

27.5

4.36

50

84.0

44.8

3.37

39.1

3.85

33.3

4.35

30.4

4.60

H3DA048

35

61.5

46.7

3.87

39.1

4.82

31.9

57.8

28.3

6.39

40

68.5

51.7

4.07

43.5

5.08

35.7

6.14

31.8

6.83

45

76.0

56.8

4.28

48

5.34

39.6

6.51

35.4

7.28

50

84.0

62

4.49

52.7

5.6

43.7

6.89

39.2

7.73

H3DA060

35

61.5

53.8

5.16

48.7

6.09

43.4

7.25

40.8

7.92

40

68.5

58.9

5.33

53.1

6.25

47.5

7.41

44.7

8.08

45

76.0

64.1

5.51

57.8

6.43

51.8

7.58

48.7

8.25

50

84.0

69.6

5.71

62.5

6.61

56.1

7.76

52.9

8.43

H3DA076

35

61.5

73.9

5.55

66.2

6.60

58.3

7.98

54.4

8.82

40

68.5

80.7

5.69

72.5

6.75

64.3

8.14

60.2

8.98

45

76.0

87.7

5.84

79.1

6.91

70.5

8.30

66.2

9.15

50

84.0

95.1

5.99

86.1

7.07

76.9

8.48

72.4

9.32

SOUND RATINGS

H*DA

MODEL

SOUND RATING

DECIBELS

H3DA012

7.8

H3DA018

7.8

H3DA024

7.8

H3DA030

7.8

H3DA036

7.8

H3DA048

8.0

H3DA060

8.2

H3DA076

8.2

Summary of Contents for STELLAR 2000 H*DA012

Page 1: ...lvanized steel provides a better paint to steel bond which resists corrosion and rust creep Special primer formulas and glossy earth tone finish insure less fading when exposed to sunlight LOWER INSTALLED COST Installation time and costs are reduced by easy power and control wiring connec tions Discharge line heat exchanger knockouts are pro vided if required Both quick connect and sweat connect m...

Page 2: ...9 0 9 1 4 0 8 0 8 0 8 1 0 Locked Rotor 1 4 1 4 3 12 1 8 1 8 2 0 1 8 Fan Diameter Inches 18 18 18 18 18 24 24 Fan Motor Rated HP 1 8 1 8 1 4 1 4 1 4 1 4 1 3 Nominal RPM 1075 1075 1100 1075 1075 850 940 Rated Voltage 230 230 230 460 460 460 415 Coil Face Area Sq Ft 9 4 9 4 11 3 11 3 14 1 20 20 0 Rows Deep 1 1 1 1 1 1 2 Fin Inches 16 16 20 20 16 18 13 Liquid Line OD 3 8 3 8 3 8 3 8 3 8 3 8 1 2 Vapor ...

Page 3: ...1 99 12 5 2 09 10 9 2 13 40 68 5 20 8 1 90 17 6 2 07 14 3 2 20 12 6 2 24 45 76 0 22 9 1 97 19 6 2 17 16 2 2 31 14 5 2 37 50 84 0 25 2 2 05 21 8 2 27 18 3 2 43 16 5 2 49 H3DA024 35 61 5 21 9 2 34 18 7 2 54 15 6 2 71 14 0 2 77 40 68 5 24 3 2 41 20 9 2 63 17 6 2 84 15 9 2 91 45 76 0 26 7 2 47 23 2 2 73 19 7 2 97 18 0 3 06 50 84 0 29 3 2 53 25 6 2 82 21 9 3 10 20 0 3 20 H3DA030 35 61 5 27 6 2 64 23 9 ...

Page 4: ...9 00 H3DA0308S78 N1AHB12 5 7 5 10 15 18 17 G2FD030S17 1025 30 0 21 9 3 32 9 70 17 G2FD036S17 1025 30 2 22 0 3 35 9 70 H3DA036S50 N1AHB12 5 7 5 10 15 18 17 G2FD036S17 1200 34 2 24 9 4 05 9 00 21 G2FD046S17 1200 H3DA048S50 N1AHC16 5 7 5 10 15 20 21 G2FD048S21 1550 46 2 34 7 5 06 9 90 N1AHD20 7 5 10 15 20 25 30 24 G2FD048S24 1550 46 2 34 7 5 06 9 90 N1AHD20 7 5 10 15 20 25 30 24 G2FD060S24 1550 47 8 ...

Page 5: ... G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM THERMOSTAT CONDENSING UNIT TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT POWER WIRING 380 415 3 50 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS...

Page 6: ...l opening s with permagum or equivalent 24 SERVICE ACCESS CLEARANCE 48 OVERHEAD CLEARANCE 12 REAR AND SIDES NOTE All outdoor wiring must be weatherproof AIR HANDLERS FOR NON FURNACE APPLICATIONS N1AH MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F2RP FAN COIL UNITS UPFLOW HORIZONTAL G2FD COIL K EU060 090 LIGHT COMMERCIAL APPLICATIONS G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW ADD ON COILS ...

Page 7: ...036 21105 004 Rev A 0902 Unitary Products Group 7 NOTES ...

Page 8: ...hange without notice Printed in U S A 036 21105 004 Rev A 0902 Copyright by York International Corp 2002 All rights reserved Supersedes 036 21105 003 Rev C 0901 Unitary 5005 Norman Product York OK Group Drive 73069 ...

Reviews: