background image

1183746-UIM-B-0215

Johnson Controls Unitary Products

17

COOLING SEQUENCE OF OPERATIONS

When the thermostat calls for COOL, the thermostat terminals G and Y
are energized, which signals the compressor, outdoor fan and indoor
blower to run.

With a call for Y, the circulating fan is energized at cooling speed.

When the thermostat is satisfied, terminals G and Y are de-energized,
de-energizing the compressor and outdoor fan.

After a cool fan off delay timing of 30 seconds, the circulating fan is de-
energized.

Safety Controls

The control circuit includes the following safety controls:

High Pressure Switch (HP) - This switch protects against excessive dis-
charge pressures due to a blocked condenser coil or a condenser
motor failure (opens at 650 ± 25 psig and closes at 450 ± 25 psig).

The above pressure switches are specifically designed to operate with
R-410A systems. R-22 pressure switches must not be used as replace-
ments for the R-410A pressure switches.

Circulating Fan

When the thermostat calls for FAN, the thermostat terminal G is ener-
gized signaling the circulating fan to run at the G-Speed airflow.

If a call for COOL occurs (Y), the circulating fan switches to run at the Y-
Speed airflow.

If a call for HEAT occurs (W), the circulating fan switches to W-Speed
after a 30 second delay.

When the thermostat ends the call for FAN, the thermostat terminal G is
de-energized, de-energizing the circulating fan.

START-UP

Prestart Check List

Complete the following checks before starting the unit.

1.

Check the type of gas being supplied. Be sure that it is the same as
listed on the unit nameplate.

2.

Make sure that the vent outlet air hood and air intake hood has
been properly installed.

Operating Instructions

1.

STOP! Read the information on the unit safety label.

2.

Set the thermostat to the OFF position.

3.

Turn off all electrical power to the unit.

4.

DO NOT try to light the burners by hand. This appliance is
equipped with an ignition device which automatically lights the
burners.

5.

Remove the access panel.

6.

Turn the gas valve switch to the OFF position.

7.

Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow B in the information on the unit safety label. If you
don't smell gas, go to the next step.

8.

Turn the gas valve switch to the ON position.

9.

Replace the control access panel.

10. Turn on all electric power to the unit.
11. Set the thermostat to the desired setting.
12. If the unit will not operate, follow the instructions To Turn Off Gas To

Appliance and call your service technician or gas supplier.

To Turn Off Gas To Unit

1.

Set the thermostat to the OFF position.

2.

Turn off all electric power to the appliance if service is to be per-
formed.

3.

Remove the control access panel.

4.

Turn the gas valve switch to the OFF position. DO NOT FORCE.

5.

Replace the control access panel.

Post Start Check List

After the entire control circuit has been energized and the heating sec-
tion is operating, make the following checks:

1.

Check for gas leaks in the unit piping as well as the supply piping.

2.

Check for correct manifold gas pressures. See Checking Gas Input.

3.

Check the supply gas pressure. It must be within the limits shown
on rating nameplate. Supply pressure should be checked with all
gas appliances in the building at full fire. At no time should the
standby gas line pressure exceed 13.5", nor the operating pressure
drop below 4.5" for natural gas units. If gas pressure is outside
these limits, contact the local gas utility for corrective action.

Manifold Gas Pressure Adjustment

Small adjustments to the gas flow may be made by turning the pressure
regulator adjusting screw on the automatic gas valve. 
Refer to Figure 10.

Adjust as follows:

1.

Remove the cap from the valve body. See Figure 10 for location.

2.

To decrease the gas pressure, turn the adjusting screw counter-
clockwise. 

3.

To increase the gas pressure, turn the adjusting screw clockwise.

Adjustment of Temperature Rise

After about 20 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts
about six feet from the furnace where they will not be affected by radi-
ant heat.

The temperature rise (or temperature difference between the return air
and the heated air from the furnace) must lie within the range shown on
the rating plate and the data in Table 6.

After the temperature rise has been determined, the CFM can be calcu-
lated as follows:

 WARNING

The ability to properly perform maintenance on this equipment
requires certain expertise, mechanical skills, tools and equipment. If
you do not possess these, do not attempt to perform any mainte-
nance other than those procedures recommended in this Installation
Manual. Failure to heed this warning could result in serious injury
and possible damage to this equipment.

!

 FIGURE 9:  

Gas Valve

NOTICE

The correct manifold pressure for natural gas furnaces is 3.5 IWG.
The correct manifold pressure for propane (LP) is 10.0 IWG.

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON

OFF

ON/OFF SWITCH
(Shown in ON position)

MAIN REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT PORT

A0303-001

BTUH Output

1.08 x CFM

OR

CFM =  

BTUH Output

Degrees F Temp Rise =  

1.08 x Degrees F Temp Rise

Summary of Contents for PCG4 Series

Page 1: ...y gas piping electric power and duct connections are required at the point of installation The gas fired heaters have spark ignition The refrigerant system is fully charged with R 410A Refrigerant and is tested and factory sealed SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Understand and pay particul...

Page 2: ...ce or additional information consult a qualified installer service agency or the gas supplier CAUTION This system uses R 410A Refrigerant which operates at higher pres sures than R 22 No other refrigerant may be used in this system Gage sets hoses refrigerant containers and recovery systems must be designed to handle R 410A If you are unsure consult the equip ment manufacturer Failure to use R 410...

Page 3: ... unit to meet local codes they are to be installed at the dealer s and or customer s expense Size of unit for proposed installation should be based on heat loss heat gain calculation made according to the methods of Air Conditioning Contractors of America ACCA This furnace is not to be used for temporary heating of buildings or structures under construction FIGURE 1 Component Location FAN MOTOR CO...

Page 4: ...h a forklift Slotted openings in the base rails are provided for this purpose WARNING Excessive exposure of this furnace to contaminated combustion air may result in equipment damage or personal injury Typical contami nates include permanent wave solution chlorinated waxes and cleaners chlorine based swimming pool chemicals water softening chemicals carbon tetrachloride Halogen type refrigerants c...

Page 5: ...and recirculate Direction Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge outlet 48 Power Entry Right Side 42 Side Opposite Ducts 36 Left Side 36 Duct Panel 12 Bottom4 4 Units may be installed on combustible floors made from class A B or C roof covering materials 1 HIGH VOLTAGE CONNECTION 7 8 HIG...

Page 6: ...y the blower decreasing your units efficiency and increasing operating costs and wear and tear on the unit and controls Filters should be checked monthly this is especially important since this unit is used for both heating and cooling CONDENSATE DRAIN A condensate trap must be installed in the condensate drain The plumbing must conform to local codes DO NOT use Teflon tape or Pipe thread compound...

Page 7: ...h unit must be wired with a separate branch circuit fed directly from the main distribution panel and properly fused Refer to Figures 7 and 8 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information FIGURE 6 Typical Field Control Wiring Diagram For Gas Heat AC Models FIGURE 7 Typical Field Power Wiring Diagram THERMOSTAT NOTE Heat Anticip...

Page 8: ...Operating WT lbs 359 366 379 386 415 422 426 442 446 495 503 508 522 530 535 Compressors Type Recip Recip Recip Scroll Scroll Scroll Condenser Coil Data Face area Sq Ft 15 1 17 0 15 1 17 0 23 8 26 0 Rows 1 1 2 2 2 2 Fins per inch 22 22 22 22 22 22 Tube diameter 3 8 3 8 3 8 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Evaporator Coil Data Face area Sq...

Page 9: ... on the outside of the pipe and blowing out the loose dirt and scale Before initial start up be sure that all of the gas lines external to the unit have been purged of air CAUTION This system uses R 410A Refrigerant which operates at higher pres sures than R 22 No other refrigerant may be used in this system CAUTION Do not leave the system open to the atmosphere Unit damage could occur due to mois...

Page 10: ...y unauthorized human contact around this area during the heating cycle Flue hood surfaces and the immediate area reach high temperatures during the heating cycle New Graphic to be added later AIR INTAKE HOOD AIR INTAKE SCREEN EXHAUST HOOD A0284 001 Table 9 Natural Gas Application Data Available On Models Input MBH 1 High Fire 1 Heating capacity valid for elevations up to 2000 feet above sea level ...

Page 11: ...995 942 889 834 Medium 3 1259 1209 1166 1126 1084 1032 980 928 Medium High 4 1314 1271 1229 1186 1144 1097 1049 998 High 5 1506 1471 1403 1389 1345 1305 1262 1216 36075 Low 1 1225 1174 1131 1090 1046 993 941 888 Low Medium 2 1259 1209 1166 1126 1084 1032 980 928 Medium 3 1314 1271 1229 1186 1144 1097 1049 998 Medium High 4 1348 1306 1259 1222 1179 1133 1086 1036 High 5 1506 1471 1403 1389 1345 130...

Page 12: ...1413 Medium 3 1922 1863 1804 1754 1724 1658 1612 1559 Medium High 4 2001 1952 1890 1839 1820 1742 1696 1651 High 5 2146 2085 2025 1960 1872 1862 1798 1735 60065 Low 1 1073 1043 1009 988 963 941 917 892 Low Medium 2 1329 1292 1250 1223 1192 1165 1136 1105 Medium 3 2054 1998 1934 1890 1843 1801 1757 1710 Medium High 4 2195 2144 2098 2049 2003 1955 1883 1868 High 5 2445 2388 2306 2293 2235 2178 2129 ...

Page 13: ... 863 Medium 3 1262 1223 1181 1137 1091 1044 994 952 Medium High 4 1324 1282 1245 1202 1161 1112 1067 1018 High 5 1517 1475 1447 1400 1357 1318 1275 1232 36075 Low 1 1231 1186 1146 1103 1069 1030 977 912 Low Medium 2 1270 1225 1189 1140 1098 1046 1008 960 Medium 3 1317 1286 1245 1198 1151 1110 1064 1024 Medium High 4 1358 1317 1275 1238 1197 1148 1105 1057 High 5 1517 1475 1447 1400 1357 1318 1275 ...

Page 14: ...1419 Medium 3 1912 1875 1805 1787 1750 1713 1672 1636 Medium High 4 2105 2014 2006 1931 1898 1845 1793 1739 High 5 2131 2058 1998 1949 1892 1840 1788 1728 60065 Low 1 1026 999 989 950 907 907 886 862 Low Medium 2 1263 1230 1192 1165 1167 1101 1099 1071 Medium 3 1987 1933 1861 1817 1820 1715 1725 1651 Medium High 4 2114 2050 2047 1974 1899 1889 1920 1866 High 5 2369 2308 2249 2183 2126 2088 2034 19...

Page 15: ...on trial If the call for heat is removed during an ignition trial period the control immediately de energizes spark and gas The control runs the inducer motor through a post purge period before de energizing If the pressure switch opens during an ignition trial period the control immediately de energizes spark and gas The control begins pressure switch proving before an inter purge and reignition ...

Page 16: ...ved or a call for heat W is removed Rollout switch lockout shall not reset automatically Power Interruptions Power interruptions of any duration shall not cause lockout or any oper ation requiring manual intervention Flame present with Gas off If flame is sensed for longer than 4 0 seconds during a period when the gas valve should be closed the control will enter lockout flashing 1 on the LED The ...

Page 17: ...our service technician or gas supplier To Turn Off Gas To Unit 1 Set the thermostat to the OFF position 2 Turn off all electric power to the appliance if service is to be per formed 3 Remove the control access panel 4 Turn the gas valve switch to the OFF position DO NOT FORCE 5 Replace the control access panel Post Start Check List After the entire control circuit has been energized and the heatin...

Page 18: ...on sumed per hour by the BTU content of the gas in your particular locality Contact your gas company for this information since it varies widely from city to city Table 15 Gas Rate Cubic Feet Per Hour1 1 EXAMPLE By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this information locate 38 seconds in th...

Page 19: ...U 43 GND BLK WHT 11 CONTACTOR COIL SINGLE POLE CONTACTOR RED 45 BLU 42 BLU 30 PUR 2 YEL 21 BLK YEL 18 GRN 44 LINE VOLTAGE FIELD INSTALLED POWER LOW VOLTAGE FIELD INSTALLED CONTROL 5 4 3 2 6 1 BLK BRN GRN 10 RED COOLING UNIT WITH GAS HEAT CONNECTION WIRING DIAGRAM CAUTION OPEN ALL DISCONNECTS BEFORE SERVICING THIS UNIT 1 ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY LOCAL AND OR NATIONAL CODES...

Page 20: ... CONTACTOR COIL 4 2 F H C DUAL CAPACITOR START CAP 1 2 5 START RELAY T1 L1 L2 T2 DRAFT MOTOR CONTROL BOARD RELAY CAP BLU RED WHT GRN Y R G C THERMOSTAT RED GRN ORG RED RED BLK ROLLOUT PRESSURE LIMIT FS L1 IND SPARK TRANSFORMER YEL YEL GRN ORG 4 5 6 1 2 3 7 8 9 3 2 1 24V COM Y SPD G SPD W SPD W Y O R G C RED ORG IGNITOR FLAME SENSOR GAS VALVE CONTROL BOARD W YEL BLU YEL RED WHT 3A FUSE BLK RED RED ...

Page 21: ...TACTOR RED 45 BLU 42 BLU 30 PUR 2 YEL 21 BLK YEL 18 GRN 44 LINE VOLTAGE FIELD INSTALLED POWER LOW VOLTAGE FIELD INSTALLED CONTROL 5 4 3 2 6 1 BLK BRN GRN 10 RED COOLING UNIT WITH GAS HEAT CONNECTION WIRING DIAGRAM CAUTION OPEN ALL DISCONNECTS BEFORE SERVICING THIS UNIT 1 ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY LOCAL AND OR NATIONAL CODES IN EFFECT AT THE TIME OF INSTALLATION OF THE UNIT...

Page 22: ...MOTOR 5 3 C 1 HI PRESS CONTACTOR COIL 4 2 F H C DUAL CAPACITOR T1 L1 L2 T2 DRAFT MOTOR CONTROL BOARD RELAY CAP BLU RED WHT GRN Y R G C THERMOSTAT RED GRN ORG RED RED BLK ROLLOUT PRESSURE LIMIT FS L1 IND SPARK TRANSFORMER YEL YEL GRN ORG 4 5 6 1 2 3 7 8 9 3 2 1 24V COM Y SPD G SPD W SPD W Y O R G C RED ORG IGNITOR FLAME SENSOR GAS VALVE CONTROL BOARD W YEL BLU YEL RED WHT 3A FUSE BLK RED BRN RED OD...

Page 23: ...y Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC refrigerants Systems must be charged with liquid refrigerant Use a commercial type metering device in the manifold hose R 410A can only be used with POE type oils POE type oils rapidly absorb moisture ...

Page 24: ...1183746 UIM B 0215 24 Johnson Controls Unitary Products NOTES ...

Page 25: ...L1 to L2 L2 to L3 L1 to L3 Total amperes L1 L2 L3 Compressor amperes L1 L2 L3 Measured voltage R and C outdoor unit control board Electrical Connections Inspection Check all that apply Equipment Data Additional Kits Accessories Installed Check all that apply Equipment Data Blower Type Set Up Supply air dry bulb temperature ADJUST A B C D A B C D Total external static pressure Supply static inches ...

Page 26: ...ion and Cycle Test Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Job site has been cleaned indoor and outdoor debris removed from job site Tools have been removed from unit All panels have been installed TXV Fixed Orifice Liquid line temperature Suc...

Reviews: