548267-YIM-C-0211

Unitary Products Group

13

Figure 12: Switch Installation

Pre-start Procedure

Before starting air conditioner, make sure of the following:

1.

The unit is properly located and level.

2.

The ductwork is properly sized, insulated, weather proofed 
and correctly spaced from combustible materials.

3.

Air is free to flow to and from outdoor coil.

4.

All wiring is correct, tight and according to the wiring 
diagrams.

5.

The unit is properly grounded electrically.

6.

The condensate drain is connected and directed away from 
the unit and structure.

7.

The outdoor fan and indoor blower wheel will turn freely.

8.

The indoor blower is factory wired to provide the correct 
speed.

System Startup, Check-out

1.

Insure that all access doors are in position. The wall 
thermostat system switch should be in the OFF position, 
the fan switch in the AUTO position and the emergency 
heat switch in the NORM position.

2.

The electrical power supply to the heat pump should be on 
for 12 hours and the compressor crankcase heater (if 
provided) is working.

3.

Set the wall thermostat fan switch to ON. The outdoor 
blower should run.

4.

Set wall thermostat fan switch to AUTO. The indoor blower 
should not run.

5.

Set the wall thermostat system switch to COOL and the 
temperature selection lever below the room temperature. 
The heat pump should be running in the cooling mode.

6.

Set the wall thermostat system switch to the HEAT 
position. The heat pump should stop.

7.

Raise the wall thermostat temperature selection lever to a 
setting above the room temperature. The heat pump 
should now run in the heating mode.

8.

To check the emergency heat operation, set the wall 
thermostat system switch to EMERGENCY HEAT. Raise 
the wall thermostat temperature selection lever high 
enough to close the second stage of the thermostat, if it is 
not already closed. The indoor blower will turn on when the 
heating elements stage on. If accessory heaters are not 
installed, the blower will not run.

9.

Set the wall thermostat to the seasonal mode of operation 
(heat or cool), adjust the temperature selection lever to the 
desired setting. Record the following information for your 
service records after the heat pump has run for 20 minutes:
• Operating Mode   ____________________________
• Discharge Pressure   ________________________
• Suction Pressure   __________________________
• Suction Line Temp. at Compressor   ____________
• Indoor Dry Bulb Temperature   _________________
• Indoor Wet Bulb Temperature   _________________
• Outdoor Dry Bulb Temperature   ________________
• Outdoor Wet Bulb Temperature   ________________
• Voltage at Contactor   _________________________
• Current at Contactor   _________________________
• Model Number   _____________________________
• Serial Number   _____________________________
• Owner   ___________________________________
• Date  _____________________________________

10. Reinstall all panels on the heat pump.

11. Check the heat pump system for tubing and sheet metal 

rattles.

12. Instruct the owner on the operation and maintenance of 

this heat pump system.

13. Give the Customer Envelope to the owner and explain why 

the registration card should be filled out and returned.

Other Features Incorporated In The Control

Anti-Short Cycle time Delay

Five minute duration, activated each time the indoor thermostat 
opens and each time the system is turned on. This delay may 
be reduced by a ratio of 256:1 by shorting the “TEST" posts.

Safety Lock-Out

This device opens the circuit to the compressor contactor in 
response to  High Pressure Limit switch opening. The 
compressor will remain off, even though the limit switches close 
and will start up only when the Lock-out is reset.

The Lock-out also lights the Emergency Heat Indicator. To 
reset the Lock-out momentarily turn the thermostat to “OFF" 
then back to its original position. The unit will start up after the 5 
minute delay, mentioned above. 

Cooling

Thermostat

Heating

Thermostat

To Furnace

Control Circuit

To Air Conditioner

Control Circuit

Double Pole

Double Throw Switch

Summary of Contents for LATITUDE Series

Page 1: ...ostat Wiring 12 12 Switch Installation 13 13 Defrost Operation Curves 14 General YORK Model UQ units are factory assembled heat pump designed to be installed along side the home or building Field installed electric heater accessories are available to provide supplemental electric heat The units are completely assembled on rigid base rails All piping refrigerant charge and electrical wiring is fact...

Page 2: ...nce with the installation instructions and any applicable local state and national codes including but not limited to building electrical and mechanical codes Before performing service or maintenance operations on unit turn off main power switch to unit Electrical shock could cause personal injury Improper installation adjustment alteration service or maintenance can cause injury or property damag...

Page 3: ...ized procedures identified by the Air Conditioning Contractors of America Figure 1 Component Location Direct Drive Condenser Fan Motor High Efficiency Enhanced Copper Tube Aluminum Fin High Efficiency Compressor Rigidly Mounted Decorative Protective Coil Guard High Efficiency Enhanced Copper Tube Aluminum Fin Outdoor Coil Blower Service Access Panel X13 or PSC Direct Drive Blower Motor Refrigerant...

Page 4: ...ion See Figure 2 7 Wind direction The hot condenser air must be discharged up and away from the home or building and if possible in a direction with the prevailing wind 8 Relationship between building sun and unit If practical place the air conditioner in an area where the unit and the ducts will be shaded from the afternoon sun when the heat load is the greatest 9 Defrost and Water Drainage Water...

Page 5: ...nit operation Figure 3 Unit 4 Point Load Weight C X Y CG D A B Right Left Front Rear Size Tons Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D 024 2 0 328 325 21 75 14 75 67 86 96 030 2 5 343 340 21 75 14 78 70 90 101 036 3 0 348 345 23 5 15 79 83 94 90 042 3 5 375 372 23 5 15 100 69 83 120 048 4 0 388 385 28 75 16 25 95 95 98 98 060 5 0 395 392 28 75 16 25 97...

Page 6: ...D CONDENSATE DRAIN 3 4 NPT H Table 2 Unit Dimensions Size Tons Dimensions A B C D E F G H 024 2 0 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 030 2 5 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 036 3 0 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 042 3 5 32 13 16 34 15 16 57 9 16 11 9 16 10 5 16 28 7 8 14 2 3 4 048 4 0 32 13 16 34 15 16 57 9 16 11 9 16 10 5 16 28...

Page 7: ...installed first The return air grille box and filter should be located and installed in the out rigger areas of the home Keep in mind the closer to the cooling unit the better The return ducting connects to the bottom of the return air box so it will be necessary to provide an opening beneath the box See Figure 5 Figure 5 Return Air Box and Grille After determining the location of the return air o...

Page 8: ...llar in the raw end of the duct and tape securely in place 4 Make sure the duct is not stretched tight and does not have kinks from excessive length after installation 5 Attach the duct end with the stub collar to the air conditioner return air flange with screws and duct tape sealing the duct cover securely Wye Insulation It is necessary to field fabricate and install an insulation jacket for the...

Page 9: ...ister This will help to eliminate the transmission of sound into the home To locate the center of the duct first cut a 6 hole in the fiberboard below the duct at the desired location After locating the duct center increase the hole in the fiber board to approximately the size of the duct connector Figure 8 Duct Connector With Damper Figure 9 Duct Connector No Damper May use duct connector without ...

Page 10: ... air ducts passing through unconditioned spaces of the building must be insulated and covered with a vapor barrier Following this practice will prevent thermal losses and condensate formation on the ducts Installing Drain Tube And Connection A drain tube a barbed elbow plastic fitting and a plastic hose clamp are provided in the small parts package packed in the blower chute 1 To insure proper con...

Page 11: ...ept a single circuit of supply power If an auxiliary heater is installed dual circuiting to the unit can be used When installing a 14 3 KW heater this method will avoid the use of large wiring To provide single circuiting an optional jumper bar can be used to electrically connect the circuit breakers provided with the heater kit If auxiliary electric heaters are not installed refer to data sheet f...

Page 12: ...ver locate it in a room that is warmer or cooler than the rest of the home such as a kitchen or hallway 8 The living or dining room is normally a good location provided there is no cooking range or refrigerator on the opposite side of wall Make final check of complete electrical system for correct wiring Check for any possible loose connections Defrost Board Run Capacitor Start Relay Optional Tran...

Page 13: ...If accessory heaters are not installed the blower will not run 9 Set the wall thermostat to the seasonal mode of operation heat or cool adjust the temperature selection lever to the desired setting Record the following information for your service records after the heat pump has run for 20 minutes Operating Mode ____________________________ Discharge Pressure ________________________ Suction Press...

Page 14: ... forced defrost feature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil temperature is above 40 F All defrost timing occurs only while the compressor is on During the defrost mode the defrost control will provide a 24 volt signal from terminal W1 66 to the fan control terminal W1 This signal will energize electric heat stage 1 if the unit...

Page 15: ... 9 47 8 51 1 60 60 60 60 2PH08520706 4 9 6 5 1 23 5 27 1 55 6 60 1 60 70 60 70 2PH08521006 7 2 9 6 1 34 5 39 8 69 4 76 70 80 70 80 2PH08521506 10 8 14 3 1 51 7 59 7 90 9 100 9 100 110 100 110 208 230 3 60 10 4 73 0 16 3 1 4 4 1 None 18 5 25 25 042 3 5 208 230 1 60 21 8 105 0 34 0 2 2 7 6 None 37 1 50 50 2PH08520506 3 6 4 8 1 17 2 19 9 58 6 61 9 70 70 70 70 2PH08520706 4 9 6 5 1 23 5 27 1 66 4 70 9...

Page 16: ...roll Scroll Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 1 11 28 11 28 16 16 20 Rows 1 2 2 2 2 2 Fins per inch 20 15 20 15 15 20 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined Intertwined Refrigerant Control TXV TXV TXV TXV TXV TXV EVAPORATOR COIL DATA Face area Sq Ft 4 67 4 67 4 67 5 44 5 44 5 44 Row...

Page 17: ...h 2227 978 1086 1976 889 1129 1677 757 1151 048 4 0 Low 1260 275 807 1096 313 915 910 336 992 804 355 1057 774 290 979 Low Medium 1471 375 870 1338 415 968 1118 455 1079 963 474 1110 788 323 1016 Medium 1546 394 865 1391 439 975 1187 479 1080 1062 501 1088 892 347 1034 Medium High 1597 434 893 1460 476 989 1277 518 995 1079 515 1050 1529 669 1132 High 2227 978 1086 1976 889 1129 1677 757 1151 1827...

Page 18: ...0 20 0 23 1200 0 21 0 21 0 21 0 22 0 25 1300 0 23 0 23 0 23 0 24 0 27 1400 0 25 0 25 0 25 0 26 0 29 1500 0 27 0 27 0 27 0 28 0 31 1600 0 29 0 29 0 29 0 30 0 33 1700 0 31 0 31 0 31 0 32 0 35 1800 0 33 0 33 0 33 0 34 0 37 1900 0 35 0 35 0 35 0 36 0 39 2000 0 37 0 37 0 37 0 38 0 41 2100 0 39 0 39 0 39 0 40 0 43 2200 0 41 0 41 0 41 0 42 0 45 060 5 0 UQ 500 0 09 0 09 0 09 0 10 0 12 600 0 1 0 10 0 10 0 ...

Page 19: ...eater kW 5 0 6 5 10 0 15 0 024 2 0 208 230 1 60 800 800 800 750 030 2 5 208 230 1 60 800 800 800 750 036 3 0 208 230 1 60 800 800 800 750 042 3 5 208 230 1 60 1300 1300 1270 1270 048 4 0 208 230 1 60 1300 1300 1270 1270 060 5 0 208 230 1 60 1300 1300 1270 1270 Table 10 Indoor Blower Specifications Size Tons Motor HP RPM Eff SF Frame 024 2 0 1 2 1100 0 8 1 0 48 030 2 5 1 2 1100 0 8 1 0 48 036 3 0 1...

Page 20: ...548267 YIM C 0211 20 Unitary Products Group Typical Wiring Diagrams UQ024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram ...

Page 21: ...548267 YIM C 0211 Unitary Products Group 21 UQ036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram ...

Page 22: ...ted in U S A 548267 YIM C 0211 Copyright 2011 by Unitary Products Group All rights reserved Supersedes 548267 YIM B 0910 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 UQ060 Typical Heat Pump 460 3 60 volt Wiring Diagram ...

Reviews: