255427-YTG-F-1006

10

Unitary Products Group

COOLING AIRFLOW DATA - MV MODELS

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

12B Air Handler

12D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1307

882

37.0

25.0

1366

869

38.7

24.6

A

B

1080

756

30.6

21.4

1097

717

31.1

20.3

B

B

1270

862

36.0

24.4

1312

856

37.2

24.2

A

A

943

689

26.7

19.5

957

646

27.1

18.3

B

A

1146

786

32.5

22.3

1167

761

33.0

21.5

A

C

1050

726

29.7

20.6

1051

703

29.8

19.9

C

B

870

632

24.6

17.9

863

580

24.4

16.4

B

C

771

594

21.8

16.8

739

520

20.9

14.7

D

B

931

668

26.4

18.9

927

629

26.2

17.8

C

A

693

565

19.6

16.0

658

495

18.6

14.0

D

A

851

624

24.1

17.7

830

567

23.5

16.1

C

C

655

567

18.5

16.1

594

488

16.8

13.8

D

C

16C Air Handler

20D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1920

1321

54.4

37.4

2209

1394

62.6

39.5

A

B

1699

1189

48.1

33.7

2022

1394

57.3

39.5

B

B

1884

1296

53.3

36.7

2178

1381

61.7

39.1

A

A

1558

1094

44.1

31.0

1798

1378

50.9

39.0

B

A

1714

1193

48.5

33.8

1965

1226

55.6

34.7

A

C

1451

1037

41.1

29.4

1843

1143

52.2

32.4

C

B

1403

1009

39.7

28.6

1596

1226

45.2

34.7

B

C

1288

947

36.5

26.8

1700

1066

48.1

30.2

D

B

1336

978

37.8

27.7

1608

1023

45.5

29.0

C

A

1214

888

34.4

25.1

1493

967

42.3

27.4

D

A

1239

915

35.1

25.9

1430

911

40.5

25.8

C

C

1098

839

31.1

23.8

1334

877

37.8

24.8

D

C

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. 
external static pressure is not recommended. 
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air 
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.

HEATING AIRFLOW DATA - MV MODELS

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

12B Air Handler

12D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1270

791

36.0

22.4

1312

762

37.2

21.6

A

A

943

714

26.7

20.2

957

668

27.1

18.9

B

A

931

643

26.4

18.2

927

591

26.2

16.7

C

A

693

567

19.6

16.1

658

488

18.6

13.8

D

A

16C Air Handler

20D Air Handler

JUMPER SETTINGS

CFM

m

3

/min

CFM

m

3

/min

High

Low

High

Low

High

Low

High

Low

COOL Tap

ADJ Tap*

1884

1217

53.3

34.5

2178

1217

61.7

34.5

A

A

1558

1065

44.1

30.2

1798

1036

50.9

29.3

B

A

1336

823

37.8

23.3

1608

748

45.5

21.2

C

A

1214

727

34.4

20.6

1493

551

42.3

15.6

D

A

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. 
external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air 
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.

Summary of Contents for MC18A2AH1

Page 1: ... 1 inch foil face fiber glass insulation providing a thermal insulation value of R 4 2 COILS Staggered rows of rifled copper tubes are mechanically expanded into enhanced surface aluminum fins to provide high heat transfer and long lasting quality The MC multi position coils may be used for upflow downflow and horizontal left or right applications Coil cabinets are insulated with 3 4 foil face ins...

Page 2: ...Depending on combination 16 1 2 14 19 32 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 MV12D 25 24 1 2 23 1 2 21 19 32 MV16C 25 21 20 18 3 32 MV20D 25 24 1 2 23 1 2 21 19 32 MC24B H 26 1 2 17 1 2 16 1 2 16 3 8 3 8 3 4 MC30B H 26 1 2 17 1 2 16 1 2 16 3 8 MC35B H 22 17 1 2 16 1 2 16 3 8 MC35C H 26 1 2 21 20 19 7 8 MC36B H 26 1 2 17 1 2 16 1 2 16 3 8 7 8 MC36C H 26 1 2 21 20 19 7 8 MC42B H 32 17 1 2 16 1 2 1...

Page 3: ...C60D H 1275 85 72 53 7 48 4 43 5 37 5 80 67 43 0 38 0 33 3 27 7 75 62 33 1 28 1 24 5 22 4 70 57 28 8 26 5 24 5 22 4 MC61D H 1450 85 72 91 7 78 4 68 1 52 3 80 67 73 4 61 5 52 0 38 6 75 62 57 3 45 6 38 4 31 2 70 57 49 2 43 0 38 4 31 2 MV16C MC42C H 1400 85 72 88 4 76 0 63 3 50 0 80 67 70 8 59 4 48 4 37 0 75 62 55 2 43 9 35 8 29 9 70 57 47 4 41 5 35 8 29 9 MC48C H 1650 85 72 100 5 86 4 72 0 56 8 80 6...

Page 4: ... Pump Sweat 3 40 2 14 2 14 x 17 5 1 x 0 866 3 8 Enhanced None 53 MC18A2AH1 2A MC18B3XH1 3 40 2 14 2 14 x 17 5 None 53 MC18B2AH1 2A MC24A3XH1 4 38 2 14 2 18 x 17 5 None 56 MC24A2AH1 2A MC24B3XH1 4 38 2 14 2 18 x 17 5 None 56 MC24B2AH1 2A MC30A3XH1 4 38 2 14 2 18 x 17 5 None 56 MC30A2AH1 2A MC30B3XH1 4 38 2 14 2 18 x 17 5 None 56 MC30B2AH1 2A MC35B3XH1 3 90 3 12 2 16 x 17 5 None 65 MC35C3XH1 None MC...

Page 5: ...7 6 45 1 60 1 3 3 4 4 6 6 8 8 13 2 17 6 4HK16502006 0 5 Heat D 14 4 19 2 49 2 65 5 3 6 4 8 7 2 9 6 14 4 19 2 MV20D 4HK 6501006 0 5 Heat D 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501506 0 5 Heat D 10 8 14 4 36 9 49 1 3 6 4 8 7 2 9 6 10 8 14 4 4HK16501806 0 5 Heat D 13 2 17 6 45 1 60 1 3 3 4 4 6 6 8 8 13 2 17 6 4HK16502006 0 5 Heat D 14 4 19 2 49 2 65 5 3 6 4 8 7 2 9 6 14 4 19 2 4HK16502506 0...

Page 6: ...8 133 75 125 150 1 1 0 1 30 KW 3 phase not approved for single source power supply 2 OCP Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse May be 0 no breaker or 1 with breaker ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY COPPER WIRE 208 230 3 60 Models Heat Kit Three Phase Heater Amps 240V Field Wiring Min Circuit Ampacity Max O C P 1 Amps Type 75 C Wire Size A...

Page 7: ...lay fuse KW MBH CONVERSIONS FOR 208 VOLT OPERATION MULTIPLY 240 VOLT TABULATED KW MBH BY 751 230 VOLT 240 VOLT 918 ELECTRICAL DATA COOLING UNIT ONLY 60 Hz MODEL Total Motor Amps Minimum Circuit Ampacity Max O C P 1 Amps Type Minimum Wire Size AWG 75 C 60 Hertz 60 Hertz 208V 230V 208V 230V MV12B 4 7 4 3 5 9 5 4 15 14 MV12D 4 7 4 3 5 9 5 4 15 14 MV16C 6 1 5 0 7 6 6 9 15 14 MV20D 7 8 7 0 9 7 8 8 15 1...

Page 8: ...If an electric heat accessory which is rated for greater than zero clearance to combustible surfaces is installed in these air handlers in the downflow operating positions on a combustible floor one of the follow ing combustible floor base accessories is required 1FB1817 1FB1821 or 1FB1824 FILTER RACK ACCESSORY 1 2 22 C 19 7 8 B D 1 1 2 3 1 2 A 22 21 1 2 All four sides 2 Max Thick Filter 3 4 1 2 3...

Page 9: ...10 47 64 PLENUM 12 1 2 FLOOR OPENING APPROX 1 2 CLEARANCE ALL AROUND FLOOR A AIR HANDLER WIDTH COMBUSTIBLE FLOOR BASE 1 1 APPROX 1 2 CLEARANCE ALL AROUND C FLOOR OPENING B PLENUM All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request Floor Base Model Used with Dimensions A B C D 1FB1817 MV12B 19 9 18 0 14 9 16 9 1FB1821 MV16C 23 4 ...

Page 10: ...tic pressure From 0 6 to 1 0 static pressure CFM is reduced by 2 per 0 1 increase in static Operation on duct systems with greater than 1 0 w c external static pressure is not recommended NOTE At some settings LOW COOL and or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners Consult the instructions for the electronic air ...

Page 11: ... AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM X L COM HUMIDISTAT THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM X L COM HUMIDISTAT MA SERIES Air Handler Control Wiring Typical A C with Electric Heat Applications CONTROL WIRING MV SERIES CONTROL WIRING MA Series Air Handler New UPG HP Systems Two Stage H P with York Guard VI Board Copel...

Page 12: ...to change without notice Printed in U S A 255427 YTG F 1006 Copyright by York International JCI 2006 All rights reserved Supersedes 255427 YTG E 0906 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Reviews: