Electrical Data
Electrical Data For Outdoor Models
Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP
Qty
FLA
(each)
FLA
YC090
208/230-3-60
1
25.0
39
164
208/230-1-60
1/3
2
2.1
-
35.5
45
460-3-60
1
12.2
19
100
460-1-60
1/3
2
1.2
-
17.6
25
575-3-60
1
9.0
14
78
575-1-60
1/3
2
0.9
-
13.1
20
YC120
208/230-3-60
2
15.7
24.5
110
208/230-1-60
3/4
2
3.0
-
41.4
50
460-3-60
2
7.8
12.0
52
460-1-60
3/4
2
1.6
-
20.8
25
575-3-60
2
5.8
9.1
39
575-1-60
3/4
2
1.4
-
15.8
20
YC150
208/230-3-60
2
22.4
35
149
208/230-1-60
3/4
2
3.0
-
56.5
70
460-3-60
2
10.6
17
75
460-1-60
3/4
2
1.6
-
27.1
35
575-3-60
2
7.7
12
54
575-1-60
3/4
2
1.4
-
20.0
25
YD150
208/230-3-60
2
22.4
35
149
208/230-1-60
3/4
2
3.0
-
56.5
70
460-3-60
2
10.6
17
75
460-1-60
3/4
2
1.6
-
27.1
35
575-3-60
2
7.7
12
54
575-1-60
3/4
2
1.4
-
20.0
25
YC180
208/230-3-60
2
25.0
39
164
208/230-1-60
1/3
4
2.1
-
64.7
80
460-3-60
2
12.2
19
100
460-1-60
1/3
4
1.2
-
32.2
40
575-3-60
2
9.0
14
78
575-1-60
1/3
4
0.9
-
24.0
30
YD180
208/230-3-60
2
25.0
39
164
208/230-1-60
3/4
4
3.0
-
68.4
90
460-3-60
2
12.2
19
100
460-1-60
3/4
4
1.6
-
33.9
45
575-3-60
2
9.0
14
78
575-1-60
3/4
4
1.4
-
25.7
30
YC240
208/230-3-60
2
30.1
47
225
208/230-1-60
3/4
4
3.0
-
79.8
100
460-3-60
2
16.7
26
114
460-1-60
3/4
4
1.6
-
44.0
60
575-3-60
2
12.2
19
80
575-1-60
3/4
4
1.4
-
32.9
45
YD240
208/230-3-60
2
30.1
47
225
208/230-1-60
3/4
4
3.0
-
79.8
100
460-3-60
2
16.7
26
114
460-1-60
3/4
4
1.6
-
44.0
60
575-3-60
2
12.2
19
80
575-1-60
3/4
4
1.4
-
32.9
45
YC300
208/230-3-60
2
48.1
75
245
208/230-1-60
3/4
4
3.0
-
120.3
150
460-3-60
2
18.6
29
125
460-1-60
3/4
4
1.6
-
48.3
60
575-3-60
2
14.7
23
100
575-1-60
3/4
4
1.4
-
38.5
50
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Summary of Contents for NC090-300
Page 73: ...505428 YTG V 0417 Johnson Controls Unitary Products 73 Typical YC120 150 Wiring Diagram...
Page 74: ...505428 YTG V 0417 74 Johnson Controls Unitary Products Typical YD120 150 Wiring Diagram...
Page 75: ...505428 YTG V 0417 Johnson Controls Unitary Products 75 Typical YC180 Wiring Diagram...
Page 76: ...505428 YTG V 0417 76 Johnson Controls Unitary Products Typical YC240 Wiring Diagram...
Page 77: ...505428 YTG V 0417 Johnson Controls Unitary Products 77 Typical YC300 Wiring Diagram...
Page 78: ...505428 YTG V 0417 78 Johnson Controls Unitary Products Typical YD180 240 Wiring Diagram...
Page 80: ...505428 YTG V 0417 80 Johnson Controls Unitary Products Typical PC120 Wiring Diagram...
Page 81: ...505428 YTG V 0417 Johnson Controls Unitary Products 81 Typical PC180 Wiring Diagram...
Page 82: ...505428 YTG V 0417 82 Johnson Controls Unitary Products Typical PD180 240 Wiring Diagram...