NOTES:
For On/Off functions, 1 is ON and 0 is OFF
Read only items are readings from sensors which only change as the measured condition changes.
47
Exhaust Damper Position for Exhaust Fan to
Turn Off (Modulating Only)
% Of Damper Position
0-100
20%
48
Economizer Damper Position for Exhaust Fan
to Turn On (Non-Modulating Only)
% Of Damper Position
0-100
60%
49
Economizer Damper Position for Exhaust Fan
to Turn Off (Non-Modulating Only)
Percent of Economizer
Position
0-100%
20%
50
APS Data
Open-Closed
Open-Closed
Open
51
Dirty Filter Switch
ON-OFF
ON-OFF
OFF
52
Dirty Filter Switch Data
Open-Closed
Open-Closed
Open
53
Cooling Mode Enable
ON-OFF
ON-OFF
ON
54
Heating Mode Enable
ON-OFF
ON-OFF
ON
55
Fan On Mode with the Sensor Option
ON-OFF
ON-OFF
ON
56
Space Setpoint Offset
°F
-5 to 5
0 degrees
57
Metric Operation
ON-OFF
ON-OFF
OFF
58
BAS Economizer
ON-OFF
ON-OFF
OFF
59
Year
Year
00-99
4
60
Month
Month
Number
1
61
Day of Month
Day
Number
1
62
Day of Week
Day
Number
1
63
Hour
Hour
0-23
0
64
Minute
Minutes
0-59
0
65
SAT (Supply Air Temp)
°F
-40 to 180
Read Only
Read Only
66
RAT (Return Air Temp)
°F
-40 to 180
Read Only
Read Only
67
OAT (Outside Air Temp)
°F
-40 to 180
Read Only
Read Only
68
ST (Space Temp)
°F
-40 to 180
Read Only
Read Only
69
OAH (Outside Air Hum)
%RH
0 to 100%
Read Only
Read Only
70
RAH (Return Air Hum)
%RH
0 to 100%
Read Only
Read Only
71
Occupied Input Enable
ON-OFF
ON-OFF
OFF
72
Alarm Array
These values represent the last 5 alarm codes in
memory. 72 is latest & 76 oldest.
Read Only
Read Only
73
Alarm Array
Read Only
Read Only
74
Alarm Array
Read Only
Read Only
75
Alarm Array
Read Only
Read Only
76
Alarm Array
Read Only
Read Only
77
CV/VAV Mode
Read Only Flag
CV=0 VAV=1
Read Only
Read Only
78
Hot Gas Reheat
ON-OFF
ON-OFF
OFF
79
Hot Gas Bypass
ON-OFF
ON-OFF
OFF
80
Compressors
Number
2 to 4
Factory Set
81
Heat Stages
Number
0 to 3
Factory Set
82
Duct Static Reading
Inches Water
0 to 5.0”
Read Only
83
Building Pressure Reading
Inches Water
0 to 5.0”
Read Only
84
Low Ambient Kit Installed
ON-OFF
ON-OFF
Factory Set
85
Building Static Pressure Sensor Enable
ON-OFF
ON-OFF
Factory Set
86
ERV Installed
ON-OFF
ON-OFF
Factory Set
87
ERV Unoccupied Fan
ON-OFF
ON-OFF
Factory Set
88
Duct Static Shutdown Setpoint
Inches Water
0 to 5.0”
4.5”
Table 5: Settable System Parameters (Continued)
Address
Function
Unit
Range
Default
Your Settings