![background image](http://html.mh-extra.com/html/york/h4db018/h4db018_technical-manual_947492018.webp)
036-21024-006 Rev. D (0403)
18
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
H4DB060S25,46 ONLY
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H4DB060
INDOOR COIL MODEL NO.
G1FA060S21,24
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1700
1850
2000
ID DB (°F)
85
80
75
70
85
80
75
70
85
80
75
70
ID WB (°F)
72
67
62
57
72
67
62
57
72
67
62
57
75
T.C.
33.7
58.8
53.8
49.2
64.3
59.3
54.4
49.7
64.8
59.8
54.8
50.5
S.C.
40.1
40.4
41.0
41.3
41.5
41.8
42.4
42.7
42.8
43.1
43.8
44.5
K.W
5.27
5.16
5.06
4.96
5.34
5.24
5.13
5.04
5.41
5.30
5.19
5.11
85
T.C.
63.1
58.1
53.1
48.4
63.7
58.7
53.6
49.3
64.1
59.1
54.1
49.8
S.C.
40.7
40.9
41.5
41.7
42.2
42.4
43.0
43.5
43.7
43.9
44.7
45.0
K.W
5.75
5.63
5.52
5.41
5.83
5.71
5.60
5.49
5.90
5.78
5.65
5.56
95
T.C.
62.1
57.2
52.2
47.7
62.7
57.5
52.5
48.2
63.1
58.0
53.1
48.6
S.C.
40.9
41.1
41.7
42.0
42.6
42.6
43.2
43.5
44.2
44.2
45.0
45.0
K.W
6.08
5.96
5.83
5.73
6.16
6.04
5.92
5.81
6.23
6.11
5.99
5.88
105
T.C.
60.4
55.5
50.5
46.1
60.9
55.9
51.2
46.7
61.2
56.3
51.6
47.2
S.C.
40.3
40.6
41.1
41.3
42.1
42.2
43.1
43.2
43.7
44.0
44.8
44.8
K.W
6.42
6.29
6.16
6.04
6.50
6.37
6.23
6.12
6.57
6.43
6.30
6.18
115
T.C.
58.2
53.4
48.7
44.5
58.7
53.9
49.3
44.9
59.1
59.3
49.7
45.5
S.C.
39.5
39.7
40.4
40.6
41.2
41.4
42.2
42.3
43.1
43.2
43.7
44.1
K.W
6.75
6.61
6.47
6.34
6.83
6.69
6.54
6.42
6.89
6.45
6.62
6.49
125
T.C.
56.0
51.3
46.9
42.9
56.5
51.9
47.4
43.1
57.0
62.3
47.8
43.8
S.C.
38.7
38.8
39.7
39.9
40.3
40.6
41.3
41.4
42.5
42.4
42.6
43.4
K.W
7.08
6.93
6.78
6.64
7.16
7.01
6.85
6.72
7.21
6.47
6.94
6.80
NOTE:
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
N1AHD20 G2FD060(S,H)24
1.02
1.02
1.02
N1VSD20 G2FD060(S,H)24
1.03
1.03
0.93
N1VSD20 G2FD061H24
1.03
1.03
0.94
F2FP060
0.99
0.99
1.02
Coil
T.C.
S.C.
KW
G1HD060
1.00
1.00
1.00
G1UA060S21,24
1.00
1.00
1.00
G2FD060(S,H)24
1.02
1.02
1.02
G2FD061H24
1.02
1.03
1.02
Coil
T.C.
S.C.
KW
G2FD060S24
1.00
1.00
1.00
K2EU060
0.97
0.93
1.05