FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown below.

NOTE: The filter pressure drop values in the “Filter Perfor-
mance” table shown below are typical values for the type of 
filter listed and should only be used as a guideline. Actual 
pressure drop ratings for each filter type vary between filter 
manufacturer.

APPLYING FILTER PRESSURE DROP TO 
DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.

Select the filter type.

2.

Select the number of return air openings or calculate the 
return opening size in square inches to determine the 
proper filter pressure drop.

3.

Determine the External System Static Pressure (ESP) 
without the filter.

4.

Select a filter pressure drop from the table based upon 
the number of return air openings or return air opening 
size and add to the ESP from Step 3 to determine the 
total system static.

5.

If total system static matches a ESP value in the airflow 
table (i.e. 0.20, 0.60, etc,) the system airflow corre-
sponds to the intersection of the ESP column and Model/
Blower Speed row.

FILTER SIZES

Input / Output

BTU/H

CFM

Cabinet 

Size

Side Return 

Filter in.

Bottom Return 

Filter in.

40/38

1200 

A

16 x 25 

14 x 25 

60/56

1200 

B

16 x 25 

16 x 25 

80/75

1200

B

16 x 25 

16 x 25 

80/75

1600 

C

16 x 25

20 x 25 

100/93

2000 

C

16 x 25

20 x 25 

120/112 

2000 

D

(2) 16 x 25

22 x 25 

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)

Airflow Range

Minimum Opening Size

Filter Type

Disposable

Washable Fiber

Pleated

1 Opening

2 Openings

1 Opening

2 Opening

1 Opening

2 Opening

1 Opening

2 Opening

Sq. in.   

Sq. in.

In w.c.

In w.c.

In w.c.

In w.c.

In w.c.

In w.c.

0 - 750

230

0.01

0.01

0.15

751 - 1000

330

0.04

0.03

0.20

1001 - 1250

330

0.08

0.07

0.20

1251 - 1500

330

0.08

0.07

0.25

1501 - 1750

380

658

0.14

0.08

0.13

0.06

0.30

0.17

1751 - 2000

380

658

0.17

0.09

0.15

0.07

0.30

0.17

2001 & Above

463

658

0.17

0.09

0.15

0.07

0.30

0.17

UNIT CLEARANCES TO COMBUSTIBLES

Application

Top

Front

Rear

Left Side

Right Side

Flue

Floor/ 

Bottom

Closet

Alcove

Attic

In.

In.

In.

In.

In.

In.

Upflow

1

3

0

0

0

0

Combustible

Yes

Yes

Summary of Contents for PV9A12N040UP11

Page 1: ...gas valve Two stage inducer operation Variable speed ECM blower operation Provides increased comfort level very quiet unit opera tion Adjustable delay timer allows two stage operation with single stage thermostat Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code dis...

Page 2: ...TTOM IMAGE RETURN END TOP IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O CABINET AND DUCT DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in PV9A12N040UP11 1200 A 14 1 2 13 1 2 12 1 8 6 1 4 PV9B12N060UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PV9B12N080UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PV9C16N080UP11 1600 C ...

Page 3: ...om two sides or one side plus bottom ELECTRICAL AND PERFORMANCE DATA Models Input High Low Output High Low Nominal Airflow Cabinet Width Total Unit AFUE Air Temp Rise MBH MBH CFM In Amps F PV9A12N040UP11 40 26 38 24 1200 14 1 2 9 94 0 35 65 PV9B12N060UP11 60 39 56 36 1200 17 1 2 9 93 2 40 70 PV9B12N080UP11 80 52 75 49 1200 17 1 2 9 92 5 45 75 PV9C16N080UP11 80 52 75 49 1600 21 12 92 8 45 75 PV9C20...

Page 4: ... 1490 920 C A 1250 790 1290 790 D A 1310 810 1360 840 C C 1090 690 1140 690 D C HIGH LOW HEAT CFM 40 000 INPUT 3 Ton 60 000 INPUT 3 Ton JUMPER SETTINGS CFM CFM High Low High Low HEAT Tap ADJ Tap 1045 740 1110 710 A Any 905 645 960 640 B Any 825 595 870 600 C Any 765 590 830 570 D Any 80 000 INPUT 3 Ton 80 000 INPUT 4 Ton JUMPER SETTINGS CFM CFM High Low High Low HEAT Tap ADJ Tap 1330 880 1490 990 ...

Page 5: ...d upon the number of return air openings or return air opening size and add to the ESP from Step 3 to determine the total system static 5 If total system static matches a ESP value in the airflow table i e 0 20 0 60 etc the system airflow corre sponds to the intersection of the ESP column and Model Blower Speed row FILTER SIZES Input Output BTU H CFM Cabinet Size Side Return Filter in Bottom Retur...

Page 6: ...ight O Reversing Valve Energized in Cool TWO STAGE AIR CONDITIONING Comfort Alert Interface HUM Dehumidification Open on Humidity Rise C 24 Volt Common C 24 Volt Common R 24 Volt Hot W2 Second Stage Heat G Fan Y2 Second Stage Cool E W1 First Stage Heat RC 24 Volt Hot Cool XFMR Y1 First Stage Cool R 24 Volt Hot Y Y2 Single Second Stage Cool Y2 Second Stage Cool Y First Stage Cool Y2 Second Stage Co...

Page 7: ...2 Delay on furnace to OFF HM Humidistat BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y2 Second Stage Heat Cool DHM Dehumidistat HUM Dehumidification Open on Humidity Rise Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y2 Second Stage Heat Cool Y 2 O Reversing Valve Energized in Coo...

Page 8: ...SIDE RETURN FILTER RACK 1SF0101 Fits all cabinet sizes Attaches to side of furnace cabinet in side return applications Holds any 16x25x1 permanent or disposable filter SIDE RETURN FILTER 1SR0302 All Models 1SR0200 All Models BOTTOM RETURN FILTER 1BR0114 or 1BR0214 For 14 1 2 cabinets 1BR0117 or 1BR0217 For 17 1 2 cabinets 1BR0121 or 1BR0221 For 21 cabinets 1BR0124 or 1BR0224 For 24 1 2 cabinets IN...

Reviews: