background image

265485-XTG-B-1208

38

Johnson Controls Unitary Products

GUIDE SPECIFICATIONS

PREDATOR

® 

MagnaDRY™

DR 090

GENERAL

 

Units shall be manufactured by Unitary Products in an ISO 
9001 certified facility. YORK® Predator

®

 MagnaDRY™ units 

are convertible single packages with a common footprint cab-
inet and common roof curb. All units have two compressors 
with independent refrigeration circuits to provide 2 stages of 
cooling. The units were designed for light commercial appli-
cations and can be easily installed on a roof curb, slab, or 
frame. All Predator

®

 MagnaDRY™ units are self-contained 

and assembled on rigid full perimeter base rails allowing for 
3-way forklift access and overhead rigging. Every unit is com-
pletely charged, wired, piped, and tested at the factory to pro-
vide a quick and easy field installation. All units are 
convertible between side and down airflow. Independent 
economizer designs are used on side and down discharge 
applications, as well as all tonnage sizes. Predator

®

 Mag-

naDRY™ units are available in the following configurations: 
cooling only, cooling with electric heat, and cooling with gas 
heat. Electric heaters are available as factory-installed 
options or field-installed accessories.

DESCRIPTION

Units shall be factory assembled, single package, (Elec/Elec, 
Gas/Elec), designed for outdoor installation. Units shall have 
a minimum EER of 10.5 (3.08 CoP). They shall have built in 
field convertible duct connections for down discharge supply/
return or horizontal discharge supply/return and be available 
with factory installed options or field installed accessories. 
The units shall be factory wired, piped and charged with R-22 
refrigerant and factory tested prior to shipment. All unit wiring 
shall be both numbered and color coded. The cooling perfor-
mance shall be rated in accordance with DOE and ARI test 
procedures. Units shall be CSA certified to ANSI Z21.47 and 
UL 1995/CAN/CSA No. 236-M90 standards.

UNIT CABINET

 

Unit cabinet shall be constructed of galvanized steel with 
exterior surfaces coated with a non-chalking, powder paint 
finish, certified at 1000 hours salt spray test per ASTM-B117 
standards. Indoor blower sections shall be insulated with up 
to 1/2” (1.27 cm) thick insulation coated on the airside. Alumi-
num foil faced insulation shall be used in the unit’s compart-
ments and be fastened to prevent insulation from entering the 
air stream. Cabinet doors shall be hinged with tool-less 
access for easy servicing and maintenance. Full perimeter 
base rails shall be provided to assure reliable transit of equip-
ment, overhead rigging, fork truck access and proper sealing 
on roof curb applications. Disposable 2” filters shall be fur-
nished and be accessible through hinged access door. Fan 
performance measuring ports shall be provided on the out-
side of the cabinet to allow accurate air measurements of 

evaporator fan performance without removing panels or cre-
ating bypass of the coils. Condensate pan shall be slide out 
design, constructed of a non corrosive material, internally 
sloped and conforming to ASHRAE 62-B9 standards. Con-
densate connection shall be a minimum of ¾” I.D. female and 
be rigid mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

 

Fan shall be a belt drive assembly and include an adjustable 
pitch motor pulley. Job site selected brake horsepower shall 
not exceed the motors nameplate horsepower rating plus the 
service factor. Units shall be designed to operate within the 
service factor. Fan wheel shall be double inlet type with for-
ward curve blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant volume. Bearings shall be sealed 
and permanently lubricated for longer life and no mainte-
nance. Entire blower assembly and motor shall be slide out 
design. 

OUTDOOR (CONDENSER) FAN ASSEMBLY 

The outdoor fans shall be of the direct drive type, discharge 
air vertically, have aluminum blades riveted to corrosion 
resistant steel spider brackets and shall be dynamically bal-
anced for smooth operation. The outdoor fan motors shall 
have permanently lubricated bearings internally protected 
against overload conditions and staged independently. A 
cleaning window shall be provided on two sides of the units 
for coil cleaning.

REFRIGERANT COMPONENTS

Compressors: 

A.

Shall be fully hermetic type, direct drive, internally pro-
tected with internal high-pressure relief and over temper-
ature protection. The hermetic motor shall be suction gas 
cooled and have a voltage range of + or – 10% of the 
unit nameplate voltage.

B.

Shall have internal spring isolation and sound muffling to 
minimize vibration and noise, and be externally isolated 
on a dedicated, independent mounting.

Coils:

A.

Evaporator and condenser coils shall have aluminum 
plate fins mechanically bonded to seamless internally 
enhanced copper tubes with all joints brazed. Special 
Phenolic coating shall be available as a factory option. 

 B. Evaporator and condenser coils shall be of the direct 

expansion, draw-thru design.

Summary of Contents for MagnaDRY

Page 1: ... assem bled on rigid full perimeter base rails allowing for 3 way forklift access and overhead rigging Every unit is completely charged wired piped and tested at the factory to provide a quick and easy field installation All units are convertible between side and down airflow A single economizer design is used on side and down discharge applica tions as well as all tonnage sizes The Predator Magna...

Page 2: ... 25 TYPICAL DR090 COOLING UNIT WITH GAS HEAT WIRING DIAGRAM 35 26 TYPICAL DR090 COOLING UNIT WITH WITHOUT ELECTRIC HEAT WIRING DIAGRAM 36 27 TYPICAL DR090 REHEAT WIRING DIAGRAM 37 LIST OF TABLES Tbl Pg 1 PHYSICAL DATA 11 2 CAPACITY RATINGS IMPERIAL 12 3 CAPACITY RATINGS METRIC 12 4 DR090 COOLING CAPACITY IMPERIAL 13 5 DR090 COOLING CAPACITY METRIC 14 6 DR090 COOLING CAPACITY ALTERNATE REHEAT MODE ...

Page 3: ... Once the plate is removed the drain pan slides out through the rear of the unit All Predator units have a second model nameplate located inside the control access door This is to prevent deterioration of the nameplate through weathering Environmentally Aware For improved Indoor Air Quality foil faced insulation is used exclusively through out the units Balanced Heating The Predator offers Ultimat...

Page 4: ...unit control board will lock out the associated compressor On Board Diagnostics Each alarm will energize a trouble light on the thermostat if so equipped and flash an alarm code on the control board LED Each high and low pressure switch alarm as well as each freezestat alarm has its own flash code The control board saves the five most recent alarms in memory and these alarms can be reviewed at any...

Page 5: ...n and fully modulating dampers capable of introducing up to 100 outside air Also include 2 51 mm pleated filters Power Exhaust Downflow only This accessory installs in the unit with a down flow economizer Motorized Outdoor Air Damper The motorized out door air damper includes a slide in plug in damper assembly with an outdoor air hood and filters The out door air dampers open to the preset positio...

Page 6: ...alling a power exhaust You can order a 1RD0411 Barometric Relief for horizontal flow economizer Dual Enthalpy Control Accessory This kit contains the required components to convert a single enthalpy economizer to dual enthalpy Barometric Relief Damper Zero to 100 capacity barometric relief dampers for use with horizontal flow or field installed slab economizers Power Exhaust This accessory install...

Page 7: ...field supplied dehumidistat connected to RHTB 1 and RHTB 2 and there is not a call for cooling it energizes the hot gas relay HGR which energizes the 3 way valve SOL 3 the condenser coil valve SOL 2 and de energizes the reheat coil bleed valve SOL 1 The Y1 signal is passed to the unit control board UCB which engages circuit 1 resulting in circuit 1 reheat mode operation When the room thermostat ca...

Page 8: ...265485 XTG B 1208 8 Johnson Controls Unitary Products FIGURE 2 REHEAT CONTROL BOARD R Y1 Y2 G W1 OCC C W2 P4 P5 P6 P3 COM HGRR HGR HUM K1 K2 K4 K3 MODE SELECTION JUMPER DEHUMIDISTAT HARNESS CONNECTION ...

Page 9: ...265485 XTG B 1208 Johnson Controls Unitary Products 9 FIGURE 3 DR090 REHEAT CONTROLS ...

Page 10: ...No Options Installed Installation Options B Option 1 C Option 2 D Options 1 2 E Option 3 F Option 4 G Options 1 3 H Options 1 4 J Options 1 2 3 K Options 1 2 4 L Options 1 3 4 M Options 1 2 3 4 N Options 2 3 P Options 2 4 Q Options 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv...

Page 11: ...6 0 98 Reheat Coil Rows 2 Fins per 2 54 cm 1 in 13 Height in mm 28 710 Face Area ft 2 m2 7 8 0 72 Condenser Fan Quantity 2 Propeller Dia in mm ea 24 610 Motor HP kW ea 3 4 0 56 Airflow CFM m3 s ea 3700 1 75 Condenser Coil Coils 2 Rows each 1 Fins per inch 2 54 cm 1 in 20 Height in mm 44 1120 Face Area ft 2 m2 14 5 1 35 Refrigerant Charge System 1 lb kg 8 0 3 63 System 2 lbs kg 6 375 2 89 Compresso...

Page 12: ...180 144 30 60 3 4 1 Electric heaters rated at 415V See table 8 for kW ratings at 380V TABLE 3 CAPACITY RATINGS METRIC Model Cooling Capacity Sound Rating dB Nominal Electric Heat Capacity kW 1 Gas Heat Capacity Input kW Output kW Temp Rise C Gas Line Size mm OD 27 19 35 C Cooling Cap kW Options kW CoP2 090 26 4 DR 26 4 3 08 85 7 14 18 27 10 35 1 28 1 8 3 25 19 05 15 52 7 42 2 17 33 19 05 1 Electri...

Page 13: ...9 34 0 67 90 0 7 7 74 6 68 6 62 7 56 7 50 8 44 8 38 9 81 9 8 1 70 7 64 9 59 1 53 2 47 4 41 6 35 8 62 81 4 7 4 81 4 78 8 74 2 68 3 62 3 56 4 50 4 74 5 7 9 74 5 72 7 69 1 63 2 57 4 51 6 45 7 57 80 6 7 4 80 6 79 2 76 0 70 1 64 1 58 2 52 2 74 5 7 9 74 5 73 2 70 2 64 4 58 5 52 7 46 9 3000 72 103 5 8 0 65 4 58 7 52 1 45 4 38 7 94 6 8 5 62 6 56 1 49 5 43 0 36 5 67 93 3 7 7 81 2 74 6 67 9 61 3 54 6 47 9 4...

Page 14: ...16 8 15 1 13 4 11 7 10 0 19 26 7 7 21 9 20 1 18 4 16 6 14 9 13 1 11 4 24 8 1 20 7 19 0 17 3 15 6 13 9 12 2 10 5 17 24 7 4 23 8 23 1 21 8 20 0 18 3 16 5 14 8 22 7 9 21 8 21 3 20 2 18 5 16 8 15 1 13 4 14 24 7 4 23 6 23 2 22 3 20 5 18 8 17 1 15 3 22 7 9 21 8 21 5 20 6 18 9 17 2 15 4 13 7 1 42 22 30 8 0 19 2 17 2 15 3 13 3 11 4 28 8 5 18 3 16 4 14 5 12 6 10 7 19 27 7 7 23 8 21 9 19 9 18 0 16 0 14 0 12...

Page 15: ... 6 7 3 33 9 7 6 12 9 13 0 13 1 13 1 13 2 67 34 1 7 0 1 9 1 8 1 6 1 5 1 4 1 2 1 1 29 5 7 3 62 29 1 6 7 6 1 6 0 5 9 5 8 5 6 5 5 5 4 25 2 6 9 57 33 4 6 3 7 8 7 7 7 6 7 4 7 3 7 2 7 0 29 3 6 6 2625 72 40 0 7 3 35 0 7 7 67 35 3 7 0 5 4 5 0 4 6 4 2 3 9 3 5 3 1 30 5 7 3 2 4 2 2 2 0 1 8 1 7 1 5 1 3 62 30 2 6 7 17 5 17 1 16 7 16 3 15 9 15 5 15 1 26 0 7 0 5 8 5 6 5 4 5 2 5 1 4 9 4 7 57 34 6 6 3 21 8 21 7 21 ...

Page 16: ...6 11 2 10 7 Temperature of Air on Condenser Coil 35 C Temperature of Air on Condenser Coil 41 C 1 06 22 11 7 3 10 7 6 3 8 3 8 3 8 3 9 3 9 19 10 7 0 0 6 0 5 0 5 0 4 0 4 0 4 0 3 9 7 3 17 9 6 7 1 8 1 8 1 7 1 7 1 6 1 6 1 6 7 6 9 14 10 6 3 2 3 2 3 2 2 2 2 2 1 2 1 2 1 9 6 6 1 24 22 12 7 3 10 7 7 19 10 7 0 1 6 1 5 1 4 1 2 1 1 1 0 0 9 9 7 3 0 7 0 6 0 6 0 5 0 5 0 4 0 4 17 9 6 7 5 1 5 0 4 9 4 8 4 7 4 5 4 4 ...

Page 17: ... dry bulb wet bulb conditions 0 10 20 30 40 50 60 70 65 75 85 95 105 Outdoor Temperature F Moisture Removal Rate lbs Water Hour 75db 71wb 80db 71wb 75db 67wb 85db 71wb 80db 67wb 85db 67wb DR090 Moisture Removal 3000 cfm Normal Mode various indoor dry bulb wet bulb conditions 5 10 15 20 25 30 65 75 85 95 105 Outdoor Temperature F Moisture Removal Rate lbs Water Hour 75db 71wb 80db 71wb 75db 67wb 85...

Page 18: ...5 10 15 20 25 30 Outdoor Temperature C Moisture Removal Rate kg Water Hour 23 9db 21 7wb 26 7db 21 7wb 23 9db 19 4wb 29 4db 21 7wb 26 7db 19 4wb 29 4db 19 4wb 23 9 29 4 35 0 40 6 18 3 DR090 Moisture Removal 1 42 m3 s Normal Mode various indoor dry bulb wet bulb conditions 2 4 6 8 10 12 14 Outdoor Temperature C Moisture Removal Rate kg Water Hour 23 9db 21 7wb 26 7db 21 7wb 23 9db 19 4wb 29 4db 21 ...

Page 19: ... 0 30 30 30 30 2TP04520950 5 6 8 5 22 9 23 8 25 1 26 0 30 30 30 30 2TP04521850 11 3 17 2 26 8 28 0 29 6 30 7 30 30 30 35 2TP04522450 15 0 22 8 33 9 35 0 36 6 37 7 35 35 40 40 2TP04523650 21 3 32 4 45 8 47 0 48 6 49 7 50 50 50 50 415 7 3 58 0 1 1 4 3 5 2 2 2 None 22 9 23 8 25 1 26 0 30 30 30 30 2TP04520950 6 7 9 3 22 9 23 8 25 1 26 0 30 30 30 30 2TP04521850 13 5 18 8 28 9 30 0 31 6 32 7 30 30 35 35...

Page 20: ...t kW m3 s In kW Out kW m3 s In kW Out kW m3 s In kW Out kW 50 1 69 1 34 1 07 1 58 1 20 0 96 100 1 62 1 37 1 09 1 49 1 21 0 97 1 38 1 08 0 86 149 1 56 1 40 1 12 1 41 1 23 0 98 1 28 1 07 0 86 1 17 0 94 0 75 199 1 48 1 42 1 14 1 30 1 23 0 99 1 15 1 06 0 85 249 1 35 1 41 1 13 1 15 1 20 0 96 0 97 1 01 0 81 TABLE 11 BLOWER PERFORMANCE 7 1 2 TON OPTIONAL MOTOR SIDE DUCT IMPERIAL ESP iwg Turns Open 0 1 2 ...

Page 21: ...BHP CFM Watts BHP CFM Watts BHP 0 2 3727 1624 1 74 3532 1506 1 62 3325 1372 1 47 3107 1222 1 31 2877 1056 1 13 0 4 3554 1606 1 72 3370 1505 1 61 3175 1387 1 49 2968 1253 1 34 2750 1103 1 18 2521 937 1 01 0 6 3195 1493 1 60 3011 1391 1 49 2816 1273 1 37 2609 1140 1 22 2391 990 1 06 2161 823 0 88 0 8 2806 1372 1 47 2622 1270 1 36 2427 1153 1 24 2220 1019 1 09 1 0 2361 1232 1 32 2178 1131 1 21 TABLE ...

Page 22: ...57 1 46 0 6 3994 2117 2 27 3661 1881 2 02 3335 1652 1 77 3018 1431 1 54 2708 1218 1 31 0 8 3590 1969 2 11 3256 1733 1 86 2931 1504 1 61 2613 1283 1 38 2304 1070 1 15 1 0 3516 2053 2 20 3174 1809 1 94 2841 1573 1 69 2515 1344 1 44 2198 1123 1 21 1 2 3091 1880 2 02 2749 1636 1 76 2416 1400 1 50 2090 1171 1 26 1 4 2658 1692 1 82 2316 1448 1 55 1 6 2218 1486 1 59 TABLE 16 BLOWER PERFORMANCE 7 1 2 TON ...

Page 23: ... 0 29 0 34 4500 0 30 0 05 0 25 0 26 0 30 0 31 0 37 4700 0 33 0 05 0 28 0 29 0 33 0 34 0 40 4900 0 36 0 05 0 30 0 31 0 35 0 37 0 43 5100 0 39 0 06 0 33 0 34 0 38 0 40 0 46 5300 0 42 0 06 0 35 0 37 0 41 0 43 0 49 5500 0 45 0 06 0 38 0 40 0 44 0 46 0 53 5700 0 48 0 06 0 41 0 43 0 47 0 49 0 56 5900 0 52 0 07 0 44 0 46 0 50 0 53 0 59 6100 0 56 0 07 0 47 0 49 0 53 0 56 0 62 6300 0 60 0 07 0 50 0 53 0 56...

Page 24: ...4 62 1 64 6 74 5 77 0 91 9 2 21 82 0 12 4 69 5 72 0 82 0 84 4 99 3 2 30 89 4 12 4 74 5 77 0 86 9 91 9 106 8 2 40 96 9 14 9 82 0 84 4 94 4 99 3 114 2 2 49 104 3 14 9 86 9 91 9 101 8 106 8 121 7 2 59 111 8 14 9 94 4 99 3 109 3 114 2 131 6 2 68 119 2 14 9 101 8 106 8 116 7 121 7 139 1 2 77 129 1 17 4 109 3 114 2 124 2 131 6 146 5 2 87 139 1 17 4 116 7 121 7 131 6 139 1 154 0 2 96 149 0 17 4 124 2 131...

Page 25: ... 7 5 MINIMUM SUPPLY AIR m3 s 9 380 415 1 06 18 1 06 24 1 06 36 1 06 TABLE 21 INDOOR BLOWER SPECIFICATIONS MODEL MOTOR MOTOR SHEAVE BLOWER SHEAVE BELT HP RPM Eff SF Frame Datum Dia in Bore in Model Datum Dia in Bore in Model DR090 1 1 2 1725 80 1 15 56 3 4 4 4 7 8 1VM50 7 5 1 AK79 A55 2 1725 80 1 15 56 3 4 4 4 7 8 1VM50 6 5 1 AK69 A53 FIGURE 8 UNIT 4 POINT LOAD D A C B L E F T F R O N T TABLE 22 4 ...

Page 26: ...rating Weight lbs kg 090 1163 527 5 1148 520 7 FIGURE 11 UNIT DIMENSIONS See Detail B For Baserail Dimensions See Detail C 89 2260 27 685 59 1500 4 1 4 110 17 3 16 435 24 3 16 615 30 3 16 765 Power Entry Ø 2 1 2 65 11 1 2 290 30 11 32 770 Control Entry Ø 7 8 22 Power Entry Ø 2 1 2 65 LEFT FRONT 6 3 16 155 Convenience Power Outlet Entry Ø 7 8 22 NOTE xxx indicates dimensions given in millimeters Fo...

Page 27: ...rner wall 36 915 Bottom4 4 Units may be installed on combustible floors 0 0 5 1 4 1 3 5 B a s e P a n 1 7 1 3 1 6 4 5 0 V i e w o f W a l l A c r o s s f r o m C o i l G a s P i p e I n l e t DETAIL B 3 3 4 9 5 3 9 1 6 9 0 2 3 8 6 0 DETAIL C 5 3 8 1 3 5 DETAIL D FIGURE 12 PREDATOR ROOF CURB DIMENSIONS 5 0 1 2 1 2 8 5 3 0 7 6 0 2 0 5 1 0 8 0 5 8 2 0 5 0 6 1 5 0 2 T Y P 5 0 I N S U L A T E D D E C K...

Page 28: ...URE 14 BOTTOM DUCT OPENINGS FROM ABOVE 3 2 1 1 1 6 8 3 0 6 1 3 1 6 1 7 5 6 1 3 1 6 1 7 5 2 7 1 2 7 0 0 1 8 4 5 5 2 1 3 1 6 5 4 0 1 9 3 1 6 4 8 5 1 7 3 1 6 4 3 5 1 4 2 3 3 2 3 7 5 1 6 3 8 4 1 5 1 8 1 1 6 4 6 0 6 3 1 2 1 6 1 0 1 2 5 1 6 3 1 5 6 1 3 1 6 1 7 5 2 4 6 1 0 2 1 5 3 5 L E F T B o t t o m g a s s u p p l y e n t r y B o t t o m P o w e r C o n t r o l a n d C o n v e n i e n c e O u t l e t...

