
FORM 160.73-O2 (605)
25
YORK INTERNATIONAL
SECTION 6
MAINTENANCE
RENEWAL PARTS
For any required Renewal Parts, refer to YORK Re new al
Parts Unit Components Manual 160.73-RP1.
CHECKING SYSTEM FOR LEAKS
Leak Testing During Operation
The refrigerant side of the system is carefully pres sure
tested and evacuated at the factory.
After the system has been charged, the system should
be carefully leak tested with a R-134a compatible leak
detector to be sure all joints are tight.
If any leaks are indicated, they must be repaired im-
me di ate ly. Usually, leaks can be stopped by tightening
fl are nuts or fl ange bolts. However, for any major re pair,
the re frig er ant charge must be removed. (See “Han dling
Re frig er ant for Dismantling and Repair”, page 29.)
CONDUCTING R-22 PRESSURE TEST
With the R-134a charge removed and all known leaks
re paired, the system should be charged with a small
amount of R-22 mixed with dry nitrogen so that a ha lide
torch or electronic leak detector can be used to detect
any leaks too small to be found by the soap test.
To test with R-22, proceed as follows:
1. With no pressure in the system, charge R-22 gas into
the system through the charging valve to a pres sure
of 2 PSIG (14 kPa).
2. Build up the system pressure with dry nitrogen to ap-
proximately 75 to 100 PSIG (517 to 690 kPa). To be
sure that the con cen tra tion of refrigerant has reached
all part of the sys tem, slightly open the oil charging
valve and test for the presence of re frig er ant with a
leak de tec tor.
3. Test around each joint and factory weld. It is im por -
tant that this test be thoroughly and carefully done,
spending as much time as necessary and using a good
leak detector.
4. To check for refrigerant leaks in the evaporator and
con dens er, open the vents in the evaporator and con-
dens er heads and test for the presence of refrigerant.
If no refrigerant is present, the tubes and tube sheets
may be considered tight. If refrigerant is detected at the
vents, the heads must be removed, the leak located (by
means of soap test or leak detector) and re paired.
EVACUATION AND DEHYDRATION OF UNIT
FIG. 11 –
EVACUATION OF CHILLER
27385A(D)
LD00949
6