background image

JOHNSON CONTROLS

11

TROUBLESHOOTING CHECKLIST

Symptom

Possible Cause(s)

Corrective Action

Capacity or 

Pressure 

Below Rating

1. 

Total resistance of system higher than anticipated. 

2. 

Speed too low.

3. 

Dampers or variable inlet varies improperly adjusted.

4. 

Poor fan inlet or outlet conditions.

5. 

Air leaks in system.

6. 

Damaged impeller or incorrect direction of rotation. 

1. 

System problems.

2. 

Adjust drive.

3. 

Adjust.

4. 

Elbows at or too close to fan.

5. 

Seal joints / correct damper settings.

6. 

Correct.

Vibration 

and Noise

1. 

Misalignment of impeller, bearings, couplings.

2. 

Unstable foundation.

3. 

Foreign material in fan causing unbalance.

4. 

Worn bearings.

5. 

Damaged impeller or motor.

6. 

Broken or loose bolts or set screws, bent shaft, or worn 

coupling.

7. 

Impeller or driver unbalanced.

8. 

60/120 Hz cycle magnetic hum due to electrical input.

9. 

Fan delivering more than rated capacity.

10. 

Loose dampers or VIVS.

11. 

Speed too high or fan rotating in wrong direction.

12. 

Vibration transmitted to fan from some other source.

1. 

Loosen, align, tighten.

2. 

Inferior design, start over.

3. 

Remove.

4. 

Replace bearings and shaft.

5. 

Check and repair.

6. 

Replace.

7. 

Balance.

8. 

Check for high or unbalanced voltage.

9. 

Reduce speed.

10. 

Adjust and tighten.

11. 

Correct.

12. 

Isolate.

Overheated 

Bearings

1. 

Too much grease in ball bearings.

2. 

Poor alignment.

3. 

Damaged impeller or drive. 

4. 

Bent shaft. 

5. 

Abnormal end thrust.

6. 

Dirt in bearings.

7. 

Excessive belt tension. 

1. 

Allow run time to purge (24 hours)

2. 

Correct.

3. 

Inspect, correct, or replace. 

4. 

Replace. 

5. 

Loosen set screws and adjust.

6. 

Replace bearing; use filtered grease.

7. 

Adjust.

Overloaded 

Motor (Pulls Too 

Many Amps)

1. 

Speed too high.

2. 

Discharge over capacity due to existing system resistance 

being lower than original  rating. 

3. 

Specific gravity or density of gas above design value.

4. 

Wrong direction of rotation or poor alignment.

5. 

Impeller wedging or binding on inlet ball.

6. 

Bearings improperly lubricated.

7. 

Motor improperly wired. 

1. 

Reduce speed or change HP.

2. 

Adjust system resistance.

3. 

Recalculate and correct.

4. 

Correct.

5. 

Loosen and adjust.

6. 

See page 

7. 

Verify and correct.

Motor

Problems 

1. 

Check for low or high voltage from power source.

2. 

High temperature; drawing too much current or dirt in 

windings. 

3. 

Vibration and noise.

4. 

Armature rubs against stator. 

5. 

Too much or not enough lubrication in bearings.

6. 

Commutator brushes on d-c motor worn or not seated 

under proper tension. 

7. 

Vibration and noise; loose hold down bolts. 

8. 

Low insulation resistance due to moisture. 

1. 

Correct voltage. 

2. 

Repair motor.

3. 

Correct armature imbalance. 

4. 

Replace worn bearings. 

5. 

Correct lubrication.

6. 

Repair motor. 

7. 

Tighten hold down bolts. 

8. 

Check resistance with a megohm meter (“Meggar”) 

or similar instrument employing a 500 vold d-c 

potential. Resistance should read at least 1 megohm. 

Note: Care should be taken to follow all local electrical, safety and building codes. Provisions of the National Electric Code (NEC), as wells as the Occupational Safety and 

Health Act (OSHA) should be followed. See additional notes on next page.

Summary of Contents for PW Series

Page 1: ...eeding it is recommended that you check for a more current version of this Installation Operation Manual IOM on our website at www johnsoncontrols com Read carefully before attempting to assemble inst...

Page 2: ...Block impeller to prevent natural rotation Do not allow material of any kind to be piled on top or inside of fan LONG TERM STORAGE OVER 1 MONTH Long term storage is de ned as storage for period excee...

Page 3: ...t is sometimes dif cult to tell whether or not it is running be sure it is not running and cannot be operated before doing any inspection or maintenance 3 DO NOT operate fan with guards removed 4 DO N...

Page 4: ...he stator pole Split Phase Interchange connections to supply of either main or auxillary winding Capacitor All types of capacitor motors are reversed in rotation by interchanging connections to supply...

Page 5: ...ts impeller hub set screws and bearing set screws be checked for tightness before start up Access Doors They should be tight and sealed NOTE The maximum torque values for weld studs are shown in the b...

Page 6: ...impeller may have to be cleaned A wash down with steam or water jet is usually suf cient covering bearings so water will not enter the pillow blocks Impellers having worn blades should be replaced Imp...

Page 7: ...ay not be lubricated before shipment When there is the slightest doubt the safe practice is to assume that the bearing has not been lubricated Always turn fan off before lubricating For grease lubrica...

Page 8: ...aight edge or taut cord placed across the faces of the sheaves will aid in alignment with single groove sheaves If multiple groove sheaves are installed use the center line of the drive as your alignm...

Page 9: ...ne if a crown exists Shim each bearing accordingly Wheel clearances and split housed bearing assembly tolerances must be adhered to YORK by Johnson Controls requires that for any rotating assembly rep...

Page 10: ...Monitor equipment for deterioration Rough Requires service Dangerous operating conditions for fan equipment Shut equipment down Shut Down Do not operate fan equipment Potential for catastrophic failur...

Page 11: ...nsion 1 Allow run time to purge 24 hours 2 Correct 3 Inspect correct or replace 4 Replace 5 Loosen set screws and adjust 6 Replace bearing use filtered grease 7 Adjust Overloaded Motor Pulls Too Many...

Page 12: ...r defects should develop prompt service can be obtained from the nearest authorized service station of the motor manufacturer while under warranty Exchange repair or replacement will be provided on a...

Reviews: