background image

10

SOC-076/SIC-076        7.1 1 1/2" (12.7 mm) 104

SOC-090/SIC-090/120 9.4 1 5/8" (15.87 mm) 170

SOC-120/SIC-090/120 11.45 1 5/8" (15.87 mm) 170

SOC-150/SIC-150        7 2 1/2" (12.7 mm) 104

SOC-180/SIC-180        9 2 5/8" (15.87 mm) 170

SOC-240/SIC-240        11.5 2 5/8" (15.87 mm) 170

Model

Nominal

load

R-22 kg

Number

of

circuits

Diameter

liquid

line

Additional

load

grs. (per

meter)

SLOPE
2%

MINIMUM

75 mm

PLUG

Air ducts (indoor unit)

1.- Connect the ducts, isolating from the unit by means of a

flexible hose, preferably of a non-combustible material, so
as to avoid transmitting the vibration of the unit itself. If the
ducts are made of flexible material they do not transmit
vibrations.

2.- It is advisable to place a damper at each discharge duct

derivation so as to be able to carry out a correct balance
of the system.

3.- Make sure there is easy access for cleaning and changing

the air filters.

Drainage connections

Install the drainage tubing of each tray through a siphon.
Leave a minimum height difference of 75 mm. between the
height of the connection to the unit and the line after the
siphon (see figure). This is to avoid that the pressure drop
produced by the fan may not interfere with the emptying of the
tray. There should be an access so that, at the beginning of
each season, the siphon may be filled with water. The
drainage line should have a minimum inclination of 2 cms. per
meter of total length.

Valves and refrigerant load

The SOC-076 unit has only one circuit and is supplied with
two valves. The SOC-150 unit has two circuits and is
supplied with four valves. These valves are supplied closed
and with an entire refrigerant load in the outdoor unit (pump-
down). Before starting the unit, make sure the valves are
completely open. The SOC-090 and SOC-120 units have
only one circuit while the SOC-180 and SOC-240 units
have two circuits. These units are suppied without valves, but
with connections ready for welding. The refrigerant load must
be carried out completely on site. See refrigerant load in the
corresponding section, and follow the recommendations
made in the Refrigerant Interconnections and Refrigerant
Load Process sections.

Emptying and dehydrating

Air does not act as a refrigerant as it cannot be liquified by the
compressor. The air and humidity remaining in the cooling

system should be completely eliminated, as these have
undesirable effects, as indicated in the list below.
- High pressure increase.
- Power consumption increase.
- Equipment performance decrease.
- The water contained in the air may freeze and block the

capillaries.

- The water may corrode certain parts of the circuit and

deteriorate the compressor.

Emptying and dehydration should be carried out by means of

a vacuum pump.

The vacuum needed is 200 microns (0.2 mm. Hg.).
Connection of the vacuum pump to the cooling circuit should

be made at the 1/4" SAE connections furnished for this
purpose, and with the valves closed.

This will allow emptying and dehydrating the units and

interconnecting tubing.

The SOC-076 and SOC-150 units are supplied preloaded

with refrigerant and does not need to be emptied.

Leakage detection

Leakage detection in the circuit that joins the two units will be

carried out by using R-22 refrigerant and the aid of a detector.

Refrigerant load

The nominal refrigerant load is calculated for a tubing length

of 7.5 meters.

Adjusting the refrigerant load

For lengths of tubing of over or under 7.5 m., the nominal

refrigerant load should be increased or decreased by the
grammes indicated above, in accordance to as to whether the
length of the liquid tubing has been increased or decreased.

Refrigerant interconnections

When installing the tubing that interconnect both units, take

special care in keeping the tubing to be used clean and dry
prior to installation. The following recommendations are
advisable:
1- Use only refrigerant quality copper tubing.
2- Do not work outdoors in the rain.
3- The ends of the tubing should remain closed during

installation.

4- Do not leave neither the drying filters nor the compressor

out in the open for more than one or two minutes.

5- For welding use low-solidus point rods with a minimum 5%

silver content.

6- When welding, and while the tubing is still hot, a flow of dry

nitrogen should be maintained so as to avoid the forming
of oxides and scales in the interior which could cause

Summary of Contents for SAC

Page 1: ...SPLIT SYSTEM YORK ...

Page 2: ... the outdoor unit 16 Checking the tension of the belts 16 General dimensions 17 18 Index General description 5 Nomenclature 5 Technical specifications 5 Mechanical specifications of outdoor units AHO F 5 Mechanical specifications of indoor unit CHI 800 5 Table of variations 6 Physical data 7 Rated performance data 8 Testing conditions 8 Correction factors 8 Cooling capacities sensitives 8 10 CHI 8...

Page 3: ...e relevant pressure and leak detection tests Electrical and control wiring system Highly reliable integrated circuits Their compact size permit easy and fast servicing It complies with the European regulations currently in force Mechanical specifications of indoor unit SIC 240 Indoor unit SIC 240 is compatible with either of the cool only outdoor units SOC 240 or heat pump SOH 240 The main feature...

Page 4: ... 380 415 3 50 SIC 150 380 415 3 50 SIC 180 380 415 3 50 SOC 180 380 415 3 50 SOC 150 380 415 3 50 SOC 076 220 240 3 50 380 415 3 50 SIC 240 380 415 3 50 SOC 090 220 240 2 50 380 415 3 50 SOC 240 380 415 3 50 SOC 120 220 240 3 50 380 415 3 50 Table of variations ...

Page 5: ...415 3 50 Power rating W 216 216 216 216 216 216 Number of fans 2 2 3 4 6 6 Power supply V ph Hz 220 240 1 50 Propeller width 510 510 510 510 510 510 Quantity 2 2 2 2 2 2 Rows deep x high 4 x 28 4 x 28 4 x 28 4 x 56 4 x 56 4 x 56 Tube O D 3 8 3 8 3 8 3 8 3 8 3 8 High mm 1 030 1 030 1 030 1 495 1 495 1 495 Wide mm 1 580 1 860 2 230 1 690 1 975 2 150 Deep mm 950 950 950 1 547 1 547 1 547 Kg 250 292 3...

Page 6: ... Comp power input 130 1 046 1 118 1 025 110 1 016 1 038 1 009 100 1 1 1 90 0 980 0 973 0 990 120 1 032 1 075 1 017 80 0 960 0 945 0 980 Flow rate 70 80 90 100 110 120 130 Note SIC units have their own information available Total capacity Model Outdoor air dry temperature C DB Air intake humid temperature C WB Compressor absorbed power Sensitive capacity W h Temperautre air going to indoor unit C D...

Page 7: ...22 33 000 9 917 14 499 21 370 25 951 12 61 19 5 29 700 15 665 20 246 27 118 29 700 13 18 17 27 060 21 459 26 040 27 060 27 060 13 75 22 48 240 14 518 20 628 29 793 35 911 12 14 19 5 43 416 22 164 28 274 37 438 43 416 12 72 17 40 200 30 264 36 374 40 200 40 200 13 29 22 44 622 13 310 19 420 28 584 34 694 13 73 19 5 40 200 20 989 27 099 36 264 40 200 14 45 17 36 984 27 253 33 363 36 984 36 984 15 17...

Page 8: ... 58 718 68 000 23 39 17 62 560 47 088 56 681 62 560 62 560 24 56 22 68 000 20 400 29 992 44 381 53 973 25 73 19 5 61 200 32 441 42 033 56 422 61 200 26 90 17 55 760 44 575 54 168 55 760 55 760 28 07 mm WG Pa m3 h m3 s W 19 9 195 10 000 2 78 1 395 18 176 11 000 3 05 1 550 16 1 158 12 000 3 33 1 565 13 4 131 13 000 3 61 1 905 10 7 105 14 000 3 89 2 050 7 4 73 15 000 4 16 2 240 3 9 38 16 000 4 44 2 4...

Page 9: ...by each one This sign indicates an electrical risk or danger Attention The unit has a remote control system and can start automatically Two minutes prior to having access to the interior the power supply should be dis connected so as to avoid any contact with the fan turbine Attention It is compulsory to read the instructions prior to any handling Attention Fan in operation Attention No to touch h...

Page 10: ... the Refrigerant Interconnections and Refrigerant Load Process sections Emptying and dehydrating Air does not act as a refrigerant as it cannot be liquified by the compressor The air and humidity remaining in the cooling system should be completely eliminated as these have undesirable effects as indicated in the list below High pressure increase Power consumption increase Equipment performance dec...

Page 11: ...ng wide tubing should be isolated from the refrigerant The insulation should have specific characteris tics be easy to install resistant to aging waterproof fireproof and have a thickness of at least 12 mm So as to avoid deterioration due to the sun it is convenient to paint same with water based enamel After having insulated the tubing do not attempt to bend it excessively as it could crack or br...

Page 12: ...erature DB Temperature DB Minimum 19 Minimum 198 Maximum 46 Maximum 32 Minimum 342 Maximum 436 Maximum 254 Maximum 23 Minimum 19 Air intake temperature to condensing unit C Notes WB Wet Bulb DB Dry Bulb Indoor units Limits of use Before final approval of the installation Verify Voltage is always between 198 254 V or 342 436 V The section of the power supply ca ble is at least that recommended in t...

Page 13: ...basic operating modes a For ventilating only Lever A set to CONT Lever B set to OFF Dial at any setting b Summer air conditioning cooling Lever A set to CONT or AUTO Lever B set to REF Dial set to the desired temperature index c Winter air conditioning heating with heating battery optional accessory Lever A set to CONT or AUTO Lever B set to CAL Dial set to the desired temperature index In the OFF...

Page 14: ... a grill The lack of this protection could provoke damage caused by the fan turbine Cleaning the filters Keep the battery filters in good condition checking them at least once a month If the filters are dirty air flow and equipment performance are reduced Cleaning the outdoor unit Dirt should not be allowed to accumulate in the outdoor battery It should be cleaned as frequently as needed with a br...

Page 15: ...PTY SPACE 600 100 572 140 2365 827 985 2323 80 633 473 381 363 473 25 225 404 40 DRAINAGE R 3 4 2038 142 5 142 5 104 37 163 37 40 28 GAS CONNECTION 11 8 LIQUID CONNECTION 5 8 A DETAIL A DETAIL 93 758 EMPTY SPACE 600 945 EMPTY SPACE 600 EMPTY SPACE 1000 70 15 15 890 920 15 950 15 D 13 7 C B A GAS TUBING CONNECTION ACCESS 11 8 LIQUID TUBING CONNECTION ACCESS D DRAINAGE CONNECTION C ...

Page 16: ...odels A B C SOC 150 1 690 1 090 1 2 SOC 180 1 975 1 375 5 8 SOC 240 2 150 1 550 5 8 EMPTY SPACE 600 1495 EMPTY SPACE 600 EMPTY SPACE 1000 D 16 5 175 B 425 20 1507 1481 33 33 A 20 GAS TUBING CONNECTION ACCESS 11 8 LIQUID TUBING CONNECTION ACCESS C DRAINAGE CONNECTION CUTOUT PUSH BUTTONS ...

Page 17: ...cycling depending on the case It is strictly forbidden to dischar ge the r efrigerant into the atmospher e Depending on the case drain the refrigerant oil from each system into an appropriate recipient and eliminate it in accordance with local applicable regulations relative to hydrocarbon waste products 3 As a general rule the solid block units are to be disassembled and removed in a single piece...

Reviews: