background image

6

ENGLISH

OPTIMAL OPERATION

To achieve optimal performance, Please note the following:
• Adjust the air flow direction correctly so that it is not directed on people.
• Adjust the temperature to achieve the highest comfort level. Do not adjust the unit to excessive temperature levels.
• Close doors and windows on COOL or HEAT modes, or performance may be reduced.
• Use TIMER ON button on the remote controller to select a time you want to start your air conditioner.
• Do not put any object near air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air

conditioner may stop running.

• Clean the air filter periodically, otherwise cooling or heating performance may be reduced.
• Do not operate unit with horizontal louver in closed position.

PREPARATION BEFORE INSTALLATION

• Before doing any work, check the interior power supply cord and the main breaker capacity are sufficient and the

installation area is sufficient and complies with the requirements.

• Check that the power supply available agrees with name plate voltage.
• Electrical work, wiring and cables must be in compliance with national and local wiring codes and standard.
• Do not use the extension cables. In the case extended cables are needed, use the terminal block.

SELECTION OF THE LOCATION

• Select a place which provides the space around the units as shown in the diagram below.

INDOOR UNIT

OUTDOOR UNIT

• Do not install in a place that cannot bear the weight of the unit.

CAUTION

Models

07

09

12

18

24

A

12cm

12cm

12cm

12cm

12cm

B

70cm

70cm

70cm

70cm

70cm

C

12cm

12cm

12cm

12cm

12cm

D

15cm

15cm

15cm

15cm

15cm

Models

07

09

12

18

24

A

30cm

30cm

30cm

30cm

30cm

B

200cm

200cm

200cm

200cm

200cm

C

60cm

60cm

60cm

60cm

60cm

D

30cm

30cm

30cm

30cm

30cm

J199.pmd

31/03/2005, 9:53 PM

6

Summary of Contents for MLCA-MLHA-07-24 manua

Page 1: ...Manual MODELS MLCA MLHA 07 24 MLCB MLHB 07 24 MACC MAHC 07 24 MINISPLIT HIGH WALL AIR CONDITIONER EN035M80013 000 The units comply with one or more of the following marks see unit for details J199 pmd...

Page 2: ...ion Quality POLICY We will continuously strive to satisfy our customers with consistent reli ability in product service and support through superior quality service culture and distinctive technology...

Page 3: ...ning system should only be carried out by trained and qualified personnel After unpacking please check the unit carefully for possible damage Before undertaking any work on the unit make sure that the...

Page 4: ...icator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating operation 3 TEMPERATURE indicator Displays the temperature sett...

Page 5: ...ing on what temperature you have selected and the room temperature The air conditioner will control room temperature automatically around the temperature point set by you If the AUTO mode is uncomfort...

Page 6: ...RE INSTALLATION Before doing any work check the interior power supply cord and the main breaker capacity are sufficient and the installation area is sufficient and complies with the requirements Check...

Page 7: ...45 5 420 128 780 48 10 45 548 115 90 266 272 298 285 290 530 110 62 590 750 MLDA MLJA 07 09 MLDB MLJB 07 09 MADC MAJC 07 MLDA MLJA 12 18 MLDB MLJB 12 MADC MAJC 09 12 MLDA MLJA 24 MLDB MLJB 24 MADC MAJ...

Page 8: ...run of 3 metres is required to minimise vibration excessive noise The indoor unit should be installed on the wall at a height of 2 3 metres or more from the floor A B and C directions should be free f...

Page 9: ...may be unstable on the wall Carefully arrange pipes so that pipes do not stick out of the rear plate of the indoor unit A B C D E F MODEL 24 Right Right Right Right Left Rear Bottom Drain hose Drain h...

Page 10: ...t any pipe vibrations cannot be transmitted to the building structure Connect the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tighten...

Page 11: ...ng piping length of 5 meters Liquid Cooling GAS Cooling suction Low pressure High pressure Manifold Gas valve Liquid valve Pressure tap Outdoor unit Indoor unit Gas line Liquid line R22 R407C R410A Ou...

Page 12: ...ed installation acceptance please refer to your contract with the power supplier if restrictions do apply for products like washing machines air conditioner or electrical ovens 4 For power details of...

Page 13: ...Te S 1 2 N Cooling heating type Cord clamp 1 2 N 3 4 5 6 7 8 Terminal block of Outdoor unit 1 2 N S L N Terminal block of indoor unit Cooling only type cooling heating type Terminal block of indoor u...

Page 14: ...itch back to heating mode when either of the following conditions is met a Unit has been running at defrosting mode for 10 minutes b T3 20 C Remark T3 is coil temperature of outdoor units 0 1 2 3 4 5...

Page 15: ...day to dry the inside of the unit 2 Stop the air conditioner and disconnect power Remove the batteries from the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not...

Page 16: ...unit This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit 5 A peculiar smell come out from the indoor unit This is caused by the indoo...

Page 17: ...Insulate them separately together 3 The room was probably very hot 3 Wait while unit has enough time to cool when you started the cool the room system D The compressor runs continuously 1 Thermostat...

Page 18: ...LDA24 MLJA24 0 8 0 8 1 01 1 01 1 35 1 35 1 96 1 96 2 8 2 8 3 5 3 5 4 6 4 6 6 0 6 0 9 4 9 4 12 5 12 5 1 1 1 1 1 530 570 580 800 850 900 1130 1400 1450 1900 35 32 30 35 32 30 37 34 32 37 34 32 37 32 28...

Page 19: ...LJA12 MLDA18 MLJA18 MLDA24 MLJA24 0 71 0 71 0 95 0 95 1 21 1 21 1 95 1 95 2 67 2 67 3 2 3 2 4 5 4 5 5 5 5 5 8 9 8 9 12 1 12 1 1 1 1 1 1 530 590 630 650 780 1050 1180 1450 1450 1900 35 32 30 35 32 30 3...

Page 20: ...MLDB18 MLJB18 MLDB24 MLJB24 0 78 0 78 1 1 1 35 1 35 1 96 1 96 2 73 2 73 3 5 3 5 4 4 4 4 6 0 6 0 9 4 9 4 12 5 12 5 1 1 1 1 1 680 700 820 850 900 1200 1400 1400 1950 2050 35 32 30 35 32 30 37 34 32 37 3...

Page 21: ...MADC18 MAJC18 MADC24 MAJC24 0 64 0 64 0 82 0 82 1 12 1 12 1 72 1 72 2 53 2 53 2 8 2 8 3 6 3 6 5 0 5 0 7 8 7 8 11 2 11 2 1 1 1 1 1 800 820 900 920 1050 1080 1690 1740 1900 1950 35 32 30 35 32 30 37 34...

Page 22: ...ds of lifting Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above 4 4 4 4 4 After removal from position the unit parts may be disposed of according t...

Reviews: