ACCESSORIES

Refer to Price Manual for specific model numbers.

Hard Start Kit 

- Provides increased starting torque for areas

with low voltage.

Compressor Blanket -

 Designed to further reduce the nor-

mal compressor operating sound. Refer to price pages for
specific match-ups.

Off Cycle Timer Delay 

- Provides a 5-minute off cycle to pre-

vent rapid recycling of the compressor.

Room Thermostats 

- A wide selection of compatible thermo-

sets are available to provide optimum performance and fea-
tures for any installation.
1 Heat Stage only, manual, mechanical thermostat. Add sub-
base for 1H/1C.
1H/1C, manual change-over electronic non-programmable
thermostat.

1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the

price book or consult factory.

SOUND RATINGS

*Rated in accordance with ARI Standard 270.

TYPICAL INSTALLATION

TYPICAL FIELD WIRING - 1 Phase Application

UNIT MODEL

SOUND RATINGS 

DECIBELS

WITH SOUND

BLANKET

WITHOUT SOUND

BLANKET

024

72

76

030

74

79

036

76

76

042

76

75

048

77

78

060

80

81

THERMOSTAT

TO
INDOOR
BLOWER

TO COIL

NEC
CLASS 2
WIRING

NEC
CLASS 1
WIRING

TO
POWER
SUPPLY

WEATHERPROOF
DISCONNECT
SWITCH

Seal opening(s) with permagum
or equivalent

24” SERVICE ACCESS
CLEARANCE

48” OVERHEAD
CLEARANCE

12” REAR AND
SIDES

NOTE: All outdoor wiring must be weatherproof

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

POWER WIRING

208/230-1-60

CONTACTOR
TERMINALS

COIL

GND.

LUG

C

Y

R

G

W

Y

R

G

W

POWER WIRING
CONTROL WIRING
FACTORY WIRING

24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)

FURNACE OR AIR HANDLER TERMINAL BLOCK

ROOM THERMOSTAT

CONDENSING UNIT

ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.

TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.

*

*

Summary of Contents for H4AH024S06

Page 1: ... which protects the compressor if undesirable operating condi tions occur Additionally the unit has high and low pressure switch for extra protection against high pressure or loss of charge The compressor is protected by a 10 year limited warranty DURABLE FINISH Cabinet is made of powder painted steel over prepainted primer The pre treated flat galva nized steel provides a better paint to steel bo...

Page 2: ...urrent Device Amps 2 20 25 35 45 45 60 Compressor Type 3 Inertia Inertia ScrollC ScrollC ScrollC ScrollC Compressor Amps Rated Load 9 9 12 6 15 4 18 6 20 5 27 5 Locked Rotor 48 66 7 83 105 109 158 Crankcase Heater Yes Yes No No No No Fan Motor Amps Rated Load 0 86 0 86 1 2 1 2 1 2 1 2 Fan Diameter Inches 18 18 24 24 24 24 Fan Motor Rated HP 1 8 1 8 1 4 1 4 1 4 1 4 Nominal RPM 1050 1050 850 850 850...

Page 3: ...7 65 55 4 61 2 G2FD035 S H 14 65 55 4 61 2 G2FD036 S H 17 21 75 55 2 61 7 65 0 G2FD042 S H 21 78 65 5 69 10 G2FD046 S H 17 78 65 5 69 10 75 8 G2FD048 S H 21 24 84 67 13 69 12 75 10 G2FD060 S H 24 90 71 15 77 13 84 0 G2FD061H24 90 77 18 84 9 G1HD024 59 55 0 G1HD036 69 55 7 61 7 65 10 G1HD048 84 67 13 69 9 75 0 G1HD060 96 77 6 84 0 F2RC F2FC024 61 F2RC F2FC030 65 55 2 F2RC F2FC036 73 61 2 F2RP F2FP0...

Page 4: ... H 24 1600 48 0 36 1 13 00 11 85 H4AH060S06 N1VSD20 10 15 18 30 24 G2FD060 S H 24 1600 58 5 44 5 12 55 10 90 H4AH060S06 N1VSD20 10 15 18 30 24 G2FD061H24 1600 59 0 45 7 12 65 11 10 1 PH 12 SEER AC F2RP RC FP FC FV4 5 H4AH024S06 F2RC FC030 5 8 10 15 18 850 23 2 16 7 11 70 10 60 H4AH024S06 F2RP FP024 5 8 10 18 850 24 0 18 0 12 00 10 80 H4AH024S06 F2RP FP030 5 8 10 15 18 850 24 6 18 6 12 00 10 75 H4A...

Page 5: ... 11 35 10 10 14 G1FA036S14 1060 29 0 21 5 11 50 10 40 17 21 G1FA036S17 21 1060 28 8 21 5 11 50 10 25 G1HD036 1060 30 4 22 9 12 00 10 70 14 G1UA030S14 1060 28 4 21 2 11 35 10 10 14 G1UA036S14 1060 29 0 21 5 11 50 10 40 17 21 G1UA036S17 21 1060 28 8 21 5 11 50 10 25 17 G2FD030 S H 17 1060 28 8 21 5 11 50 10 25 14 G2FD035 S H 14 1060 28 8 21 5 11 50 10 25 17 G2FD036 S H 17 1060 30 2 22 6 12 00 10 50 ...

Page 6: ...0 59 0 43 4 12 00 10 50 G1HD060 1800 57 5 41 8 11 80 10 25 21 24 G1UA060S21 24 1850 59 0 43 4 12 00 10 50 24 G2FD060 S H 24 1850 59 0 43 4 12 00 10 50 24 G2FD061H24 1850 59 5 45 0 12 10 10 65 COOLING CAPACITY Upflow Downflow Horizontal Furnaces and Coils Continued UNIT MODEL FURNACE COIL MODEL COOLING CFM RANGE MIN MAX W RATED CFM NET MBH SEER W O TDR SEER TDR EER TOTAL SENS COOLING CAPACITY With ...

Page 7: ... 41 0 30 6 12 60 11 55 P1XUD20V G1FA060S24 24 1360 42 0 31 7 12 85 11 85 P1XUD20V G1UA060S24 24 1360 42 0 31 7 12 85 11 85 P1XUD20V G2FD048 S H 24 24 1360 42 0 31 3 12 75 11 80 H4AH048S06 P1DUB16V G1FA048S17 17 1500 47 0 32 3 13 00 11 90 P1DUB16V G1UA048S17 17 1500 47 0 32 3 13 00 11 90 P1DUC20V G1FA048S21 21 1610 47 0 35 5 12 40 11 40 P1DUC20V G1UA048S21 21 1610 47 0 35 5 12 40 11 40 P1DUC20V G2F...

Page 8: ...ent accessory information refer to the price book or consult factory SOUND RATINGS Rated in accordance with ARI Standard 270 TYPICAL INSTALLATION TYPICAL FIELD WIRING 1 Phase Application UNIT MODEL SOUND RATINGS DECIBELS WITH SOUND BLANKET WITHOUT SOUND BLANKET 024 72 76 030 74 79 036 76 76 042 76 75 048 77 78 060 80 81 THERMOSTAT TO INDOOR BLOWER TO COIL NEC CLASS 2 WIRING NEC CLASS 1 WIRING TO P...

Page 9: ...7 3 18 1 17 3 16 0 K W 2 38 2 33 2 27 2 22 2 41 2 36 2 30 2 25 2 43 2 38 2 32 2 27 115 T C 21 8 18 6 15 4 13 9 21 9 18 9 15 7 14 3 22 0 19 1 16 0 14 7 S C 15 9 15 8 15 0 13 4 16 4 16 4 15 3 13 8 16 9 16 9 15 6 14 1 K W 2 53 2 45 2 40 2 35 2 56 2 48 2 43 2 38 2 58 2 51 2 46 2 40 125 T C 19 7 16 2 12 8 12 1 19 8 16 3 13 1 12 5 19 8 16 7 13 5 13 0 S C 15 4 15 0 13 8 11 8 16 0 15 5 14 0 12 0 16 5 16 1...

Page 10: ... 2 96 2 87 3 21 3 13 3 02 2 94 115 T C 28 0 24 6 20 1 17 6 27 6 24 8 20 6 18 2 28 8 25 4 21 1 18 8 S C 19 8 19 5 18 5 17 2 21 4 20 2 19 6 17 9 21 8 21 9 20 7 18 5 K W 3 29 3 19 3 07 2 98 3 30 3 22 3 11 3 03 3 38 3 28 3 17 3 10 125 T C 25 9 21 8 17 0 15 1 24 6 21 8 17 4 15 7 26 5 22 5 17 8 16 3 S C 17 7 18 0 16 7 15 5 19 9 18 6 17 9 15 9 19 7 21 2 19 1 16 3 K W 3 48 3 35 3 22 3 13 3 46 3 37 3 26 3 ...

Page 11: ...99 125 T C 31 7 27 7 19 7 32 5 27 9 20 7 33 2 29 4 21 7 S C 27 5 25 1 20 4 27 1 25 0 21 9 26 7 25 6 23 3 K W 4 51 4 44 4 31 4 58 4 52 4 35 4 56 4 49 4 36 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB1206 G2FD036 S H 17 1 00 1 00 1 00 N1AHB1206 G2FD046 S H 17 0 99 0 99 0 98 N1AHD1406 G2FD048 S H 24 1 02 1 03 0 99 N1VSB12 G2...

Page 12: ...3 4 07 3 98 3 94 4 26 4 19 4 11 4 07 115 T C 37 8 35 3 30 9 26 4 38 9 35 6 30 9 27 2 39 9 36 0 30 9 28 0 S C 29 0 25 5 26 6 25 2 31 0 27 2 28 4 26 9 33 0 29 0 30 3 28 5 K W 4 40 4 34 4 22 4 22 4 52 4 46 4 32 4 31 4 65 4 57 4 45 4 43 125 T C 35 0 32 9 28 3 23 7 36 4 33 2 28 0 24 6 37 7 33 4 27 7 25 5 S C 29 4 24 0 25 3 23 5 31 6 25 8 27 4 25 2 33 7 27 6 29 4 26 9 K W 4 79 4 72 4 57 4 61 4 91 4 85 4...

Page 13: ... 7 43 6 40 0 35 2 S C 32 6 31 5 30 9 34 1 33 1 32 5 35 6 34 7 34 0 K W 5 23 5 15 5 02 5 29 5 23 5 10 5 35 5 32 5 19 125 T C 37 2 34 1 30 3 37 9 34 2 30 8 38 4 34 4 31 3 S C 31 2 30 3 29 6 32 4 31 8 31 3 33 7 33 4 32 9 K W 5 75 5 69 5 46 5 82 5 77 5 56 5 89 5 86 5 67 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHC1606 G2FD048...

Page 14: ... 5 70 5 62 5 50 5 75 5 67 5 56 5 80 5 73 5 63 105 T C 59 7 55 6 49 8 60 3 56 2 50 5 60 9 56 7 51 1 S C 42 5 40 7 41 2 44 2 42 0 42 0 45 8 43 2 42 8 K W 6 36 6 25 6 09 6 41 6 31 6 16 6 46 6 37 6 24 115 T C 55 8 51 6 45 2 55 9 52 2 45 7 56 0 52 7 46 1 S C 41 4 39 2 38 7 42 9 40 9 40 0 44 4 42 6 41 3 K W 7 12 6 99 6 84 7 17 7 04 6 92 7 23 7 10 7 00 125 T C 51 9 47 6 40 6 51 5 48 2 40 9 51 1 48 7 41 1...

Page 15: ...TION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE APPLICATIONS N1AH OR N1VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F2RC F2FC OR F2RC F2FP FAN COIL UNITS UPFLOW HORIZONTAL G2FD COIL ...

Page 16: ...e without notice Printed in U S A 036 21215 003 Rev B 1202 Copyright by York International Corp 2002 All rights reserved Supersedes 036 21215 003 Rev A 0602 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Reviews: