COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
UNIT MODEL
FURNACE**
COIL
MODEL
COOLING
CFM RANGE
(Min.-max.)
W
RATED
CFM
NET MBH
SEER
1
EER
TOTAL
SENS.
YHJD18S41S1
450 - 750
14,17
FC/MC/PC18
600
17.0
12.6
13.00
11.00
450 - 750
14,17
FC/MC/PC24
600
17.0
12.9
13.50
11.00
450 - 750
14
HC18
600
17.0
12.6
13.00
11.00
450 - 750
14
HC30
600
17.0
12.8
13.00
11.00
450 - 750
14
HD24
600
17.0
13.0
13.50
11.00
YHJD24S41S1
600 - 1000
14
FC/MC/PC32
800
23.0
17.5
13.00
11.00
600 - 1000
17,21
FC/MC/PC35
800
23.0
17.5
13.00
11.00
600 - 1000
14
HC30
800
23.0
17.2
13.00
11.00
600 - 1000
17
HC36
800
23.0
17.5
13.00
11.00
600 - 1000
14,17
HD36
800
23.0
16.4
13.00
11.00
YHJD30S41S1
800 - 1200
14
FC/MC/PC37
1000
29.0
23.4
13.00
11.00
800 - 1200
17,21
FC/MC/PC43
1000
29.0
23.4
13.00
11.00
800 - 1200
21
HC42
1000
29.0
23.4
13.00
11.00
800 - 1200
21,24
HD48
1000
29.0
23.4
13.00
11.00
YHJD36S41S1
1000 - 1400
14
FC/MC/PC37
1200
35.0
26.6
13.00
11.00
1000 - 1400
17,21
FC/MC/PC43
1200
35.0
26.8
13.00
11.00
1000 - 1400
21,24
FC/MC/PC48
1200
35.0
27.0
13.00
11.00
1000 - 1400
21
HC42
1200
35.0
26.8
13.00
11.00
1000 - 1400
21,24
HD48
1200
35.0
26.8
13.00
11.00
YHJD42S41S1
1200 - 1600
21,24
FC/MC/PC48
1400
41.5
31.4
13.00
11.00
1200 - 1600
21,24
FC/MC/PC60
1400
41.0
31.2
13.00
11.00
1200 - 1600
21
HC42
1400
41.0
31.2
13.00
11.00
1200 - 1600
24
HC60
1400
41.0
31.2
13.00
11.00
1200 - 1600
21,24
HD60
1400
41.5
31.4
13.00
11.00
YHJD48S41S1
1400 - 1800
24
HC60
1600
47.0
35.6
13.00
11.00
1400 - 1800
21,24
HD60
1600
47.0
35.4
13.00
11.00
1400 - 1800
21,24
MC62
1600
47.0
35.6
13.00
11.00
YHJD60S41S1
1600 - 2000
21,24
MC62
1800
54.0
42.5
13.00
11.00
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
** Refer to Quick Selection Chart for specific furnace match-up.