333495-YTG-C-0908
Johnson Controls Unitary Products
21
115°F
125°F
1500
77
52.2
6.2
27.9
20.8
13.7
-
-
-
46.7
6.6
26.3
19.2
12.1
-
-
-
72
47.9
6.1
36.8
29.7
22.6
15.5
-
-
42.0
6.5
33.6
26.5
19.4
12.2
-
-
67
43.5
5.9
43.5
38.6
31.5
24.3
17.2
-
37.2
6.4
37.2
33.8
26.7
19.5
12.4
-
62
40.2
5.8
40.2
40.2
39.4
32.3
25.1
18.0
34.7
6.2
34.7
34.7
34.7
28.1
20.9
13.8
57
42.0
5.8
42.0
42.0
36.6
29.4
22.3
15.2
37.6
6.2
37.6
37.6
31.0
23.9
16.8
9.7
1750
77
52.9
6.4
36.9
23.6
14.7
-
-
-
47.8
6.8
36.9
22.6
13.4
-
-
-
72
48.5
6.2
41.1
32.6
24.2
15.8
-
-
43.0
6.7
38.4
30.0
21.6
13.2
-
-
67
44.1
6.1
44.1
41.6
33.7
25.3
16.9
-
38.1
6.6
38.1
37.4
29.7
21.3
12.9
-
62
40.7
5.9
40.7
40.7
42.2
33.8
25.4
17.0
35.5
6.4
35.5
35.5
35.5
30.7
22.2
13.8
57
42.6
5.9
42.6
42.6
39.2
30.8
22.3
13.9
38.5
6.4
38.5
38.5
34.6
26.2
17.8
9.4
2000
77
53.6
6.5
45.9
26.4
15.7
-
-
-
48.9
7.0
47.5
26.1
14.8
-
-
-
72
49.2
6.4
45.3
35.6
25.8
16.1
-
-
43.9
6.9
43.3
33.5
23.8
14.1
-
-
67
44.7
6.2
44.7
44.7
36.0
26.3
16.6
-
39.0
6.8
39.0
39.0
32.8
23.1
13.4
-
62
41.3
6.1
41.3
41.3
45.1
35.4
25.6
15.9
36.3
6.6
36.3
36.3
36.3
33.3
23.5
13.8
57
43.2
6.1
43.2
43.2
41.8
32.1
22.4
12.7
39.4
6.6
39.4
39.4
38.2
28.5
18.8
9.1
2250
72
50.7
6.5
48.8
38.3
27.2
16.2
-
-
45.8
7.0
45.8
36.0
25.0
13.9
-
-
67
46.1
6.3
46.1
46.1
37.9
26.9
15.8
-
40.7
6.9
40.7
40.7
34.4
23.3
12.3
-
62
42.6
6.2
42.6
42.6
44.5
33.4
22.3
11.3
37.9
6.7
37.9
37.9
37.9
30.1
19.1
8.0
57
44.6
6.2
44.6
44.6
43.9
32.8
21.7
10.7
41.0
6.7
41.0
41.0
40.4
29.4
18.3
7.2
2500
72
52.3
6.6
52.3
41.0
28.6
16.2
-
-
47.7
7.0
47.7
38.5
26.1
13.7
-
-
67
47.5
6.4
47.5
47.5
39.9
27.5
15.1
-
42.4
6.9
42.4
42.4
36.0
23.6
11.1
-
62
43.9
6.3
43.9
43.9
43.9
31.5
19.0
6.6
39.4
6.7
39.4
39.4
39.4
27.0
14.6
2.2
57
45.9
6.3
45.9
45.9
45.9
33.5
21.1
8.7
42.7
6.7
42.7
42.7
42.7
30.2
17.8
5.4
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
BHZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65