York PS9 DH Series Installation Manual Download Page 19

269441-UIM-A-0407

Unitary Products Group

19

VERTICAL VENT APPLICATIONS AND 

TERMINATION

Roof mounted vertical terminals may be field fabricated. Standard PVC/
SRD fittings may be used. If installing a vertical venting system through
any unconditioned space such as an attic or crawl space it must be
insulated.

1.

Observe all clearances listed in vent clearances in these instruc-
tions.

2.

Termination should be positioned where vent vapors are not objec-
tionable.

3.

Termination should be located where it will not be affected by wind
gusts, light snow, or allow recirculation of flue gases.

4.

Termination should be located where it cannot be damaged,
plugged or restricted by tree limbs, leaves and branches.

5.

Horizontal portions of the vent system must slope upwards and be
supported to prevent sagging. The vent system may be supported
by the use of clamps or hangers secured to a permanent part of
the structure every 4 ft. (1.22 m).

VENTING MULTIPLE UNITS

Only the sealed combustion system can be used for installations requir-
ing more than one furnace in a structure. A separate sealed combustion
air pipe and a separate vent pipe must be installed for each furnace. Do
not connect more than one furnace to a combustion air pipe or a vent
pipe. The combustion air and vent termination must be located as
shown in Figures 23 or 24.

 

COMBUSTION AIR SUPPLY

All installations must comply with Section 5.3, Air for Combustion and
Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections
7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2 Installation Code - latest edi-
tions.

This furnace is certified to be installed with one of three possible com-
bustion air intake configurations.

1.

OUTDOOR COMBUSTION AIR:

 This is a sealed combustion air

configuration where the combustion air is supplied through a PVC
or ABS pipe that is connected to the PVC coupling attached to the
burner box and is terminated in the same atmospheric zone as the
vent. This type of installation is approved on all models. Refer to
Figures 25 & 27.

2.

AMBIENT COMBUSTION AIR:

 Combustion air is supplied from

the area surrounding the furnace through the combustion air pipe
in the furnace casing. The combustion air and the vent pipes are
not terminated in the same atmospheric zone. Refer to Figures 19
& 26 for vent terminations. Refer to “AMBIENT COMBUSTION
AIR SUPPLY” and “VENT AND SUPPLY OUTSIDE AIR SAFETY
CHECK PROCEDURE” for proper installation.

3.

VENTILATED COMBUSTION AIR:

 Combustion air is supplied

through a PVC or ABS pipe that is connected to the PVC coupling
attached to the burner box and is terminated in a ventilated attic or
crawl space. The combustion air and the vent pipes are not termi-
nated in the same atmospheric zone. Refer to Figure 28 for crawl
space and attic termination. Only the combustion air intake may
terminate in the attic. The vent must terminate outside.

Outdoor Combustion Air

Combustion Air Intake/Vent Connections

This installation requires combustion air to be brought in from outdoors.
This requires a properly sized pipe (shown in Figures 31, 33, or 35) that
will bring air in from the outdoors to the furnace combustion air intake
collar on the burner box. The second pipe (shown in Figures 31, 33 or
35) is the furnace vent pipe.

 FIGURE 22:  

Crawl Space Termination Configuration - 2Pipe

 FIGURE 23:  

Double Horizontal Sealed Combustion Air and Vent 

Termination

 

12” MINIMUM
BELOW
OVERHANG

12”
SEPARATION
BETWEEN BOTTOM
OF COMBUSTION
AIR PIPE AND
BOTTOM OF VENT

MINIMUM

MAINTAIN 12”
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
HIGHER

VENT DRAIN

VENT

2”
MIN.

COMBUSTION AIR

 FIGURE 24:  

Double Vertical Sealed Combustion Air and Vent 

Termination

 FIGURE 25:  

Sealed Combustion Air Intake Connection and Vent 

Connection

MIN.
6”

2” (5.08 cm)
VENT
CONNECTION

AIR INTAKE

Summary of Contents for PS9 DH Series

Page 1: ...Gas Valve 9 Downflow Gas Piping 9 Horizontal Gas Piping 9 Electrical Wiring 11 Thermostat Chart 12 Accessory Connections 13 Typical Twinned Furnace Application 13 Single Stage Twinning Wiring Diagram...

Page 2: ...ible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models ARE NOT CSA l...

Page 3: ...other storage purposes as a fire hazard may be created Never store items such as the following on near or in contact with the fur nace 1 Spray or aerosol cans rags brooms dust mops vacuum cleaners or...

Page 4: ...the cabinet to the duct connec tor Refer to the installation instructions for additional information When replacing an existing furnace if the existing plenum is not the same size as the new furnace...

Page 5: ...nges or tabs that are securely attach and sealed to the supply air duct and to the base of the furnace The transi tion duct must have insulation between the transition duct and any com bustible materi...

Page 6: ...et specifically intended for horizontal applications If a matching cooling coil is used it may be placed directly on the supply air side of the furnace and sealed to prevent leakage A warm air duct pl...

Page 7: ...e of a filter Replacement filter size is shown in Table 5 NOTES 1 Air velocity through throwaway type filters may not exceed 300 feet per minute All velocities over this require the use of high veloci...

Page 8: ...ce plenum Any branch duct rectan gular or round duct attached to the plenum must attach to the vertical plenum above the filter height The use of straps and or supports is required to support the weig...

Page 9: ...at the factory for natural gas fired operation at 0 8 000 feet 0 m 2 438 m above sea level The manifold pressure must be changed in order to manitain proper and safe operation when the furnace is ins...

Page 10: ...extremely dangerous condition resulting in premature heat exchanger failure excessive sooting high levels of carbon monoxide personal injury property damage a fire hazard and or death High altitude a...

Page 11: ...versed the control board will flash 9 times The furnace will not operate until the polarity is corrected Refer to Furnace Diag nostics section of the User s Information Maintenance Ser vice Manual pro...

Page 12: ...w Batteries BN11C01124 DP11C40124 PSC 2 STAGE COOLING READY FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C00124 BP11C50124 PP11C70224 THERMOSTAT THERMOSTAT THERMOSTAT HP2 Single Stage H P E RD E...

Page 13: ...furnace operates on W2 then the use of an air mixing device in the plenum to mix the air from both fur naces is strongly recommended The mixing device must be installed before any ducts that supply a...

Page 14: ...as shown in the Figure 15 1 Connect the low voltage wiring from the wall thermostat to the ter minal strip on the control board of Furnace 1 For staging applica tions the wire from thermostat W1 is co...

Page 15: ...for Type BH Gas Venting Systems IPEX System 636 PVC is certified to this standard 8 In Canada the first three feet 900 mm of the vent must be readily accessible for inspection Example An 80 000 BTUH f...

Page 16: ...proper fit support and slope on the following systems A Sealed combustion air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or...

Page 17: ...ons 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Page 18: ...VC street elbow as shown in Figure 18 3 Locate the rubber condensate hose in front of the blower access panel 4 Slide the hose through the hole in the top cover and insert the hose on to the barbed fi...

Page 19: ...gh a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in the same atmospheric zone as the vent This type of installation is approved on all models Ref...

Page 20: ...uvers and grilles varies widely the installer should follow lou ver or grilles manufacturer s instructions Dampers Louvers and Grilles Canada Only 1 The free area of a supply air opening shall be calc...

Page 21: ...bow usage Follow all notes procedures and required materials in the SEALED COMBUSTION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a venti la...

Page 22: ...of heat tape Wrap the drain trap and the drain line with the heat tape and secure with ties Follow the heat tape manufacturer s recommendations CONDENSATE DRAIN HOSE PART NUMBERS DOWNFLOW HORIZONTAL C...

Page 23: ...e pan close to the inducer 8 Install hose 9 between the external drain on the Wye and the condensate trap with the dogleg end installed on the protruded stub drain of the condensate trap The length of...

Page 24: ...IS TUBE FOR THE BLOCKED CONDENSATE SWITCH MUST BE RELOCATED FROM ITS ORIGINAL FACTORY INSTALLED LOCATION BEHIND THE COMBUSTION AIR PIPE TO THE TAP BEHIND THE DRAFT INDUCER A SMALL HOSE IS INSTALLED ON...

Page 25: ...BARBED TEE 3 8 BARBED NIPPLES 1 1 2 PIECE OF 3 8 HOSE HOSE 10 3 4 2 1 2 HOSE 4 SPRING CLAMP 1 SPRING CLAMP 1 2 3 4 22 1 8 HOSE 8 DOG LEG USED AFTER CONDENSATE TRAP HOSE 9 3 4 33 3 4 1 5 8 HOSE 6 1 5...

Page 26: ...kout opening in this configuration using the provided condensate trap bracket Some modifications may however have to be made to the condensate hoses Installation with condensate trap bracket Back of c...

Page 27: ...ts Group 27 FIGURE 33 Horizontal Right Condensate Drain Hose Configuration Option 1 Front of Casing HOSE 2 HOSE 7 THIS TUBE FOR THE BLOCKED CONDENSATE SWITCH HAS BEEN FACTORY INSTALLED FOR THIS POSITI...

Page 28: ...SE 4 SPRING CLAMP 3 4 3 4 HOSE 7 21 SPRING CLAMP 3 4 17 1 2 3 8 HOSE 2 DOG LEG 1 SPRING CLAMP 1 2 3 4 22 1 8 HOSE 8 DOG LEG USED AFTER CONDENSATE TRAP 1 2 3 4 8 1 8 HOSE 1 DOGLEG SPRING CLAMP CUT 4 1...

Page 29: ...Condensate Drain Hose Configuration Option 2 Back of Casing HOSE 2 CUT FROM HOSE 1 2 1 2 long HOSE 7 THIS TUBE FOR THE BLOCKED CONDENSATE SWITCH HAS BEEN FACTORY INSTALLED FOR THIS POSITION HOSE 9 HO...

Page 30: ...SE 4 SPRING CLAMP 3 4 3 4 HOSE 7 21 SPRING CLAMP 3 4 17 1 2 3 8 HOSE 2 DOG LEG 1 SPRING CLAMP 1 2 3 4 22 1 8 HOSE 8 DOG LEG USED AFTER CONDENSATE TRAP 1 2 3 4 8 1 8 HOSE 1 DOGLEG SPRING CLAMP CUT 4 1...

Page 31: ...nt piping or terminal 3 Failure of combustion air blower motor 4 Blockage of condensate drain piping LIMIT CONTROLS There is high temperature limit control located on the furnace vestibule panel near...

Page 32: ...ing out With furnace in operation check all of the pipe joints gas valve connec tions and manual valve connections for leakage using an approved gas detector a non corrosive leak detection fluid or ot...

Page 33: ...at the gas meter times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas mul...

Page 34: ...erence atmo spheric pressure Refer to Figure 39 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tighten...

Page 35: ...ser selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins The blower speed connections shown in Figure 40 are typical How eve...

Page 36: ...out Low gas pressure faulty gas valve faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the...

Page 37: ...26 25 24 22 21 19 Low 775 777 757 733 698 663 627 584 549 490 22 22 21 21 20 19 18 17 16 14 80 1600 C High 2071 2026 1981 1935 1864 1796 1713 1625 1532 1401 59 57 56 55 53 51 48 46 43 40 Med High 1583...

Page 38: ...50 from the airflow 0 60 to obtain air flow difference 2042 2152 110 CFM 3 Subtract the total system static from 0 50 and divide this differ ence by the difference in ESP values in the table 0 60 0 5...

Page 39: ...269441 UIM A 0407 Unitary Products Group 39 SECTION XI WIRING DIAGRAM FIGURE 41 Wiring Diagram...

Page 40: ...o change without notice Printed in U S A 269441 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167569 UIM A 1205 Unitary 5005 Norman Product York OK Group Drive 73...

Reviews: