5324339-YTG-D-1117

14

Johnson Controls Unitary Products

NOTES: 

1. Airflow tested with dry coil conditions, without air filters, at 460 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency enhanced ECM blower motor used for all indoor blower assemblies.
4.

 

Minimal variations in airflow performance data results from using downflow duct applications. Data above may be used in those cases.

5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.

RECOMMENDED BLOWER SPEED FOR ELECTRIC HEAT

Model

Heater kW

10

15

18

20

25

PCE6B36

C (ML)

A (HI)

--

--

--

PCE6B48

D (LO)

C (ML)

B (MH)

A (HI)

--

PCE6B60

D (LO)

D (LO)

C (ML)

B (MH)

A (HI)

NOTE: T

he recommended HEAT speed selections above will give approximately a 45 degree temperature rise at 0.3" static with 460V power supply. If lower or higher

             heating airflow is desired, or if duct static or voltage are different than specified, other speed taps may be used.

AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION 

Model

Jumper Position

External Static Pressure (Inches WC)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

36

High Cool

A 1621

1531

1454

1371

1299

1223

1138

1039

966

869

B 1507

1418

1339

1268

1200

1130

1059

981

911

837

C 1410

1288

1209

1132

1054

982

904

831

755

691

D 1224

1137

1052

978

902

824

748

682

611

549

Low Cool

A 1060

964

879

795

706

623

538

459

397

331

B 1017

919

830

742

650

570

487

415

344

276

C 974

875

780

688

595

517

436

371

291

222

D 813

721

617

509

404

323

237

171

81

81

Heat

A 1264

1179

1092

1017

942

865

787

735

662

598

B 1147

1056

972

895

815

735

657

578

511

450

C 1003

904

813

724

632

552

470

400

327

258

D 902

802

700

602

504

429

348

292

201

201

48

High Cool

A 1893

1845

1804

1764

1717

1672

1625

1576

1528

1473

B 1785

1737

1694

1650

1597

1547

1501

1452

1392

1335

C 1703

1649

1595

1546

1491

1436

1385

1327

1264

1200

D 1654

1596

1535

1483

1427

1370

1315

1252

1187

1118

Low Cool

A 1304

1225

1152

1072

998

893

842

785

731

648

B 1265

1183

1109

1026

950

839

789

733

681

596

C 1200

1116

1039

952

874

757

707

652

599

512

D 1304

1225

1152

1072

998

893

842

785

731

648

Heat

A 1423

1351

1281

1211

1143

1056

1002

941

883

804

B 1304

1225

1152

1072

998

893

842

785

731

648

C 1125

1039

957

870

791

672

623

564

507

416

D 1000

912

820

733

652

529

481

418

354

255

60

High Cool

A 2305

2255

2215

2164

2103

2074

2024

1965

1910

1867

B 2186

2144

2101

2059

2003

1956

1930

1886

1837

1796

C 2007

1963

1919

1873

1828

1781

1731

1693

1646

1606

D 1935

1887

1840

1788

1754

1702

1645

1609

1560

1519

Low Cool

A 1675

1627

1566

1512

1473

1423

1374

1324

1278

1234

B 1523

1463

1405

1350

1302

1248

1196

1143

1089

1044

C 1369

1307

1251

1196

1141

1082

1024

964

907

849

D 1413

1352

1295

1240

1187

1130

1073

1015

959

905

Heat

A 1762

1724

1661

1608

1574

1526

1478

1429

1390

1341

B 1479

1418

1361

1306

1256

1201

1147

1092

1037

989

C 1369

1307

1251

1196

1141

1082

1024

964

907

849

D 1209

1147

1084

1022

957

897

835

777

722

669

Summary of Contents for PCE6*36 Series

Page 1: ... and tested prior to shipment Test stations using a state of the art computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via computers during assembly Vital run test statistics such as system pressure motor cur rents air velocity and temperature unit vibration and gas system safeties are monitored and recorded by the system to i...

Page 2: ... must be set to YES and a humidistat is connected from the low volt age R and HUM color coded leads During cooling operation if the humidity level is above the humidistat set point the indoor blower speed is reduced by approximately 15 Simple Control Circuit Field thermostat wiring connect to color coded leads using twist on wire connections Cooling controls use a contactor and a 2nd stage 24 VAC ...

Page 3: ... not low Nox 3 Cabinet Size A small 35 x 51 B large 45 x 51 8 Generation Level 1 first generation 4 Nominal Air Conditioning Cooling Capacity BTUx1000 24 24 000 BTU etc 9 Revision Level A original release B second release Examples PCE6B4221A is a packaged A C with electric heat 16 SEER 3 1 2 ton large cabinet 230 volt single phase low NOx model first generation first release COMPONENT LOCATION 287...

Page 4: ... duct openings on the roof curb Transition is from rectangle to 16 round for the 1AK0108 kit and from rectangle to 18 round for the 1AK0109 kit Roof Curbs S1 1RC0503 S1 1RC0501 NRCA approved curbs provide proper fit to base unit for rooftop installations Curbs are designed to be assembled through hinge pins in each corner Kit also provides seal strip to assure an air tight seal These are 8 inch hi...

Page 5: ...reated galvanized steel shall provide a better paint to steel bond which resists corrosion and rust creep Powder paint finish shall provide superior corrosion resistance 1000 hour salt spray tested On Site Flexibility All model sizes shall use a compact design cabinet Field convertible duct connections from side shot to down shot allows the installer to have greater flexibil ity with less inventor...

Page 6: ... to control refrigerant flow CONTROLS Simple Control Circuit Field thermostat wiring connects to color coded leads using twist on wire connections Cooling controls use contactor and relays for simple application and troubleshooting Mate n lock plug connectors are used Enhanced ECM indoor blower control is managed by a multi stage indoor blower control board that includes field adjust able speed ta...

Page 7: ...pe Interlaced Interlaced Interlaced Indoor Coil Data Face area Sq Ft 6 3 6 3 6 3 Rows 3 3 4 Fins per inch 16 16 16 Tube diameter 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Refrigerant control TXV TXV TXV Outdoor Fan Data Fan diameter Inch 26 26 26 Type Prop Prop Prop Drive type Direct Direct Direct No speeds 1 1 1 Motor HP each 1 3 1 3 1 3 RPM 850 850 850 Nominal total CFM 3200 32...

Page 8: ...7 10 4 17 6 18 1 15 4 16 6 11 0 18 7 19 4 17 7 18 5 11 7 K W 4 23 4 22 4 19 4 19 4 13 4 17 4 18 4 18 4 15 4 10 4 11 4 14 4 17 4 12 4 07 COOLING PERFORMANCE DATA 3 TON HIGH SPEED PACKAGED UNIT MODEL NO PCE6B36 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1000 1200 1400 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 38 5 41 0 40 0 43 2 46 6...

Page 9: ...7 4 17 5 12 5 20 4 11 4 17 9 17 6 11 8 22 3 12 1 K W 3 98 4 10 3 98 3 91 3 89 3 99 4 05 4 00 3 92 3 93 4 00 4 01 4 02 3 93 3 97 COOLING PERFORMANCE DATA 4 TON HIGH SPEED PACKAGED UNIT MODEL NO PCE6B48 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1400 1600 1800 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 46 5 54 3 55 5 56 6 59 6 47 9 54...

Page 10: ... 24 3 27 5 24 6 25 9 18 4 25 1 26 7 25 2 27 5 19 6 K W 4 57 4 38 4 39 4 35 4 32 4 58 4 47 4 49 4 46 4 43 4 58 4 57 4 59 4 56 4 54 COOLING PERFORMANCE DATA 5 TON HIGH SPEED PACKAGED UNIT MODEL NO PCE6B60 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1600 1800 2000 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 59 2 68 9 66 5 71 8 77 1 61 3 ...

Page 11: ...ntire length of duct 2 Units must be installed outdoors Overhanging structures or shrubs should not obscure outdoor air discharge outlet 3 Units may be installed on combustible floors made from wood or class A B or C roof covering materials Note For units applied with a roof curb the minimum clearance may be reduced from 1 inch to 1 2 inch between combustible roof curb material and this supply air...

Page 12: ...02546 22 1 27 6 31 5 35 13 7 20 34 5 35 NOTES Single source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field installed single point power modification 1 MCA Minimum Circuit Ampacity 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit breaker to be field installed 4 Single Point Connection Required ELECTRICAL DATA FOR ...

Page 13: ...1 2SPWK036 15 25 6HK06501846 S1 2SPWK036 15 25 6HK06502046 S1 2SPWK036 15 30 PCE6B6041 460 3 60 6HK06501046 S1 2SPWK036 20 15 6HK06501546 S1 2SPWK036 20 25 6HK06501846 S1 2SPWK036 20 25 6HK06502046 S1 2SPWK036 20 30 6HK06502546 S1 2SPWK037 20 35 WEIGHTS AND DIMENSIONS Model Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D PCE6B36 466 461 32 13 167 131 130 38 PC...

Page 14: ...60 964 879 795 706 623 538 459 397 331 B 1017 919 830 742 650 570 487 415 344 276 C 974 875 780 688 595 517 436 371 291 222 D 813 721 617 509 404 323 237 171 81 81 Heat A 1264 1179 1092 1017 942 865 787 735 662 598 B 1147 1056 972 895 815 735 657 578 511 450 C 1003 904 813 724 632 552 470 400 327 258 D 902 802 700 602 504 429 348 292 201 201 48 High Cool A 1893 1845 1804 1764 1717 1672 1625 1576 1...

Page 15: ...2 0 16 1300 0 07 0 03 0 17 1400 0 08 0 04 0 18 48 4 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 60 5 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08...

Page 16: ...OOF CURB INSTALLATION REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A0324 001 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0390 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT CONDENSATE DRAIN ...

Page 17: ...on Controls Unitary Products 17 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT ROOF CURB ROOF CONDENSATE DRAIN A0389 001 ...

Page 18: ... change without notice Published in U S A 5324339 YTG D 1117 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes 5324339 YTG C 0817 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: