background image

161036-YIM-E-1008

4

Johnson Controls Unitary Products

3.

Proximity to the clothes dryer vent – The clothes dryer vent 
should not be located upwind from the unit.

4.

Ability to service – Side access panels of the unit should 
not be closer than 24 inches to a structure so blower and 
controls may be serviced.

5.

Sound transmission – Locate the unit away from bedroom 
windows or other rooms where sound may be objectionable.

6.

 Air Circulation – The outside coil sides should not be 
closer than 24 inches to a structure that will restrict air flow 
through the coil. The air discharge of the unit requires a 60-
inch clearance between the top of the unit and any 
obstruction.See Figure 2.

7.

 Wind direction – The hot condenser air must be discharged 
up and away from the home or building, and if possible in a 
direction with the prevailing wind.

8.

 Relationship between building, sun and unit – If practical, 
place the air conditioner in an area where the unit and the 
ducts will be shaded from the afternoon sun (when the heat 
load is the greatest).

9.

Defrost and Water Drainage - Water will run off the outdoor 
coil when the heat pump defrosts during the heating 
season. This water will run through the drain holes of the 
heat pump base pan onto the ground below. A slight grade 
away from the unit will improve drainage.

10. Average Winter Snow Depth - The heat pump must be 

installed above the average snow depth to allow the 
outdoor coil to drain properly. 
Cinder blocks, if permitted by local codes, or a metal frame 
may be used to support the unit above the snow. Insure 
that the support does not obstruct drainage holes in the 
base pan of the unit. Metal frame legs must be supported 

by concrete pads. The heat pump must set level and 
securely upon the support.

NOTE: 

If installing on blocks, the middle rail must be supported.

Figure 2: Air Discharge Clearance

Site Preparation

After the site has been selected and prepared, using criteria 
mentioned above, install the air conditioner support pad at the 
selected site.

NOTE: 

This unit must be installed and operated on a level 
surface. Failure to do so will result in condensate 
drainage problems.

Clearances

All units require certain clearances for proper operation and 
service. Refer to Table 3 for the clearances required for 
construction, servicing and proper unit operation.

Figure 3: Unit 4 Point Load Weight

60”

C

CG 

D

A

B

Right 

Left

Front 

Rear 

Size

(Tons)

Weight (lbs.)

Center of Gravity

4 Point Load Location (lbs.)

Shipping Operating

X

Y

A

B

C

D

024

(2.0)

345

342

21.75

14

79

71

91

101

030

(2.5)

350

347

21.75

14

80

72

92

103

036

(3.0)

353

350

23.5

15

80

84

95

91

042

(3.5)

377

372

23.5

15

100

69

83

120

048

(4.0)

387

382

28.75

16.25

94

94

97

97

060

(5.0)

395

390

28.75

16.25

96

96

99

99

Summary of Contents for LATITUDE JP024-060

Page 1: ...tion 11 13 Defrost Operation Curves 12 14 Demand Defrost Curve Selection Jumper 12 General YORK Model JP units are factory assembled heat pump designed to be installed along side the home or building Field installed electric heater accessories are available to provide supplemental electric heat The units are completely assembled on rigid base rails All piping refrigerant charge and electrical wiri...

Page 2: ...NSI NFPS No 70 or Canadian Electrical Code Part 1 C22 1 latest editions 2 Local plumbing and waste water codes and other applicable local codes Refer to Table 6 for unit physical data and to Table 5 for electrical data This product must be installed in strict compliance with the installation instructions and any applicable local state and national codes including but not limited to building electr...

Page 3: ...nce and routing of electrical service to connect the unit Try to select a site for the unit that it is as close as possible to the proposed return grille location Unit may be positioned to draw air from underneath structure Direct Drive Condenser Fan Motor Decorative Protective Coil Guard Heavy Gauge Base Rails Control Box Service Access Panel Refrigerant Connections X13 Direct Drive Blower Motor ...

Page 4: ...grade away from the unit will improve drainage 10 Average Winter Snow Depth The heat pump must be installed above the average snow depth to allow the outdoor coil to drain properly Cinder blocks if permitted by local codes or a metal frame may be used to support the unit above the snow Insure that the support does not obstruct drainage holes in the base pan of the unit Metal frame legs must be sup...

Page 5: ... E F D CONDENSATE DRAIN 3 4 NPT H Table 2 Unit Dimensions Size Tons Dimensions A B C D E F G H 024 2 0 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 030 2 5 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 036 3 0 32 13 16 30 11 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 042 3 5 32 13 16 34 11 16 57 9 16 11 9 16 10 5 16 28 7 8 14 2 3 4 048 4 0 32 13 16 34 11 16 57 9 16 11 9 16 10 5 ...

Page 6: ...d be installed first The return air grille box and filter should be located and installed in the out rigger areas of the home Keep in mind the closer to the cooling unit the better The return ducting connects to the bottom of the return air box so it will be necessary to provide an opening beneath the box See Figure 5 Figure 5 Return Air Box and Grille After determining the location of the return ...

Page 7: ...ace 4 Make sure the duct is not stretched tight and does not have kinks from excessive length after installation 5 Attach the duct end with the stub collar to the air conditioner return air flange with screws and duct tape sealing the duct cover securely Wye Insulation It is necessary to field fabricate and install an insulation jacket for the Wye Insulation will prevent loss of capacity especiall...

Page 8: ...ound into the home To locate the center of the duct first cut a 6 hole in the fiberboard below the duct at the desired location After locating the duct center increase the hole in the fiber board to approximately the size of the duct connector Figure 8 Duct Connector With Damper Figure 9 Duct Connector No Damper May use duct connector without damper if no interior furnace or air handler is connect...

Page 9: ...in hose to the drain tube Service Access Access to all serviceable components is provided at the following locations Blower compartment access panel Control box access panel Refer to Figure 1 for location of these access locations and minimum clearances in Table 3 Power And Control Wiring Field wiring to the unit must conform to provisions of the current N E C ANSI NFPA No 70 or C E C and or local...

Page 10: ...tall on a partitioning wall not on an outside wall 3 Never expose it to direct light from lamps sun fireplaces etc 4 Avoid locations close to doors that lead outside to windows or to adjoining outside walls 5 Avoid locations close to radiators warm air registers or in the direct path of heat or cold air from them 6 Make sure that there are no pipes or ductwork in that part of the wall chosen for t...

Page 11: ...at temperature selection lever high enough to close the second stage of the thermostat if it is not already closed The indoor blower will turn on when the heating elements stage on If accessory heaters are not installed the blower will not run 9 Set the wall thermostat to the seasonal mode of operation heat or cool adjust the temperature selection lever to the desired setting Record the following ...

Page 12: ...ature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil temperature is above 40 F All defrost timing occurs only while the compressor is on During the defrost mode the defrost control will provide a 24 volt signal from terminal W1 66 to the fan control terminal W1 This signal will energize electric heat stage 1 if the unit is so equipped Fo...

Page 13: ...44 0 47 3 50 50 2PH08510706 4 9 6 5 1 23 5 27 1 51 8 56 3 60 60 2PH08511006 7 2 9 6 1 34 5 39 8 65 6 72 2 70 80 2PH08511506 10 8 14 3 1 51 7 59 7 87 1 97 1 90 100 208 230 3 60 8 2 72 0 16 0 1 6 4 1 None 18 5 25 042 3 5 208 230 1 60 17 1 86 0 26 5 1 8 7 6 None 30 8 40 2PH08510506 3 6 4 8 1 17 2 19 9 52 3 55 7 60 60 2PH08510706 4 9 6 5 1 23 5 27 1 60 1 64 6 70 70 2PH08511006 7 2 9 6 1 34 5 39 8 73 9...

Page 14: ... Recip Recip Recip Recip Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 28 11 28 11 28 16 16 16 Rows 2 2 2 2 2 2 Fins per inch 15 15 15 15 15 15 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined Intertwined Refrigerant Control TXV TXV TXV TXV TXV TXV EVAPORATOR COIL DATA Face area Sq Ft 4 67 4 67 4 67 5 44...

Page 15: ...136 1090 535 1161 High 2227 978 1086 1976 889 1129 1677 757 1151 048 4 0 Low 1260 275 807 1096 313 915 910 336 992 804 355 1057 774 290 979 Low Medium 1471 375 870 1338 415 968 1118 455 1079 963 474 1110 788 323 1016 Medium 1546 394 865 1391 439 975 1187 479 1080 1062 501 1088 892 347 1034 Medium High 1597 434 893 1460 476 989 1277 518 995 1079 515 1050 High 2227 978 1086 1976 889 1129 1677 757 11...

Page 16: ...0 19 0 20 0 23 1200 0 21 0 21 0 21 0 22 0 25 1300 0 23 0 23 0 23 0 24 0 27 1400 0 25 0 25 0 25 0 26 0 29 1500 0 27 0 27 0 27 0 28 0 31 1600 0 29 0 29 0 29 0 30 0 33 1700 0 31 0 31 0 31 0 32 0 35 1800 0 33 0 33 0 33 0 34 0 37 1900 0 35 0 35 0 35 0 36 0 39 2000 0 37 0 37 0 37 0 38 0 41 2100 0 39 0 39 0 39 0 40 0 43 2200 0 41 0 41 0 41 0 42 0 45 060 5 0 JP 500 0 09 0 09 0 09 0 10 0 12 600 0 1 0 10 0 ...

Page 17: ... CFM Heater kW 5 0 6 5 10 0 15 0 024 2 0 208 230 1 60 800 800 800 750 030 2 5 208 230 1 60 800 800 800 750 036 3 0 208 230 1 60 800 800 800 750 042 3 5 208 230 1 60 1300 1300 1270 1270 048 4 0 208 230 1 60 1300 1300 1270 1270 060 5 0 208 230 1 60 1300 1300 1270 1270 Table 10 Indoor Blower Specifications Size Tons Motor HP RPM Eff SF Frame 024 2 0 1 2 1100 0 8 1 0 48 030 2 5 1 2 1100 0 8 1 0 48 036...

Page 18: ...161036 YIM E 1008 18 Johnson Controls Unitary Products Typical Wiring Diagrams JP024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram ...

Page 19: ...161036 YIM E 1008 Johnson Controls Unitary Products 19 JP036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram ...

Page 20: ...nted in U S A 161036 YIM E 1008 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 161036 YIM D 1206 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 JP060 Typical Heat Pump 460 3 60 volt Wiring Diagram ...

Reviews: