York MaxE YK Operating And Maintenance Download Page 27

FORM 160.73-O2 (605)

27

YORK INTERNATIONAL

VACUUM DEHYDRATION

To obtain a suffi ciently dry system, the following in struc -
tions have been assembled to provide an ef fec tive meth od 
for evacuating and dehydrating a system in the fi eld. Al-
though there are several methods of de hy drat ing  a  sys tem, 
we are recommending the fol low ing, as it produces one of 
the best results, and af fords a means of obtaining accurate 
readings as to the ex tent of de hy dra tion.

The equipment required to follow this method of de-
 hy dra tion consists of a wet bulb indicator or vacuum 
gauge, a chart showing the relation between dew point 
tem per a ture and pressure in inches of mercury (vac u um), 
(See Table 2) and a vacuum pump capable of pumping 
a suit able vacuum on the system.

OPERATION

Dehydration of a refrigerant system can be obtained 
by this method because the water present in the sys tem 
reacts much as a refrigerant would. By pulling down 
the pressure in the system to a point where its sat u -
ra tion temperature is considerably below that of room 
tem per a ture,  heat  will  fl ow from the room through the 
walls of the system and vaporize the water, allowing 
a large percentage of it to be removed by the vacuum 
pump. The length of time necessary for the de hy dra tion 
of a system is dependent on the size or volume of the 
sys tem, the capacity and effi ciency of the vacuum pump, 
the room temperature and the quantity of water present 
in the system. By the use of the vacuum in di ca tor  as 
suggested, the test tube will be evacuated to the same 
pressure as the system, and the distilled water will be 
maintained at the same saturation tem per a ture  as  any 
free water in the system, and this tem per a ture  can  be 
observed on the thermometer.

If the system has been pressure tested and found to be 
tight prior to evacuation, then the saturation tem per a ture 
recordings should follow a curve similar to the typ i cal 
saturation curve shown as Fig. 12.

The temperature of the water in the test tube will drop as 
the pressure decreases, until the boiling point is reached, 
at which point the temperature will level off and remain 
at this level until all of the water in the shell is vaporized. 
When this fi nal vaporization has taken place the pressure 
and temperature will continue to drop until eventually 
a temperature of 35°F (1.6°C) or a pres sure of 5 mm 
Hg. is reached.

When this point is reached, practically all of the air has 
been evacuated from the system, but there is still a small 
amount of moisture left. In order to provide a medium 
for carrying this residual moisture to the vac u um  pump, 
nitrogen should be introduced into the system to bring it 
to atmospheric pressure and the in di ca tor  tem per a ture  will 
return to approximately am bi ent  temperature.  Close  off 
the system again, and start the second evac u a tion.

The relatively small amount of moisture left will be car-
 ried out through the vacuum pump and the tem per a ture 
or pressure shown by the indicator should drop uni-
 form ly until it reaches a temperature of 35°F (1.6°C) 
or a pres sure of 5 mm Hg.

When the vacuum indicator registers this temperature 
or pressure, it is a positive sign that the system is evac-
 u at ed and dehydrated to the recommended limit. If this 
level cannot be reached, it is evident that there is a leak 
somewhere in the system. Any leaks must be cor rect ed 
before the indicator can be pulled down to 35°F or 5 
mm Hg. in the primary evacuation.

During the primary pulldown, keep a careful watch on 
the wet bulb indicator temperature, and do not let it fall 
below 35°F (1.6°C). If the temperature is allowed to fall 
to 32°F (0°C), the water in the test tube will freeze, and 
the re sult will be a faulty temperature reading.

FIG. 12 – 

SATURATION CURVE

LD00474

6

Summary of Contents for MaxE YK

Page 1: ...CENTRIFUGAL LIQUID CHILLERS Supersedes 160 73 O2 1202 Form 160 73 O2 605 MODEL YK STYLE F R 134a COOLING ONLY WITH OPTIVIEWTM CONTROL CENTER FOR ELECTRO MECHANICAL STARTER SOLID STATE STARTER VARIABLE...

Page 2: ...materials This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are...

Page 3: ...NCLATURE YK CB CB P6 CM F MOTOR CODE 60 Hz 50 Hz CH CX 5CE 5CT CJ CY 5CF 5CU CK CZ 5CG 5CV CL CA 5CH 5CW CM CB 5CI 5CX CN DA 5CJ 5DA CP DB 5CK 5DB CR DC 5CL 5DC CS DD 5CM 5DD CT DE 5CN 5DE CU DF 5CO 5...

Page 4: ...ystem and Fundamentals of Operation 6 SECTION 2 System Operating Procedures 9 SECTION 3 System Components Description 15 SECTION 4 Operational Maintenance 21 SECTION 5 Troubleshooting 23 SECTION 6 Mai...

Page 5: ...M STARTER SOLID STATE STARTER 10 FIG 5 CHILLER STARTING SEQUENCE SHUTDOWN SEQUENCE VARIABLE SPEED DRIVE 11 FIG 6 LIQUID CHILLER LOG SHEETS 12 FIG 7 SYSTEM COMPONENTS 15 FIG 8 SCHEMATIC DRAWING YK COMP...

Page 6: ...n external SECTION 1 DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION 00116vip CONDENSER CONTROL CENTER COMPRESSOR MOTOR EVAPORATOR FIG 1 MODEL YK MAXETM CHILLER SYSTEM OPERATION DESCRIPTION SEE FI...

Page 7: ...ity for only a relatively small part of the time the unit is in operation CAPACITY CONTROL The major components of a chiller are selected for full load capacities therefore capacity must be controlled...

Page 8: ...FORM 160 73 O2 605 8 FIG 2 REFRIGERANT FLOW THRU CHILLER PREROTATION VANES See Detail A SUCTION EVAPORATOR ELIMINATOR OIL COOLER LD00924 FLOW CONTROL ORIFICE SUB COOLER CONDENSER DISCHARGE BAFFLE DIS...

Page 9: ...operated start the pump The Control Center will not allow the chiller to start unless chilled liquid ow is established through the unit A eld supplied chilled water ow switch is required If the chill...

Page 10: ...rt to circulate oil for a 50 second pre run to establish oil ow and adequate lubrication to all bearings gears and rotating surfaces within the compressor The high and low oil pressure transducers OP...

Page 11: ...current limit software function plus the 3 phase 100 solid state overload current limiter CM 2 on Electro Mechanical Starter applications or the Solid State Starter current Limit function will overrid...

Page 12: ...ing condenser water temperature may be as much as 25 F 14 C colder than the standby return chilled water temperature Cooling tower fan cycling will normally provide adequate control of the entering co...

Page 13: ...erant analysis NEED FOR MAINTENANCE OR SERVICE If the system is malfunctioning in any manner or the unit is stopped by one of the safety controls consult the Operation Analysis Chart Table 1 pages 23...

Page 14: ...water from the cooling tower condenser condenser pump and the chilled water system chilled water pump and coils Open the drains on the evaporator and condenser liquid heads to assure complete drainage...

Page 15: ...SECTION 3 SYSTEM COMPONENTS DESCRIPTION MOTOR EVAPORATOR COMPRESSOR SUCTION DUAL RELIEF VALVES SIGHT GLASS VARIABLE SPEED OIL PUMP CONTROL BOX REFRIGERANT CHARGING VALVE 00611vip FRONT VIEW FIG 7 SYS...

Page 16: ...YORK INTERNATIONAL FORM 160 73 O2 605 16 FIG 7 SYSTEM COMPONENTS CONT D 28778A DISCHARGE LINE OIL COOLER OIL RESERVOIR PUMP REAR VIEW System Components Description...

Page 17: ...d all interconnecting oil piping and passages There are main points within the motor compressor which must be supplied with forced lubri cation as follows 1 Compressor Drive Shaft Low Speed a Shaft se...

Page 18: ...YORK INTERNATIONAL FORM 160 73 O2 605 18 LOW SPEED GEAR REAR BEARING DOUBLE BELLOWS SHAFT SEAL FIG 8 SCHEMATIC DRAWING YK COMPRESSOR LUBRICATION SYSTEM LD08577 System Components Description...

Page 19: ...rcurrent transformers are furnished with all units HEAT EXCHANGERS Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion welded seams Heat exchanger tubes are inte...

Page 20: ...refrigerant Isolation of the refrigerant in this sys tem must be performed by a quali ed service technician OPTIONAL HOT GAS BYPASS Hot gas bypass is optional and is used to eliminate compressor surge...

Page 21: ...ducing the low pressure oil rich liquid to ow from the evaporator through the dehydrator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following pro cedure 1 Shut the...

Page 22: ...mp discharge connection to the oil charging valve A located on the remote oil reservoir cover plate See Fig 10 Do not tighten the connection at the charging valve until after the air is forced out by...

Page 23: ...ant into system greater than normal with high discharge Variable ori ce problem Remove obstruction temperature Temperature difference between leaving Evaporator tubes dirty or Clean evaporator tubes c...

Page 24: ...SYMPTOM REDUCED OIL PUMP CAPACITY Oil pump pumping capacity Excessive end clearance Inspect and replace worn parts pump Other worn pump parts Partially blocked oil supply Check oil inlet for blockage...

Page 25: ...ector can be used to detect any leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system through the charging...

Page 26: ...isconnect the vacuum pump leaving the vac uum indicator in place 6 Hold the vacuum obtained in Step 3 in the system for 8 hours the slightest rise in pressure indicates a leak or the presence of moist...

Page 27: ...d found to be tight prior to evacuation then the saturation temperature recordings should follow a curve similar to the typical saturation curve shown as Fig 12 The temperature of the water in the tes...

Page 28: ...iller model See Table 3 Charge the correct amount of refrigerant and record the level in the evaporator sight glass The refrigerant charge should always be checked and trimmed when the system is shut...

Page 29: ...the condenser or evaporator compressor while making any necessary repairs While the main disconnect switch and compressor motor starter are open meg the motor as follows 1 Using a megohm meter megger...

Page 30: ...ERNATIONAL FORM 160 73 O2 605 30 LD00476 FIG 14 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES Minimum Insulation Resistance vs Temperature per IEEE Std 43 Open Motors Maintenance TEMPERATURE F...

Page 31: ...ead pressure over a period of time accompanied by a steady rise in condensing temperature and noisy operation These symptoms may also be due to foul gas buildup Purging will remove the foul gas reveal...

Page 32: ...the ends of all tubes with water Do not use carbon tetrachloride for this purpose since its fumes give the same ame discoloration that the refrigerant does 3 With nitrogen or dry air blow out the tub...

Page 33: ...lines passages or dirty oil lters If the unit is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil lter element Examine the oil lter element for the presence of alu minum...

Page 34: ...re not supplied and bearings are designed for long life under standard conditions Frames 284T thru 587UZ are furnished with double shielded or open ball or roller bearings It is necessary to re lubric...

Page 35: ...user to provide for proper water treatment to provide for a longer and more economical life of the equipment The following recommendation should be followed in determining the condition of the water...

Page 36: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by YORK International Corporation 2005 ALL RIGHTS RESERVED Form 160 73 O2...

Reviews: