265485-XTG-B-1208
14
Johnson Controls Unitary Products
1.
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW
of the supply air blower motor.
2.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
TABLE 5: DR090 COOLING CAPACITY - METRIC
Air On
Evap. Coil
Temperature of Air on Condenser Coil 24°C
Temperature of Air on Condenser Coil 29°C
m
3
/s
WB
(°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°F)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
1.06
22
34
6.4
18.0
16.4
14.9
13.4
11.8
-
-
31
7.1
17.0
15.4
13.9
12.4
10.8
-
-
19
30
6.2
21.8
20.2
18.7
17.2
15.6
14.1
12.6
28
6.9
20.8
19.3
17.8
16.2
14.7
13.2
11.6
17
27
6.0
25.6
24.0
22.5
21.0
19.4
17.9
16.4
25
6.7
24.3
22.8
21.2
19.7
18.2
16.6
15.1
14
25
6.0
25.5
25.2
23.7
22.2
20.6
19.1
17.6
24
6.7
24.1
23.6
22.1
20.5
19.0
17.5
15.9
1.24
22
35
6.6
19.5
17.8
16.1
14.3
12.6
-
-
32
7.2
18.5
16.8
15.1
13.3
11.6
-
-
19
31
6.5
23.6
21.8
20.1
18.4
16.6
14.9
13.2
29
7.1
22.7
21.0
19.2
17.5
15.8
14.0
12.3
17
27
6.2
26.9
26.2
24.2
22.5
20.7
19.0
17.3
26
6.8
25.4
24.6
23.0
21.2
19.5
17.8
16.0
14
26
6.2
26.2
26.1
25.5
23.8
22.0
20.3
18.6
25
6.8
24.9
24.7
23.9
22.2
20.4
18.7
16.9
1.42
22
36
6.8
21.1
19.1
17.2
15.3
13.3
-
-
33
7.4
20.1
18.2
16.2
14.3
12.3
-
-
19
32
6.7
25.4
23.5
21.5
19.6
17.7
15.7
13.8
29
7.2
24.6
22.7
20.7
18.8
16.8
14.9
12.9
17
28
6.5
28.3
28.3
25.9
24.0
22.1
20.1
18.2
26
7.0
26.5
26.5
24.8
22.8
20.9
18.9
17.0
14
27
6.5
27.0
27.0
27.3
25.4
23.4
21.5
19.6
26
7.0
25.7
25.7
25.7
23.8
21.8
19.9
18.0
1.59
22
37
6.8
22.6
20.5
18.4
16.3
14.2
-
-
34
7.4
21.5
19.4
17.3
15.2
13.0
-
-
19
33
6.7
27.2
25.1
23.0
20.9
18.8
16.7
14.6
30
7.2
26.3
24.2
22.0
19.9
17.8
15.7
13.6
17
29
6.5
29.2
29.2
28.0
25.9
23.8
21.7
19.6
27
7.0
27.1
27.1
26.2
24.1
22.0
19.9
17.8
14
28
6.5
27.8
27.8
28.0
25.9
23.8
21.7
19.6
26
7.0
26.3
26.3
26.3
24.2
22.1
20.0
17.9
1.77
22
38
6.9
24.1
21.8
19.6
17.3
15.0
-
-
34
7.5
22.8
20.6
18.3
16.0
13.8
-
-
19
34
6.7
29.1
26.8
24.5
22.2
20.0
17.7
15.4
31
7.3
27.9
25.6
23.4
21.1
18.8
16.5
14.3
17
30
6.5
30.0
30.0
30.0
27.8
25.5
23.2
21.0
28
7.0
27.7
27.7
27.7
25.4
23.1
20.9
18.6
14
29
6.5
28.7
28.7
28.7
26.4
24.1
21.8
19.6
27
7.0
26.9
26.9
26.9
24.6
22.3
20.1
17.8
Temperature of Air on Condenser Coil 35°C
Temperature of Air on Condenser Coil 41°C
1.06
22
28
7.8
16.0
14.4
12.9
11.4
9.8
-
-
26
8.3
15.3
13.8
12.3
10.8
9.3
-
-
19
25
7.6
19.9
18.4
16.8
15.3
13.8
12.2
10.7
23
8.1
18.9
17.4
15.9
14.3
12.8
11.3
9.8
17
23
7.4
23.0
21.5
19.9
18.4
16.9
15.3
13.8
21
7.8
21.1
20.0
18.5
17.0
15.5
14.0
12.5
14
23
7.4
22.8
22.0
20.4
18.9
17.4
15.8
14.3
21
7.8
21.1
20.3
18.8
17.3
15.8
14.3
12.8
1.24
22
29
7.9
17.6
15.8
14.1
12.3
10.6
-
-
27
8.4
16.8
15.1
13.4
11.7
10.0
-
-
19
26
7.7
21.9
20.1
18.4
16.6
14.9
13.1
11.4
24
8.1
20.7
19.0
17.3
15.6
13.9
12.2
10.5
17
24
7.4
23.8
23.1
21.8
20.0
18.3
16.5
14.8
22
7.9
21.8
21.3
20.2
18.5
16.8
15.1
13.4
14
24
7.4
23.6
23.2
22.3
20.5
18.8
17.1
15.3
22
7.9
21.8
21.5
20.6
18.9
17.2
15.4
13.7
1.42
22
30
8.0
19.2
17.2
15.3
13.3
11.4
-
-
28
8.5
18.3
16.4
14.5
12.6
10.7
-
-
19
27
7.7
23.8
21.9
19.9
18.0
16.0
14.0
12.1
25
8.2
22.6
20.7
18.8
16.9
14.9
13.0
11.1
17
25
7.5
24.7
24.7
23.6
21.6
19.7
17.7
15.8
23
8.0
22.6
22.6
21.9
20.0
18.1
16.2
14.3
14
24
7.5
24.5
24.5
24.1
22.2
20.2
18.3
16.3
23
8.0
22.6
22.6
22.3
20.4
18.5
16.6
14.7
1.59
22
31
8.0
20.4
18.3
16.1
14.0
11.9
-
-
28
8.6
19.4
17.3
15.3
13.3
11.2
-
-
19
28
7.8
25.3
23.2
21.1
18.9
16.8
14.7
12.6
25
8.3
23.6
21.8
19.8
17.7
15.7
13.6
11.6
17
25
7.6
25.0
25.0
24.4
22.3
20.2
18.1
16.0
23
8.1
22.7
22.7
22.4
20.4
18.3
16.3
14.2
14
25
7.5
24.8
24.8
24.6
22.5
20.4
18.3
16.2
23
8.1
22.7
22.7
22.6
20.5
18.5
16.5
14.4
1.77
22
31
8.1
21.6
19.3
17.0
14.8
12.5
-
-
28
8.6
20.4
18.3
16.1
13.9
11.7
-
-
19
28
7.8
26.8
24.5
22.2
19.9
17.7
15.4
13.1
25
8.4
24.5
23.0
20.8
18.6
16.4
14.2
12.1
17
25
7.6
25.3
25.3
25.3
23.0
20.8
18.5
16.2
23
8.1
22.9
22.9
22.9
20.7
18.5
16.3
14.1
14
25
7.6
25.1
25.1
25.1
22.8
20.5
18.3
16.0
23
8.1
22.9
22.9
22.9
20.7
18.5
16.3
14.2
Temperature of Air on Condenser Coil 46°C
Temperature of Air on Condenser Coil 52°C
1.06
22
24
8.8
14.6
13.1
11.6
10.1
8.7
-
-
21
9.3
13.9
12.4
11.0
9.5
8.1
-
-
19
21
8.5
17.8
16.3
14.9
13.4
11.9
10.4
9.0
19
9.0
16.8
15.3
13.9
12.4
11.0
9.6
8.1
17
19
8.3
19.2
18.6
17.1
15.6
14.2
12.7
11.2
17
8.8
17.3
17.2
15.7
14.3
12.8
11.4
9.9
14
19
8.3
19.4
18.7
17.3
15.8
14.3
12.8
11.4
18
8.8
17.7
17.1
15.7
14.2
12.8
11.3
9.9
1.24
22
24
8.9
16.0
14.4
12.7
11.0
9.4
-
-
22
9.4
15.3
13.6
12.0
10.4
8.7
-
-
19
22
8.6
19.6
17.9
16.3
14.6
12.9
11.2
9.6
19
9.1
18.5
16.8
15.2
13.6
11.9
10.3
8.6
17
20
8.4
19.8
19.5
18.7
17.0
15.4
13.7
12.0
18
8.9
17.8
17.7
17.2
15.6
13.9
12.3
10.6
14
20
8.4
20.0
19.7
18.9
17.2
15.5
13.8
12.2
18
8.9
18.3
17.9
17.2
15.5
13.9
12.2
10.6
1.42
22
25
9.0
17.5
15.7
13.8
11.9
10.0
-
-
22
9.5
16.7
14.9
13.0
11.2
9.4
-
-
19
22
8.7
21.4
19.5
17.6
15.8
13.9
12.0
10.1
20
9.2
19.7
18.3
16.5
14.7
12.8
11.0
9.2
17
20
8.5
20.4
20.4
20.3
18.4
16.6
14.7
12.8
18
9.0
18.3
18.3
18.3
16.9
15.0
13.2
11.3
14
21
8.5
20.7
20.7
20.5
18.6
16.7
14.9
13.0
19
9.0
18.8
18.8
18.6
16.8
15.0
13.1
11.3
1.59
22
25
9.1
18.4
16.4
14.5
12.5
10.5
-
-
22
9.7
17.4
15.5
13.6
11.7
9.8
-
-
19
22
8.8
21.8
20.5
18.5
16.5
14.5
12.6
10.6
20
9.3
19.6
19.1
17.2
15.3
13.4
11.5
9.6
17
20
8.6
20.4
20.4
20.4
18.4
16.4
14.4
12.5
18
9.1
18.1
18.1
18.1
16.4
14.5
12.6
10.7
14
21
8.6
20.7
20.7
20.6
18.6
16.6
14.6
12.7
19
9.1
18.6
18.6
18.6
16.6
14.7
12.8
10.9
1.77
22
25
9.2
19.3
17.2
15.1
13.0
11.0
-
-
22
9.8
18.2
16.2
14.2
12.2
10.2
-
-
19
22
8.9
22.3
21.5
19.4
17.3
15.2
13.1
11.0
19
9.4
19.4
19.4
17.9
16.0
14.0
12.0
10.0
17
20
8.7
20.4
20.4
20.4
18.3
16.3
14.2
12.1
18
9.2
18.0
18.0
18.0
16.0
14.0
12.0
10.0
14
21
8.7
20.7
20.7
20.7
18.6
16.5
14.4
12.3
18
9.2
18.5
18.5
18.5
16.5
14.5
12.5
10.5