12
Minimum
14
220/240.3.50 14 5,2 4 x 2.5 -
380/415.3.50 7 2 4 x 2.5 -
220/240.3.50 23 5.5 4 x 2.5 -
380/415.3.50 10 3.2 4 x 2.5 -
220/240.3.50 23 5.7 4 x 2.5 -
380/415.3.50 10 3.3 4 x 2.5 -
380/415.3.50 10 3.5 4 x 2.5 -
380/415.3.50 27 7.1 4 x 2.5 15
380/415.3.50 30 6.4 4 x 2.5 15
Power supply V.ph.Hz. Consumption A
Fan
Model Fan
Start Nominal
Power
supply cable
section
SOC-120/SOC-090/120
SOC-090/SIC-090/120
SIC-076
SIC-180
SIC-240
SIC-150
mm
2
A
Automatic
switch
Air intake temperature to
evaporating unit
°
C
Voltage limits
Nom. 220/240 V Nom. 380/415 V Temperature WB Temperature DB
Temperature DB
Minimum
19
Minimum
198
Maximum
46
Maximum
32
Minimum
342
Maximum
436
Maximum
254
Maximum
23
Minimum
19
Air intake temperature to
condensing unit
°
C
Notes: WB -Wet Bulb, DB -Dry Bulb.
Indoor units
Limits of use
Before final approval of the installation
Verify:
- Voltage is always between 198-
254 V., or 342-436 V.
- The section of the power supply ca-
ble is, at least, that recommended in
the corresponding wiring diagrams.
- Condensation drainage is carried out
perfectly and there are no leaks in
the water circuit.
- Operating instructions have been
given to the user.
- The need to clean the air filter peri-
odically has been notified.
- The guarantee card has been filled
out.
- Maintenance instructions have
been given, or a regular servicing
contract has been signed.