5219967-UTG-A-0716
Johnson Controls Unitary Products
13
UNIT DIMENSIONS
Model
Dimensions
A
B
C
24
51-1/4
35-3/4
47
30
51-1/4
35-3/4
47
36
51-1/4
45-3/4
49
42
51-1/4
45-3/4
49
48
51-1/4
45-3/4
53
60
51-1/4
45-3/4
55
UNIT CLEARANCES
1
2
1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Direction
Distance (in.)
Direction
Distance (in.)
Top
3
3. Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.
36
Power Entry (Right Side)
36
Side Opposite Ducts
36
Left Side
24
Duct Panel
0
Bottom
4
4. Units may be installed on combustible materials made from wood or class A, B or C roof covering materials only if factory base rails are left in place as shipped.
1
INDOOR BLOWER SPECIFICATIONS
Model
Motor
HP
RPM
EFF.
SF
Frame
24050, 30050
1/3
Variable
0.8
1.0
48
24075, 30075, 36065
1/2
Variable
0.8
1.0
48
36100, 42065. 42100,
48065, 48100, 48125
3/4
Variable
0.8
1.0
48
60065, 60100, 60125
1
Variable
0.8
1.0
48
SOUND PERFORMANCE
Model
(Tons)
Sound Rating
1
dB (A)
1. Rated in accordance with AHRI Standard 270.
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
24
75
62.4
61.5
64.2
67
61
57.3
49.6
30
75
60.5
61.6
64.8
66.9
60.9
56.0
49.7
36
74
58.5
61.8
65.4
66.5
60.7
54.8
49.8
42
74
63.5
63.9
62.3
65
64
54.1
46.6
48
74
63.5
63.9
62.3
65
64
54.1
46.6
60
76
72.3
65.0
63.9
64
60
55.5
49.0
HIGH VOLTAGE
CONNECTION 7/8”
HIGH VOLTAGE
CONNECTION 1-3/32”
COMPRESSOR
ACCESS PANEL
CONDENSATE
DRAIN
BLOWER
ACCESS
PANEL
CONTROL ACCESS
PANEL
LOW VOLTAGE CONNECTION
GAS SUPPLY
EXHAUST HOOD
COMBUSTION AIR INTAKE
HEAT EXCHANGER ACCESS PANEL
B
A
C
A0296-001
COIL GUARD