 Indoor Unit Fixing

   Thread the indoor unit piping and cable through the hole.

   Hang the top of the unit onto the upper ridge of them in mounting plate.

   Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.

   Press the bottom left and bottom right hand corners of the unit against the mounting plate until the 

 xing prongs 

click into place in the retainers provided to that effect.

Drainage line

Interconnection cable

Note: The condensate evacuation line should be taped to the  

refrigerant lines with vinyl tape.

a)  Access  plate  for  the 

condensate drainage 

pump detection

  (condensate pump is 

available as an 

  accessory).

Condensate

drainage line

Vinyl tape

a

OUTDOOR UNIT

Q

 

Fixing and Piping

  Piping must be performed by quali

 ed personnel ac-

cording to good refrigeration systems practices.

  Piping materials and insulation materials must be of 

refrigerant quality.

  Select the pipe diameters according to the size of unit 

and cut the pipe to design length by using pipe cut-

ter.

  Install the 

 are nuts and 

 are the end of the pipes.

  Check that no foreign bodies are inside the piping.

  Align the central of the connecting pipes and tighten 

the 

 are nut.

  Fix piping with pipe clamps and check that any pipe 

vibrations cannot be transmitted to the building struc-

ture.

  Connect the pipe correctly.

  Do not apply the excessive torque.

  Use an appropriate bending tool to form curves and 

avoid over-tightening the refrigerant tubes.

  To prevent heat loss, the two lines must be insulated 

separately.

Q

 

Maximum Piping Length

The  suction  line  must  have  a  2%  gradient  up  to  the

compressor on horizontal sections.

Where piping lengths are unusually long and include a

large number of oil traps, it may be necessary to adjust

to compressor charge.

Q

 

Refrigerant piping connections

  (FLARE connections)

To avoid alteration of unit capacities, check that piping 

lengths  and  changes  in  elevation  are  kept  to  a  strict 

minimum.
Before  connecting  the  refrigerant  lines,  follow  the

procedures below (if pre-charged connection lines are

not supplied):

  Select copper pipe diameters according to the size of 

unit to be installed.

  Install the refrigeration lines, checking that no foreign 

boodies get inside the piping.

  Install the 

 are connectors and 

 are the ends of the 

pipes.

  Evacuate the piping. This operation, which should last 

at least 15 minutes if there are large piping lengths and

  changes in elevation, should be followed by a leak test.

Refrigerant charge to be added per extra meter 

of piping length when more than 

7.5

 meters.

NOTES

Unit size

MODELS

7

9

12

18

24

28

30

(m) 

10 

1

5

 

1

8

 

20

 

20

 

20 

20

Unit size

MODELS

7

9

12

18

24

28

30

g/m

30

30

30

30

65

65

65

J277-EN.indd   10

26.12.2005   15:15:23 Uhr

Summary of Contents for RLCA-RLHA

Page 1: ...Installation Owner s Manual MODELS RLCA RLHA 07 30 MINISPLIT HIGH WALL AIR CONDITIONER EN 035M80147 000 The units comply with one or more of the following marks see unit for details ...

Page 2: ...lation manual carefully before starting the installation It will tell you necessary information Quality POLICY We will continuously strive to satisfy our customers with consistent reli ability in product service and support through superior quality service culture and distinctive technology 2 2 R 50Hz 60Hz Set RLCAxxFSAAAR RLCAxxFSAADR RLHAxxFSAAAR RLHAxxFSAADR Outdoor RLDAxxFS AAR RLDAxxFS ADR RL...

Page 3: ... electrical connection which may be dangerous and can cause injury Installation and maintenance of this air conditioning system should only be carried out by trained and quali ed personnel After unpacking please check the unit carefully for possible damage Before undertaking any work on the unit make sure that the power supply has been disconnected WARNING CAUTIONS Do not store or unpack the unit ...

Page 4: ...ure is activated in heating operation 3 TEMPERATURE indicator Displays the temperature settings when the air conditioner is operational 4 OPERATION indicator This indicator ashes after power is on and illuminates when the unit is in operation 5 TIMER indicator This indicator illuminates when TIMER is set ON OFF NOTE All the pictures in this manual are for explanation purpose only They may be sligh...

Page 5: ...type without or AUTO operation the air conditioner will automatically increase cooling or decrease heating 1 C per hour The set temperature will be steady 2 hours later The fan speed will be automatically controlled Q DRYING OPERATION The dry mode will automatically select the drying operation based on the difference between the set temperature and the actual room temperature Thetemperatureisregul...

Page 6: ...work check the interior power supply cord and the main breaker capacity are suf cient and the installation area is suf cient and complies with the requirements Check that the power supply available agrees with name plate voltage Electrical work wiring and cables must be in compliance with national and local wiring codes and standard Do not use the extension cables In the case extended cables are n...

Page 7: ...TURES 540 525 225 75 404 88 700 458 5 35 250 88 33 60 261 60 82 80 540 527 245 5 Ø420 128 780 48 10 45 5 1 1 8 4 5 90 266 272 298 RLDA RLJA 07 09 RLDA RLJA 12 18 RLDA RLJA 24 30 560 1 141 5 135 351 2 694 5 301 5 843 313 335 125 235 ...

Page 8: ...lled on the wall at a height of 2 3 metres or more from the oor A B and C directions should be free from obstructions NOTES This illustration is for explanation purposes only Copper lines must be insulated independently C B A 1 2 3 5 4 7 6 Self tapping screw B ST3 9X10 Loop the connective cable Remote Controller Air Filter Remote Controller holer 30cm minimum 200cm minimum 60cm minimum 30cm minimu...

Page 9: ...he indoor unit may be unstable on the wall Carefully arrange pipes so that pipes do not stick out of the rear plate of the indoor unit A B C D E F MODEL 24 30 Right Right Right Right Left Rear Bottom Q Drain hose Drain hose is exible and can be routed to suit vari ous piping arrangements The drain line must include elbow trap U bend Connect a plastic condensate pipe with an internal diameter of 12...

Page 10: ...that any pipe vibrations cannot be transmitted to the building struc ture Connect the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tubes To prevent heat loss the two lines must be insulated separately Q Maximum Piping Length The suction line must have a 2 gradient up to the compressor on horizontal section...

Page 11: ...n interconnecting piping length of 5 meters Liquid Cooling GAS Cooling suction Low pressure High pressure Manifold Gas valve Liquid valve Pressure tap Outdoor unit Indoor unit Gas line Liquid line R22 R407C R410A Outdoor heat pump unit install the unit at least 10 cm above ground level to facilitate drainage of defrost water and prevent accumulation of ice In effect defrost water can cause accumul...

Page 12: ...roprene sheeted cord 245 IEC 57 or H05RN F Disconnecting device must have a contact separation of at least 3 mm Models 07 18 Cooling only Power supply Indoor L N 1 2 N 1 2 N Outdoor CAUTIONS Models 07 18 Cooling and Heating L N 1 2 N 3 4 1 2 N 3 4 Outdoor Indoor Models 24 30 Cooling only Cooling and Heating Outdoor Indoor For correct installation a proper ground connection must be made for unit Po...

Page 13: ... 1 2 N 3 4 Ter S 1 2 N Cord clamp 1 2 Term 1 2 N S L N Terminal block of indoor unit Cooling only type cooling heating type Terminal block of indoor unit Cord clamp To outdoor unit To outdoor unit Terminal block of outdoor unit Wire holding board Terminal block of outdoor unit Cooling only type cooling heating type Cooling only type Cooling heating type ...

Page 14: ...30000 Btu h 220 240V 50Hz 32A 220 230V 60Hz NOTE b Unit has been running at high temperature protection mode for 90 minute High temperature protection mode when coil temperature of indoor unit reaches 55 C outdoor unit will turn off external unit fan but still keep compressor running 2 Condition to stop defrosting Units will switch back to heating mode when either of the following conditions is me...

Page 15: ...about half a day to dry the inside of the unit 2 Stop the air conditioner and disconnect power Remove the batteries from the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not attempt to do this yourself Contact your dealer or servicer Q Checks before operation Check that the wiring is not broken off or disconnected Check that the air lter is installed Check if ...

Page 16: ...ut from the indoor unit This is a normal condition when the air conditioner has not been used for a long time or during rst use of the unit 5 A peculiar smell comes out from the indoor unit This is caused by the indoor unit giving off smells permeated from building material from furniture or smoke 6 The air conditioner turns to FAN only mode from COOL or HEAT for cooling and heating models only mo...

Page 17: ...ly very hot cool when you started the sys tem 1 Remove charge repair evacuate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room D The compressor runs con tinuously 1 Thermostat adjustment too low in heating mode or too high in cool ing mode 2 Faulty fan 3 Refrigerant charge too low leak 4 Air or incondensables in refrigerant circuit 1 Check thermostat setti...

Page 18: ...55 55 57 57 Indoor Unit Power Supply V Ph Hz 220 240 1 50 Ph 1 1 1 1 1 1 Fan Air ow m3 h 400 400 450 450 580 580 800 800 1080 1080 1150 1150 Input Power W 39 5 39 5 39 5 39 5 38 5 38 5 53 53 65 65 70 70 Running Current A 0 17 0 17 0 17 0 17 0 17 0 17 0 24 0 24 0 29 0 29 0 32 0 32 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 ...

Page 19: ...50 150 75 75 Running Current A 0 14 0 14 0 14 0 14 0 14 0 14 0 24 0 24 0 68 0 68 0 34 0 34 Dimension Height mm 250 250 250 250 265 265 292 292 330 330 330 330 Width mm 710 710 710 710 790 790 920 920 1080 1080 1080 1080 Depth mm 190 190 190 190 195 195 225 225 225 225 225 225 Weight kg 8 5 8 5 8 5 8 5 9 0 9 0 13 13 17 17 17 17 System Operation Control Wireless Control with LCD Display Outdoor Unit...

Page 20: ...ufacturer for disposal Under No circumstances should refrigerant be vented to atmosphere Where appropriate drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal of oily wastes 3 Packaged unit can generally be removed in one piece after disconnection as above Any xing down bolts should be removed and then unit ...

Reviews: