5803641-JIM-B-0620
32
Johnson Controls Ducted Systems
–
–
Communication for SA BUS devices
EconCtrlr parameter reports UCB-to-economizer board SA BUS
communication status. Positive of the VDC (typically, a
fluctuating 1.5 to 3.5 volts reading to C; at least 0.25 volts lower
than +) SA BUS communication circuit to the UCB. Through the
unit wiring harness, may continue on to the 4-stage board and/or
fault detection & diagnostics board
+
+
Communication for SA BUS devices
EconCtrlr parameter reports UCB-to-economizer board SA BUS
communication status. Positive of the VDC (typically, a
fluctuating 1.5 to 3.5 volts reading to C; at least 0.25 volts higher
than –) SA BUS communication circuit to the UCB. Through the
unit wiring harness, may continue on to the 4-stage board and/or
fault detection & diagnostics board
ANALOG OUTPUTS Pin at center on upper edge of economizer board
J4
EX VFD
2-10 VDC positive output for the modulating
power Exhaust fan Variable Frequency Drive/
discharge damper modulating power exhaust
actuator
ExFanVFD parameter reports output status (0-100%) when
ExFType selection is Variable Frequency Fan; EAD-O parameter
reports output status (0-100%) when ExFType selection is
Modulating Damper. Used to ramp the power exhaust fan VFD/
position the discharge damper actuator.
COM
24 VAC common/0-10 VDC negative for the
power exhaust variable frequency drive/
discharge damper modulating power exhaust
actuator
Connects through circuit trace to 24V~ IN pin COM
24V~
24 VAC hot supplied for the discharge damper
modulating power exhaust actuator and
economizer actuator
Connects through circuit trace to 24V~ IN pin HOT
ECON
2-10 VDC output for the Economizer actuator
Econ parameter reports output status (0-100%). Used to position
the economizer actuator for minimum position, free cooling,
demand ventilation, cooling economizer loading and purge
functions
COM
24 VAC common/0-10 VDC negative for
economizer actuator
Connects through circuit trace to 24V~ IN pin COM
BINARY OUTPUTS Pin at right on upper edge of economizer board
J3
24V~
24 VAC hot supplied for an incremental
(floating control) economizer actuator
Connects through circuit trace to 24V~ IN pin HOT
ACT-A
24 VAC hot outputs to position an incremental
(floating control) economizer actuator
Unused in current control revision
ACT-B
24 VAC return
Unused in current control revision
COM
24 VAC common for an incremental (floating
control) economizer actuator
Connects through circuit trace to 24V~ IN pin COM
EX-FAN
24 VAC hot output to energize power exhaust
fan contactor coil/VFD enable relay coil
ExFan parameter reports output status (Off-On) when ExFType
selection is Non-Modulating, Modulating Damper or Variable
Frequency Fan. Used to turn on/enable the power exhaust fan
motor.
COM
24 VAC common/0-10 VDC negative for
economizer actuator
Connects through circuit trace to 24V~ IN pin COM
24V~ IN Pin connections at right on upper edge of economizer board
C
COM
24 VAC transformer Common referenced to
cabinet ground
24 VAC common connection to power the economizer board.
Connects through circuit traces to C/COM terminals and pins
distributed on the economizer board.
Table 14: Smart Equipment™ Economizer Board Details (Continued)
Board
Label
Cover
Label
Description
Function & Comments