![background image](http://html.mh-extra.com/html/york/split-system-yhjd18-thru-60/split-system-yhjd18-thru-60_technical-manual_913496035.webp)
Johnson Controls Unitary Products
35
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
YHJD60S41S1
EVAPORATOR COIL MODEL NO
FC/MC62
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1600
1800
2000
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
65.7 4.7 4.1 66.7 4.6 4.2 67.6 4.6 4.3
70
64.7 5.1 3.7 65.4 5.0 3.8 66.1 4.9 3.9
80
63.8 5.5 3.4 64.1 5.4 3.5 64.5 5.3 3.6
47
60
56.9 4.4 3.8 57.4 4.4 3.9 58.0 4.3 4.0
70
55.8 4.8 3.4 56.3 4.8 3.5 56.8 4.7 3.5
80
54.7 5.2 3.1 55.2 5.2 3.1 55.6 5.1 3.2
40
60
51.9 4.3 3.5 51.7 4.3 3.5 51.4 4.3 3.5
70
50.6 4.8 3.1 51.1 4.7 3.2 51.7 4.7 3.2
80
49.3 5.2 2.8 50.6 5.1 2.9 51.9 5.0 3.0
30
60
44.1 5.0 2.6 43.6 5.0 2.5 43.1 5.0 2.5
70
45.3 4.6 2.9 44.8 4.6 2.9 44.4 4.6 2.8
80
46.5 4.2 3.2 46.1 4.2 3.2 45.6 4.1 3.2
17
60
36.6 5.0 2.2 36.8 4.9 2.2 36.9 4.9 2.2
70
36.0 4.5 2.4 36.5 4.5 2.4 37.1 4.4 2.4
80
35.3 4.0 2.6 36.3 4.0 2.6 37.3 4.0 2.7
10
60
27.3 4.7 1.7 27.7 4.6 1.7 28.1 4.6 1.8
70
30.4 4.4 2.0 31.2 4.3 2.1 32.0 4.3 2.2
80
33.4 4.0 2.4 34.7 4.0 2.5 35.9 4.0 2.7
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
MBH
KW
COP
AHX60
–
1.00
1.02
0.99
F6FP060
–
0.99
1.01
0.98
MA20D MC62D
1.00
1.00
1.00
MV20D MC62D
0.99
0.99
1.00
Furnaces
Coils
MBH
KW
COP
T*(8,L)X*C20
FC/MC62D
0.98
1.02
0.96
T*9X*D20
FC/MC62D
0.98
0.97
1.01
Y*9C*D20
FC/MC/PC60D
0.98 0.97 1.02
Y*(8,L)C*C20
FC/MC62D
0.98 1.01 0.98
Y*9C*C20
FC/MC62D
0.99 0.99 1.01