5167540-YIM-H-0518
64
Johnson Controls Ducted Systems
Table 34: ZR061 Charging Table
Air Flow
Indoor Db/Wb
Outdoor
DB
Suction
Pressure
Suction
Temp.
Liquid
Pressure
Liquid
Temp.
Delta T
Db
Compr.
amps
300 Cfm/Ton
80/62
75
129
59
279
88
-29
9.7
85
132
59
298
92
-28
10.2
95
136
56
343
102
-27
11.2
300 Cfm/Ton
80/67
75
141
66
279
87
-25
9.7
85
146
63
304
93
-23
10.4
95
150
62
350
102
-22
11.4
300 Cfm/Ton
80/72
75
151
72
278
84
-20
9.6
85
156
71
309
93
-19
10.3
95
162
69
354
102
-18
11.5
300 Cfm/Ton
75/63
75
131
58
279
87
-24
9.8
85
135
58
300
92
-22
10.1
95
140
56
347
100
-21
11.2
400 Cfm/Ton
80/62
75
136
64
279
87
-26
9.7
85
141
65
303
93
-25
10.3
95
145
62
348
102
-24
11.3
400 Cfm/Ton
80/67
75
147
68
279
86
-22
9.6
85
151
68
307
93
-21
10.3
95
156
65
351
102
-19
11.4
400 Cfm/Ton
80/72
75
157
74
279
81
-17
9.5
85
163
74
311
91
-16
10.3
95
169
72
358
102
-15
11.7
400 Cfm/Ton
75/63
75
138
61
279
87
-21
9.7
85
141
60
303
92
-20
10.3
95
145
58
348
100
-18