![background image](http://html1.mh-extra.com/html/york/soh-076/soh-076_technical-information_4170550005.webp)
5
Nom. 230 V
Nom. 400V
Air intake temperature to the outdoor coil DB
Air intake temperature to the indoor coil
Operating cycle
Operating cycle
Voltage limits
Minimum °C
Maximum °C
Minimum °C
Maximum °C
Cool WB
22
Cool
46
Heat
24
Cool
2
Heat
-20
(1)
Heat DB
25
Cool WB
14
Heat DB
10
(2)
Minimum
198
Maximum
254
Minimum
342
Maximum
436
SICH-070B-
076B
SICH-090B-
120B
SICH-150B
SICH-180B
SICH-240C
SIH-300B
Fan
Coil
Weight
Dimensions
with
standard
packing
Indoor units
Limits of use
Notes:
WB = wet bulb. DB = dry bulb.
(1) At below -20°C, only the emergency heater remains operative.
(2) This equipment can operate, for short intervals, at temperatures below 10°C so as to raise the conditioned air temperature to 10°C.
Model
Motor power rating
kW
0.75
1.5
1.5
3
3
5.5
Power supply
V.ph.Hz
400.3.50
Motor rpm
1 400
Number of turbines
1
2
2
2
2
2
Turbine Ø
mm
320
320
320
320
380
380
Turbine width
mm
320
240
320
320
380
380
Amount
1
2
2
2
2
Tubing depth x height
4 x 21
4 x 25
4 x 25
4 x 29
5 x 32
5 x 32
Diameter tubing
3/8"
Surface
m²
0.57
0.84
1.11
1.4
1.76
1.76
Height
mm
760
833
883
935
950
950
Width
mm
1 444
1 825
2 125
2 390
2 800
2 800
Depth
mm
930
930
930
955
1 030
1 030
Nett
kg
120
165
195
240
310
310
Gross
kg
142
195
230
290
350
350