Page 29: ...MODEL DIMENSION A B C DR090 28 1 4 717 18 1 16 459 28 1 4 717 NOTE XXX indicates millimeters 18 1 4 465 5 5 32 130 31 11 16 805 2 31 32 75 18 1 4 465 Return Air Supply Air C A B 35 3 4 90 8 Outside Air Intake Hood 26 66 25 3 4 65 4 30 1 4 76 8 26 66 39 1 2 100 or 47 1 2 120 7 Relief Hood for Power Exhaust or Barometric Relief 88 1 4 224 2 58 1 4 148 ...

Page 30: ...241 1 Barometric relief must be ordered seperately and installed in duct work ERV or End Return Slab Economizer 50 tall cabinet 2EE047052242 2 Barometric relief or fresh air hood not included Must be ordered seperately 2EE04705424 Fresh Air Hood 2EE04705424 Fresh Air Damper 2EE04705424 Return Air Damper 2EE04705424 Barometric Relief Damper 2EE04705424 Barometric Relief Hood 2EE04705424 Fresh Air H...

Page 31: ... POWER EXHAUST 1EH0408 Barometric Relief Hood 1EH0408 Barometric Relief Damper 2PE047032XX Power Exhaust 2EE04705524 Fresh Air Hood 2EE04705524 Fresh Air Damper 2EE04705524 Return Air Damper Field Installed Duct Work 2EE04705X24 Slab Economizer 2PE047032XX Power Exhaust 1EH0409 Barometric Relief Damper 1EH0409 Barometric Relief Hood 1EH0409 Fresh Air Hood ...

Page 32: ...s Unitary Products FIGURE 21 SLAB ECONOMIZER END RETURN W POWER EXHAUST 2EE04705X24 Slab Economizer 1EH0409 Barometric Relief Hood 1EH0409 Barometric Relief Damper 1EH0409 Fresh Air Hood 2PE047032XX Power Exhaust Field Installed Duct Work ...

Page 33: ... programmable Thermostat 2ET0770010024 includes subbase 2 Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back position 3 TO REMOTE SENSOR 2ET04701324 IF USED DEHUMIDISTAT Dehumidistat closes on rise in humidity RC RH Y1 Y2 G W1 W2 C C W2 W1 G Y2 Y1 R OCC RCB REHEAT CONTROL BOARD HUM TERMINAL BLOCK RH 1 1 2 3 4 1 DEHUMIDIST...

Page 34: ...ONNECT COOLING UNIT WITH OR WITHOUT ELECTRIC HEAT TERMINAL BLOCK TB1 FIELD SUPPLIED DISCONNECT GROUND LUG THREE PHASE POWER SUPPLY FIGURE 24 FIELD WIRING DISCONNECT COOLING UNIT WITH GAS HEAT L1 T1 L2 T2 T3 L3 FIELD SUPPLIED DISCONNECT THREE PHASE POWER SUPPLY GROUND LUG CONTACTOR 1M ...

Page 35: ...265485 XTG B 1208 Johnson Controls Unitary Products 35 FIGURE 25 TYPICAL DR090 COOLING UNIT WITH GAS HEAT WIRING DIAGRAM ...

Page 36: ...265485 XTG B 1208 36 Johnson Controls Unitary Products FIGURE 26 TYPICAL DR090 COOLING UNIT WITH WITHOUT ELECTRIC HEAT WIRING DIAGRAM ...

Page 37: ...265485 XTG B 1208 Johnson Controls Unitary Products 37 FIGURE 27 TYPICAL DR090 REHEAT WIRING DIAGRAM ...

Page 38: ...l be hinged with tool less access for easy servicing and maintenance Full perimeter base rails shall be provided to assure reliable transit of equip ment overhead rigging fork truck access and proper sealing on roof curb applications Disposable 2 filters shall be fur nished and be accessible through hinged access door Fan performance measuring ports shall be provided on the out side of the cabinet...

Page 39: ...f the in shot type constructed of aluminum coated steel All gas piping shall enter the unit cabinet at a single location through either the side or bottom without any field modifica tions An integrated control board shall provide timed control of evaporator fan functioning and burner ignition Heating section shall be provided with the following minimum protec tion A Primary and auxiliary high temp...

Page 40: ... with optional indoor blower motors that provide higher static output and or higher airflow CONVENIENCE OUTLET POWERED NON POW ERED Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors ELECTRIC HEAT Electric Heaters range from 7 kW to 27 kW and are available in all the voltage options of the base unit PHASE MONITOR Designed to preven...

Reviews: